Professional Documents
Culture Documents
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
LOGO!
Innovative Switching & Control ... In detail
The Original!
Introduction
Wiring
Hardware assembly Connecting power supply Connecting inputs and outputs Switch-on behavior Connectors Basic functions Special functions Control for operation First program LOGO! in run mode Configuring LOGO! Help functions Realizing typical tasks step by step Modem wizard Other options Control of bottle filling conveyor
Integrated functions
Operation on device
Application example
Application example
Introduction
L1
K2
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
K2
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example E-Stand (ESx) 4 outputs 4 outputs Connection interface for LOGO! TD Backlit display Adjustable contrast The internal qualities count Switch for electrical connection
RUN/STOP
Maximum configuration: 24 digital inputs + 8 analog inputs +16 digital outputs + 2 analog outputs
Introduction
To connect LOGO! to the power supply: LOGO! ..... with DC supply voltage
L+ M L1 N
L+
I1
I2
I3
I4
I5
L1
I1
I2
I3
I4
Protection by fuse if required (recommended) for: 12/24 RC...: 24: 0.8 A 2.0 A
With voltage spikes, use a varistor (MOV) with an operating voltage at least 20% higher than nominal voltage.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
2-wire technology
3-wire technology
L+ M I1 I2 I3 I4 I5
I8
L1 N I1 I2 I3 I4
I5 I6
The inputs of these devices are grouped into 2 blocks of 4 I each. Different phases are only possible between, not within the blocks.
The inputs of these devices are nonisolated and therefore require the same reference potential (ground) as the power supply.
With 2-wire connections no correction of the impedance of the measurement line occurs. 3-wire connection suppresses this influence.
Introduction
DM8 24
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Q5 M Q1 M Q2 M
Q6 M
load
load
You can connect different loads to the outputs, e.g.: lights motors switches etc. ...
L1 / L+ 1 1 2 1 2
DM8...R
Q5 2 1 Q6 2
Q1
Q2
load
N/M
load
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
LOGO! with analog outputs You can connect different devices to analog outputs, e.g.: frequency converter to control drives Output signals: *) 0-10V 0-20mA 4-20mA
*)
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example Function keys Standard LOGO! keys unipolar power supply connector 12V DC, 24V AC/DC Recommended fuse: 0,5A LOGO! TD Cable 2,5m, extendable to up to 10 meters with standard Sub-D serial cable
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
whether a program is stored in the internal LOGO! memory or whether a memory card (memory module) is connected
s No Program Press ESC LOGO!
Warning!
If there is a program on the memory card, it is automatically copied to the internal LOGO! memory when switching on . Any program in the internal LOGO! memory is overwritten.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Q1
LOGO!
Prior to power-off
s
After power-on
s
I: 0.. 123456789 1..0123456789 2..01234
In RUN time
LOGO!
LOGO!
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
AQ1 AQ2
Analog I/O
C C C C
Cursor Keys
AM1 . AM6
F1 F2 F3 F4
Connectors
Introduction
AND
AND (edge)
OR
NOR
XOR
NOT
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
8 basic functions
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
A look at the circuit diagram shows that the light H1 is only on when S1 and S2 and S3 are closed. Input and output states are dependent on each other. The circuit to the right is called AND logic. In words contact S1 and S2 and S3 have to be closed for the light to burn. Symbol for this connection is .
S1 S2 S3
H1
AND
S1 S2 S3 x
&
H1
Output of the AND function is 1 only when all inputs are 1. If one input pin of this block is not connected, the status is automatically 1.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
To turn the lamp H2 on, the contact S1 or S2 or S3 have to be closed. The dependence of output states from inputs states is called OR logic. In words at least one of the contacts S1 or S2 or S3 have to be closed for the lamp H2 to light up. Symbol for this connection is .
S1
S2
S3
H2
OR
S1 S2 S3 x
>
Logic table for OR block: Input 1 Input 2 0 0 1 1 0 0 1 1 Input 3 0 1 0 1 0 1 0 1 Output 0 1 1 1 1 1 1 1
Output of the OR function is 1, when at least one input is 1. If one input pin of this block is not connected, the status is automatically 0.
0 0 0 0 1 1 1 1
Introduction
S1
Electro mechanical counter
S1
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
S2
0 6 1 5
S3
S2
S3
H2
H2
&
H2
Output of AND with edge triggering is 1, only when all inputs are 1 and in the previous cycle at least one input was 0. If one input pin of this block is not connected, the status is automatically 1.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
A look at the circuit diagram shows that the light H2 is not on, only when all contacts are switched. The circuit to the right is called NAND logic. In words S1 and S2 and S3 have to be switched for the light H2 not to burn. Symbol for this connection is .
S1
S2
S3
H2
NAND
S1 S2 S3 x
&
H2
Output of NAND is 0, only when all inputs are 1. If one input pin of this block is not connected, the status is automatically 1.
Introduction
S1
S3
S3
0 6 1 5
S1 S2
Wiring
H2
Integrated functions
Electro mechanical counter
S3 H2
&
H2
Output of NAND with edge triggering is 1, only when at least one input is 0 and in the previous cycle all inputs were 1. If one input pin of this block is not connected, the status is automatically 1.
Introduction
A look at the circuit diagram shows that the light H1 is only on, when the normally closed contact S1 and S2 and S3 are not switched. The circuit to the right is called NOR logic. In words when S1 or S2 or S3 are switched, the light is not on. Symbol for this connection is .
S1
S2
S3
NOR
Operation on device LOGO! Soft Comfort V6.1 Application example Output of NAND is 1, only when all inputs are 0. As soon as any input is switched (status 1), the output is switched off. If one input pin of this block is not connected, the status is automatically 0.
S1 S2 S3 x
H1
>1
H1
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
A look at the circuit diagram shows that the light H1 is only on, when only one of either S1 or S2 is switched. This circuit is called XOR logic. In words when either contact S1 or contact S2 are switched, the light is on. Symbol for this connection is .
S1 S2
H1
XOR
S1 S2
=1
H1
Output of XOR is 1, when inputs have different states. If one input pin of this block is not connected, the status is automatically 0.
Introduction
A look at the circuit diagram shows that the light H1 is only on, when the switch S1 is not switched. This circuit is called NOT logic. Symbol for this connection is .
S1
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
K1
H1
NOT 1
S1 H1
Output is 1, when the input is 0, i.e. NOT inverts the status at the input. The advantage of NOT is for instance: You will not need a normally closed contact any more for LOGO!. You can use a normally open contact and change it with NOT to a normally closed contact. If the input pin of this block is not connected, the status is automatically 1.
Introduction
On-delay
Timer
On-/ Off-delay Off-delay Analog comparator Retentive On-delay
Analog
Analog amplifier PWM Analog threshold trigger Analog differential trigger Random generator PI controller Yearly timer Analog watchdog Ramp Analog MUX Analog Math
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Wiping relay Pulse generator (pulse output) Edge triggered wiping relay
Miscellaneous
Latching relay Pulse relay Message text Up/Down counter
Counter
Hours counter
Threshold trigger Softkey Shift register Analog Math Error Detection
31 special functions
Introduction
A look at the circuit diagram shows that the motor only starts after expiry of the delay time. This function is called On-delay. In words the motor will be switch on with a programmed ON delay time. Symbol for this function is .
S1
K1
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
K1
Diagram:
Trg Q T Ta (Timer active) T
Description of the function: With 0 to 1 transition of input Trg the timer starts. If the status of input Trg is 1 for long enough, the output is set to 1 on expiration of the time T. The output follows the input with on delay. The output is reset to 0 when the status at input Trg is 0. If the status of input Trg changes to 0 before the time T has expired, the time is reset. The time elapsed is reset after a power failure.
Introduction
A look at the circuit diagram shows that the motor only stops after expiry of the delay time. This function is called Off-delay. In words the motor will be switch off with a programmed OFF delay time. Symbol for this function is .
S1
K1
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
K1
Diagram:
Trg Ta R Q (Timer active) T T
Description of the function: When the input Trg is 1, the output Q is switched instantaneously to 1. When the status of Trg changes from 1 to 0, the timer will be activated. The output remains set. When the timer reaches the configured value (Ta=T), output Q is reset to 0. When input Trg is switched on and off again, the time Ta restarts. Input R (Reset) is used to reset the time Ta and the output before Ta has expired.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
A look at the circuit diagram shows that: when S1 is closed, contact K1 closes with a delay time and the motor runs. when S1 is opened, contact K2 opens with a delay time and the motor stops. This function is called On-/Off-delay. In words the motor is switched on and off with a programmed delay time. Symbol for this function is .
S1
K1
K2
K1 K2 M
Diagram:
Trg Q TH TL
Description of the function: The time TH starts after a 0 to 1 transition at input Trg. If the status at input Trg is 1 for the duration of the time TH, the output is set to 1 on expiration of the time TH. (the output follows the input on delayed). When the status at input returns to 0, TL starts. If the status at input Trg is 0 for the duration of time TL, the output is set to 0 on expiration of the time TL.
Introduction
A look at the circuit diagram shows that the motor M starts delayed after pressing the pushbutton S1. Pushbutton S2 (n.c. contact) stops the motor again. This function is called retentive On-delay. Symbol for this connection is .
S1 S2
K1
K1
K2
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
K1
K2
Diagram:
Trg R
Q T
Ta
Description of the function: The current time Ta starts with a 0 to 1 transition at input Trg. Output Q is set to 1 when Ta reaches the time T. The output Q is only reset to 0 when the status at input R is 1. Further switching actions at input Trg have no influence on output Q.
Introduction
A look at the circuit diagram shows that the light H1 is only on, when the switch S1 is closed, but only as long as the set time at timer T1. Symbol for this connection is .
S1
T1
T1
H1
Diagram:
Operation on device LOGO! Soft Comfort V6.1 Application example Description of the function: When the input Trg is set to 1, the output Q is immediately switched to 1. The current time Ta starts in LOGO! at the same time and the output remains set. When Ta reaches the value specified in T (Ta=T), the status of output Q is reset to 0 (pulse output). On input Trg transition from 1 to 0 before the specified time has expired, the output follows immediately with a 1 to 0 transition.
Trg
Ta
Introduction
A look at the circuit diagram shows that the light H1 remains on for the time specified on the timer T1 when the switch S1 is closed. Symbol for this connection is .
S1
T1
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
T1 T1 H1
Diagram:
Trg Ta T T
Description of the function: The output status is switched to 1 after the input Trg is set to 1. Time Ta is started at the same time. After Ta has reached the value specified in T (Ta=T) the output Q status is reset to 0 (pulse output). If input Trg changes again from 0 to 1 (retriggering) before the specified time has expired, the time Ta is reset and the output remains switched on.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
The output is controlled via a specified on/ offdate. The function supports any combination of weekdays. You select the active weekdays by deselecting the inactive days.
Mon Tue WedThurs Fri Sa So
On : 07 30 : 08 00 : 10 00
Off 16 05 12 00 12 30
Wednesday
Description of the function: Every weekly timer has three cams. You can configure a time hysteresis for each cam. Within the cam setting you specify the on/off times.
Monday
If you enable pulse output, the timer will be reset after one cycle. Pulse output applies to all three cams.
Introduction
Description of the function: Every yearly timer has an on- and off-timer. At the specified on-time the yearly timer switches on the output. At the specified offtime the yearly timer switches off the output. The offdate specifies the day/year on which the output is reset to 0 again. By selecting the option field Monthly, the timer switches on or off at a specified day each month. Yearly, the timer switches on or off each year at a specified month and day. Pulse Output, the timer output switches on at the specified On Time for one cycle. Then it is reset.
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
On 05.10
Off 10.20
15.05.2005
15.05.2005
08.11.2005
08.11.2005
Introduction
The pulse profile of the output can be customized via pulse/ pause ratio. Symbol for this function is .
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Diagram:
En
Inv
Q
pulse period / pause width
Description of the function: In the parameters you can adjust the pulse period and the pause width. With input INV you can also invert the output. You can customized the time period in seconds, minutes or hours. The time basis of both parameters can be set independently. The input block INV only negates the output if it is enabled via EN.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
With a random generator the output is switched on and off again within a specified time. Symbol for this function is .
Diagram:
En
Q
max. ON delay / max. OFF delay
Description of the function: With a 0 to 1 transition of the input En a random time e.g. between 0 and 10 seconds is started. The output is set to 1 on expiration of the on delay time, if the input En is 1 at least for the duration of the on delay time. The time is reset if the status at input En returns to 0 before the on delay time has expired. When the input En changes from 1 to 0, a random off delay time between 0 and e.g. 15 seconds is started. The time is reset if the status at input En returns to 1 before the on delay time has expired.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
The input pulse (edge control) starts a specified time. The output is reset on expiration of this time. Prior to the expiration of this time (e.g. 15 s) an off prewarning is generated. Symbol for this function is .
Diagram:
Trg Ta Q T (OFF delay) 1s 15s
Description of the function: With a 0 to 1 transition at input Trg, the current time starts and the output Q is set to 1. E.g. 15 s before Ta reaches the time T, the output Q is reset to 0 for a time of 1 s (configurable time). When Ta reaches the time T, the output Q is reset to 0. When input Trg is switched on and off again before Ta expires, Ta is reset (retriggering option).
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Switch with two different functions: Pulse switch with off delay Switch (continuous lighting) Symbol for this function is .
Diagram:
Trg
Q 5s
>20s
Description of the function: The output Q is set to 1 with a 0 to 1 transition of the status at input Trg. When the input Trg changes to 0 before expiration of the continuous lighting time, the output resets to 0 with an off delay of e.g. 5 seconds. With a 0 to 1 transition of the status at input Trg and if the status 1 is set at least for the duration of e.g. 20 seconds, the continuous lighting function is enabled and the output Q is switched on continuously. If the input Trg is switched once again from 0 to 1 and again to 0, the output Q is switched off.
Introduction
A look at the circuit diagram shows that the switch S1 triggers the counter pulses. Switch S2 determines whether the counter increases or decreases. When the counter status reaches a value >= 5, the light switches on.
Wiring
Diagram:
Integrated functions Operation on device
2
Cnt Dir
6 5 4 3 5 4 3 2 3 2 4 3 5 6
S1
S2
1
0
Counter R Q
C1
>=5 H1
With every positive edge at input Cnt the internal counter increments (Dir = 0) or decrements (Dir = 1) by one count. Output Q is set to 1 when the internal value is greater than or equal to the value specified in Par. You can use reset input R to reset the output and the internal count value to the start value. When R=1, the output is 0 and the pulses at input Cnt are not counted. If you set a Start Value the counter begins to count either up or down from this value.
Introduction
R En Ral Q MN = MI
3 2 1 0 3 2 1 0
MN = 0
3 2 1
OT Application example Description of the function: The hours counter monitors the input En. As long as the status of this input is 1, LOGO! determines the expired time OT and the timetogo MN. LOGO! displays the times in parameter assignment mode. Output Q is set to 1 when the timetogo MN = 0. Use input R to reset output Q and timetogo counter to the specified value MI. The internal counter OT continues the count. Use input Ral to reset output Q and the timetogo counter MN to the specified value MI. The internal counter OT is reset to 0.
Introduction
The output is switched on and off, depending on two specified frequencies. Symbol for this function is .
Diagram:
Fre > On Q Fre > Off Fre < Off Fre < On
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Fre =12 Fre = 5 Fre gate time On = 10 Off = 4 Fre = 3 Fre = 5
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Description of the function: The output is switched on when the analog value exceeds a specified on threshold. The output is switched off when the analog value drops below a specified off threshold (hysteresis). This function reads the analog value AI1 to AI8 as a value between 0 and 1000. The offset parameter is then added to the analog value. The result is multiplied by the gain parameter. Output Q is set to 1 if this value exceeds the on threshold (On). Q is reset to 0 again after the value drops below the off threshold (Off).
Diagram:
Introduction
Description of the function: The function calculates the difference between the analog values Ax-Ay. The offset parameter is added to the difference. Then the difference is multiplied by the gain parameter. If this differential value exceeds the parameterized threshold, output Q is set to 1. Q is reset to 0, when the threshold drops below again.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Diagram:
Introduction
Description of the function: The function reads the analog value of the signal at analog input Ax. This value is multiplied by the gain parameter. The offset parameter is added to the analog value. Output Q is set or reset depending on the specified threshold (On) and the differential value ( ).
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Diagram:
Timing diagram A: Function with negative differential delta value
Introduction
Description of the function: If the status at input En changes from 0 to 1, then the analog value of the signal at analog input Ax will be saved. This saved value is called Aen. The updated values Ax and Aen are each multiplied by the gain parameter. Then the offset parameter is added to the analog value. Output Q is set, if the input En is 1 and the updated value at the input Ax is outside of the range of Aen +/. Threshold 1 defines the difference value above Aen, Threshold 2 defines the difference value below Aen.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Diagram:
Introduction
Description of the function: The function reads the analog value of the signal at analog input Ax. This value is multiplied by the gain parameter. Then the offset parameter is added to the analog value, i.e. (Ax * gain) + offset = updated value Ax. Output AQ shows the updated value Ax.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Description of the function: If the input A/M is set to 0, then the special function sets output AQ with the value that is set with parameter Mq. If the input A/M is set to 1, then automatic mode commences. As an integral sum the value Mq is adopted, the controller function begins the calculations of the formulas. The updated value PV is used within the formulas. Updated value PV = (PV * gain) + offset If the updated value PV = SP, then the function does not change the value of AQ. With a disturbance, AQ continues to increase / decrease until the updated value PV again corresponds to SP. The speed with which AQ changes depends on the parameters KC and TI. If the input PV exceeds the parameter Max, then the updated value PV is set to the value of Max. If the PV falls short of the parameter Min, then the updated value PV is set to the value of Min. If the input R is set to 1, then the AQ output is reset. As long as R is set, the input A/M is disabled. The sampling time is fixed at 500 ms.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Parameter: Sensor: Type of sensor used Min: Minimum value for PV Max: Maximum value for PV Gain: Gain for PV Offset: Zero offset for PV SP: Set point assignment Mq: Value of AQ in manual mode Parameter sets: applied presets for KC, TI and Dir KC: Gain TI: Integral time Dir: Action direction of the controller Number of decimal places in message text
Introduction
Parameter sets:
To simplify the use of the PI controller, parameters for KC, TI and Dir are preset as sets for the following applications:
Wiring
Parameter Set Applications Temperature, low temperature control for small rooms; small volumes
Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Parameter KC 0.5
Parameter TI (s) 30
Parameter Dir
Heater, ventilation, temperature, low temperature control for large rooms, large volumes
Fast pressure change, compressor control Slow pressure change, Differential pressure control (flow control) Barrel, container filling without downpipe/ drain Barrel, container filling with downpipe/ drain
1.0
120
3.0
Pressure 2
1.2
12
1.0 0.7
1 20
+ +
Parameters can manually be specified via the parameter set User defined.
Introduction
Description of the function: At the analog output, this special function starts up one of two levels or offset. Here you can set how quickly the level should be reached. If the input En is set, then the function issues the value StSp + offset at output AQ for the first 100 ms. Then, depending on the connection of Sel, the function runs from value StSp + offset to either level 1 or level 2 at the acceleration set in Rate. If the input St is set, the function runs to the value StSp + offset at the acceleration set in Rate. Then the function issues the value StSp + offset at output AQ for 100 ms. Finally offset is issued at output AQ. If the input St is set, the function can only be restarted once the inputs St and En have been reset. If input Sel has been changed, depending on the connection of Sel, the function runs from level 1 to level 2 or the other way round. If the input En is reset, the function immediately issues offset at output AQ. The analog value at the output is recalculated every 100 ms.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction Parameter: Gain: Gain for AQ in message text Offset: Zero offset for AQ in message text L1 and L2: Levels to be reached Largest output value: Maximum value that must not be exceeded under any circumstances Start/ stop offset: value that is issued for 100ms in addition to parameter offset after starting the function and before reaching the offset value (prompted by input St). This parameter is intended for controlling motors. Speed of change: Acceleration with which level 1, level 2 or offset is reached. Steps/ second are input. Number of decimal places in message text
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Diagram:
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Description of the function: This special function outputs one of four predefined analog values or 0 at the analog output. If input En is set, then the function issues one of 4 possible analog values V1 to V4 at output AQ, depending on the value of S1 and S2. If the input En is not set, then the function issues the analog value 0 at output AQ. All 4 analog values V1 to V4 can be parameterized as a reference to another analog function, so the analog values can be dynamically changed in runtime (e.g. via potentiometer at an analog input).
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Description of the function: The PWM function modulates the analog input value Ax into a pulsed digital output signal. The pulse width is proportional to the analog value Ax. The function reads the value of the signal at the analog input Ax. This value is multiplied by the value of parameter A (gain). Parameter B (offset) is added to the product, as follows: (Ax * Gain) + Offset = Actual value Ax The function block calculates the proportion of the value Ax to the range. The block sets the digital output Q high for the same proportion of the PT (periodic time) parameter, and sets Q low for the remainder of the time period.
Introduction
Calculation rule : Q = 1, for Ax / (Max - Min) of time period PT Q = 0, for PT - [Ax / (Max - Min)] of time period PT
Note: Ax in this calculation refers to the actual value Ax as calculated using the Gain and Offset. Min and Max refer to the minimum and maximum values specifed for the range.
Example 1:
Operation on device LOGO! Soft Comfort V6.1 Application example Periodic time (PT) = 4 sec. Ax = 500 1) 500 / (1000-0) = 0,5 2) 4 sec. * 0,5 = 2 sec. Q = 2 sec. high , 2 sec. low
Example 2:
Periodic time (PT) = 10 sec. Ax = 300 1) 300 / (1000-0) = 0,3 2) 10 sec. * 0,3 = 3 sec. Q = 3 sec. high , 7 sec. low
Introduction
Description of the function: The function combines four values and three operators to form an equation. The operator can be any one of the four standard operators: +,-,x,/ For each operator, you must set a unique priority of High ("H"), Medium ("M"), or Low ("L"). The high operation will be performed first, followed by the medium operation and the low operation. The operand values can reference another previously-defined function to provide the value. You can also configure the behavior of the function when the Enable parameter "En"=0. The function block can either retain its last value or be set to 0. The result is an internal analog value (-32768 - +32767). A result out of this range causes an overflow-error.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Operator / Priority Value 1
Value 2
Value 3
Value 4
Introduction
Examples:
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example Description of the function: The analog math error detection block sets the output when the referenced analog math function block has an error. You can program the function to set the output on a zero division error, an overflow error, or when either type of error occurs. If you select the Automatically reset checkbox, the output is reset prior to the next execution of the function block. If not, the output retains its state until the analog math error detection block is reset with the R parameter.
Introduction
A look at the circuit diagram shows that the coil K1 has current with the pushbutton S1. The switch K1 closes (latch). This function is called latching relay. Symbol for this connection is .
S1 S2
K1
K1
K1
K2
Diagram:
S
Application example
Q
Description of the function: Input S sets output Q, input R resets output Q again.
Introduction
A look at the circuit diagram shows that the light H1 is switched on and off with the pushbuttons S1 or S2. This function is called pulse relay. In words a short pulse at S1 or S2 switches the light H1 on and off. Symbol for this connection is .
S1
S2
K1
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
K1
H1
Diagram:
Trg
Description of the function: Output Q changes its status, i.e. the output is set or reset, with each 0 to 1 transition at input Trg. You reset the pulse relay to 0 with a signal at input R.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Features:
Only one programming tool for basic module and LOGO! TD
Selection / enabling of different character sets Up to 24/32 characters per line
(depending on selected character set)
Ticker text Selection of message destination Bar graph functionality Display state of analog input values Digital I/O states Display of remaining time of all timers (except weekly/yearly timer)
Introduction
Display of a configured message text in run mode. Symbol for this function is .
Wiring Integrated functions Operation on device Description of the function: LOGO! Soft Comfort V6.1 Application example With a 0 to 1 transition of the input signal and when the system is in RUN, the corresponding message text is output to the display. The message text is hidden when the status of the signal at input changes from 1 to 0. When multiple message text functions are triggered with En=1, the message text that has the highest priority is shown. Changing between the standard display and the message texts display is possible by using the keys and . If acknowledge message is chosen, the respective message text will be hidden by pressing any key on LOGO!, if En=0.
s Motor on
I: 0.. 123456789 1 234 Alarm! 1..0123456789 Current Temp ESC OK 2..01234
97 LOGO C
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
To be able to use all features of the message text function in LOGO! ..0BA6, Use new feature must be enabled (File -> Message text settings). LOGO! ..0BA6 supports several languages. To ensure, that all characters of a language used in a message text can be displayed correctly, it is necessary to activate an accordant character set. 6 character sets are available *)
ISO_8859_1 ISO_8859_5 German, English, Italian, Spanish (partly), Dutch (partly) Russian
ISO_8859_9
ISO_8859_16 GBK SJIS *)
Turkish
French Chinese Japanese (partly)
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Character set 1 (e.g. ISO_8859_1)
In the same message text 2 different character sets can be selected. By using the Flag M27 character set 1 or character set 2 gets activated.
Introduction
For the LOGO! on-board display and for LOGO! TD ticker text can be used. You can ticker the text in 2 ways: Character by character or Line by line
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Character by character (one character after another tickers through the display)
1st
half
2nd
half
or Line by line. (the display alternates between the 1st half and the 2nd half of the message text)
In the function block message text you can choose Character by character or Line by line and enable one or more lines which shall be tickered.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
The ticker speed can be adjusted via the menu item File -> Message Text Settings -> Ticker Timer Setting . You can set the speed for Character by character in milliseconds. This time has also effect to the time for Line by line (Character by character x10).
Message destination is another properties parameter in the function block message text: Here you can decide, on which device the message text shall appear: LOGO! on-board display LOGO! TD Both displays
Introduction
Example 1:
Step 1: Click at Insert a bar graph into the message Step 2: Select a function block which is already placed in the circuit diagram to indicate its value.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Step 3: Scale the bar graph by defining the range of the value, bar graph size and its direction on the display.
The vertical adjustment of the bar graph is from the bottom to the top !
Introduction
Example 2:
The analog value of a temperature sensor (PT100) is to be indicated over its entire measuring range as bar graph horizontally in the message text.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
2 analog input values (AI) can be displayed in one message text if they are used in the circuit diagram.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example If an analog input value is indicated in a message text, via the menu item File -> Message Text Settings can be defined, how often LOGO! refreshes the analog values in a message text.
Introduction
You can assign names such as "On" or "Off" to the two states of a digital input or output. With the LOGO! 0BA6 series, you can display this name of a digital I/O state in a message text.
Wiring
Example:
Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example Step 2: Open message text with a double click, define area for the status indication of I1 with a mouse click and select ON/OFF button. Step 1: Place 1 input, 1 output and an enabled message text in your circuit diagram.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example Step 4: Automatically the first input I1 is selected. Type in a text you want to display for both states of I1.
Introduction
Step 5: Do the same for Digital Outputs and display the state of Q1.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Wiring
Integrated functions
Application example
LOGO! Soft Comfort V6.1 provides a static editor for message texts that can help when you need to reposition text elements. For example, it has a recycle bin area where you can temporarily move message text elements in order to rearrange the position of elements on the display area. You can move elements up, down, left, or right without changing the position of any other elements. To use the static editor, click the "Edit manually" button. You will also be prompted to edit manually if you try to place or move elements in the message area that have a position conflict with existing elements.
Introduction
Description of the function: This special function has the effect of a mechanical pushbutton or switch. In parameter assignment mode, the output is set with a signal at input En, if the Switch parameter is set to On and confirmed with OK. Whether the function was configured for pushbutton or switching action is of no concern here. The output is reset to 0 in the following three cases: After a 0 to 1 transition at input En. When the function was configured for momentary pushbutton action, and one cycle has expired since it was switched on. When the position Off was selected at the Switch parameter and confirmed with OK in parameter assignment mode.
Diagram:
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Description of the function: The function reads the value at input In with a positive edge at input Trg. This value is applied to shift register bit S1 to S8, depending on the shifting direction: Shift up: The value at input In is set at S1; the previous value at S1 is shifted to S2; the previous value at S2 is shifted to S3 etc. Output Q returns the value of the configured shift register bit. If retentivity is disabled, the shift function restarts at S1 to S8 after a power failure. When enabled, retentivity always applies to all shift register bits.
Diagram:
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
S4 = Q (example)
Shift up
Shift down
Introduction
Have you designed a circuit? Do you want to enter it into LOGO! ? How do you do this?
Wiring
s
Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example Connect LOGO! to the power supply and switch it on. The display now shows you this message.
LOGO!
s
Press ESC to get to the main menu.
ESC OK
s
> Program.. Card.. Setup.. Start LOGO! s > Edit.. Clear Prg Password Msg Config LOGO! s
Here you can also move the > cursor by pressing Move the > cursor to Edit.. and confirm with OK . In the next sub-menu please chose Edit Prg. You are now in programming menu. .
Introduction
The first character in the first line is the > cursor. Press to move the > cursor up and down. Move it to Program.. and confirm with OK . LOGO! opens the programming menu.
ESC OK
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
ESC OK
ESC OK
Press to select all output, marker and open connectors. The following applies when you edit a circuit: ....
B1
Q1
ESC OK
LOGO!
Introduction 1. You have to create your circuit by working from the output to the input.
I1
Q1
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
B002
Q1
&
B002
>
B002
B001
Q2
3. You cant connect an output to an upstream input within the same path (recursion).
&
&
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
B02
1 I3 B01
x B02 I1 x &
B01 Q1
x B02 I1 x &
Introduction 5. When the cursor appears as a solid square ( ), press with to select a connector (Co), a basic function (GF) or a special function:
&
Q1 SF Q1
B1
B1 OK
B1 OK
Application example
&
Q1
&
Q1
&
Q1
&
Q1 OK GF Q1
&
Q1
>1
Q1
Co Q1
Introduction
Let us now take a look at the following parallel circuit consisting of two switches.
Circuit diagram
K1 E1
S1 K1
S2
LOGO! interprets the parallel circuit of S1 and S2 as an OR logic, because S1 or S2 switches on the output.
>1
Q1
Introduction
L1 N
S1 S2 I5 I6 I7 I8 L1 N I1 I2 I3 I4
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
S1 switches input I1, while S2 switches input I2. The load (E1) is connected to the relay Q1.
Q1
ESC OK
LOGO! 230RC
Let us now input the program (starting at the output and working towards the input). LOGO! initially shows the output Q1. You will see an underscore ( _ ) below the Q in Q1. It is called a cursor. The cursor indicates your current position in the program.
L1 E1 N
Q1
Q2
Q3
Q4
Introduction
Wiring Q1 Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example The cursor is displayed as a solid square ( ): Selected between the following by pressing : Connector (Co) Basic function (GF) Special function (SF)
ESC OK
The cursor indicates your current position in the program. At this point you only enter the first block (the OR block). Press OK to select editing mode.
LOGO! s
Q1
ESC OK
LOGO!
s
Co
Q1
ESC OK
LOGO!
Introduction
Wiring GF Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example Q1
ESC OK
LOGO!
s
The AND is the first block of the basic functions (GF) list. You can choose between the following by pressing : AND AND (edge) NAND NAND (edge) OR NOR XOR NOT Select the OR block ( >1 ) and confirm with OK . In1 In2 In3 In4 B1 >1 Q1
ESC OK
LOGO! s
In1 In2 In3 In4
B1 >1 Q1
ESC OK
LOGO!
Introduction You have now entered the first block. Each new block is automatically assigned a block number (B1). Now you interconnect the block inputs (B1). Press OK . The cursor is displayed as a solid square ( ): You can choose between the following by pressing : Connector (Co) Basic functions (GF) Special functions (SF) Please select Connector (Co) and confirm with OK . The first element of the list (Co) is input I1 Confirm with OK . The underscore cursor automatically jumps to the next input (In2) that needs to be allocated. Co In2 In3 In4
s
B1
>1 Q1
ESC OK
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
LOGO! s
I1 In2 In3 In4 B1 >1 Q1
ESC OK
LOGO!
s
I1 In2 In3 In4 B1 >1 Q1
ESC OK
LOGO!
.
Introduction Now you connect input I2 to the input of the OR block. You already know how to do this: 1. Switch to editing mode: Press OK 2. To select the Co list: Press 3. To confirm the Co list: Press OK 4. To select I2: Press 5. To apply I2: Press OK We do not need the last two inputs of the OR block for this program. In the LOGO! program you mark the unused inputs with an X. The process is the same: 1. Switch in editing mode: Press OK 2. To select the Co list: Press 3. To accept the Co list: Press OK 4. To select X: Press 5. To apply X: Press OK I1 Co In3 In4
s
B1
>1 Q1
ESC OK
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
LOGO! s
I1 I2 In3 In4
B1 >1 Q1
ESC OK
LOGO! s
I1 I2 X X B1 >1 Q1
ESC OK
LOGO!
s
I1 I2 X X Now all block inputs are connected. For LOGO! the program is complete. You can review your first program by pressing the cursor with the 4 arrow keys ( _ ) and moving through the program. We now exit program input mode and return to the programming menu with ESC . The program is automatically saved in the internal memory (E2PROM). To start the program, return to the main menu with ESC . Move the cursor to Start: Press confirm press OK . . To B1 >1
Q1
ESC OK
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
LOGO! LOGO! s > Edit Prg Edit Name AQ Memory? LOGO! s > Edit.. Clear Prg Password Msg Config s Program.. Card.. Setup.. > Start LOGO!
ESC OK
ESC OK
ESC OK
Introduction
In RUN mode LOGO! shows the following display: Status of inputs 1 Input I status is 1 1 Input I status is 0 Status of outputs 1 Output Q status is 1 1 Output Q status is 0
S1
=1 =0 S2
Q: 0.. 1 23456789 1..0123456 AI : I: 0.. 1 23456789 1.. 0123456789 2.. 01234
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Tu 09:14 2009-09-22
The window to the left displays time and date. The window in the middle displays the inputs states (I1 to I9; I10 to I19; I20 to I24). The window to the right displays outputs states (Q1 to Q9; Q10 to Q16). Also the internal values of all analog inputs/outputs can be displayed.
=1 Q1
When switch S1 is closed, input I1 is supplied with voltage and the status at input I1 is 1. LOGO! program calculates the status for the outputs. Output Q1 is 1, in this case. When Q1 is 1, LOGO! sets relay Q1, and the load connected to Q1 is supplied with voltage.
Introduction Parameterization of functions: Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example When speaking of parameterization, we refer to the configuration of functions. You can configure the parameters in programming mode or in parameter assignment mode You can configure: the delay times of timer functions the switching times of timer switch counter thresholds the monitoring interval for a hour counter on and off threshold for a trigger threshold and some other functions To get to configuration mode press ESC in RUN mode, set the cursor to Set Param and confirm with OK . I: 0.. 123456789 1..0123456789
sLOGO! 12/24 RC
2..01234
ESC OK
LOGO!
LOGO! 12/24 RC
Stop
LOGO!
Introduction
s B2 T =10:00s Ta =00:00
ESC OK
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Block selection: Choose In parameterization mode the desired block with . If the desired block is chosen, press OK . The cursor jumps to the first parameter that can be modified. The value can be changed pressing the arrow keys . If the desired value is configured, then press OK . The next blocks requiring modification, can be chosen with etc..
LOGO!
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
LOGO!
To return to RUN mode press ESC .
ESC OK
LOGO!
Introduction
You can select the menu language via the LOGO! menu and acknowledge with OK (LOGO! must be in Stop-mode).
s Program.. Card.. > Setup.. Start LOGO! s Clock.. LCD.. > Menu Lang BM AI NUM
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Available languages:
EN English IT Italian NL Dutch ES Spanish FR French CN Chinese DE German TR Turkish RU Russian JP Japanese *)
ESC OK
ESC OK
LOGO! s
> EN
This setting can be separately done for LOGO! TD .
ESC OK *) since E-Stand 3 (ES3)
LOGO!
s
Program.. Card.. > Setup.. Start s LOGO!
Introduction
ESC OK
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
To activate the backlight of the LOGO! display permanently, follow these steps.
Clock.. > LCD.. Menu Lang BM AI NUM s LOGO! Contrast > BackLight
ESC OK
You can select between: Default (Backlight is ON for 20 sec. or controlled by user program) Always On
ESC OK
ESC OK
LOGO!
Introduction
In the menu of LOGO! TD nearly the same menu items are available as in the menu of LOGO! basic module - except the possibility to edit the program.
Wiring Integrated functions Operation on device Menu item LOGO! Soft Comfort V6.1 Application example
In STOP mode Program.. Card.. > Stop Set Param Msg Config Set..
The following table shows on which device which menu items are available
LOGO! Basic module LOGO! TD
*)
*) Since E-Stand 4 (ES4) of LOGO! and LOGO! TD, switching into stop mode can be protected by password.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Modem wizard
for standard 11-bit analog modems
e.g. context menu, toolbar Control programs drawing directly on a PC in FBD or LAD Offline simulation with status for each function (color change) and forcing Online test in FBD and LAD with color change for each function and 30 actual values
0BA0, 0BA1, 0BA2, 0BA3, 0BA4, 0BA5, 0BA6 with function check
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
2.
3.
1. 2. 3.
Insert CD (LOGO! Soft Comfort V6.1) in CD-ROM drive Display CD content with help of Explorer Double click on start.html
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Start.html functions Direct choice of 10 languages Software installation Direct start of software from CD-ROM Display manuals on CD-ROM Display online help Choice of example programs on CD-ROM Choice of CAD drawings on CD-ROM Installation of necessary tools such as Acrobat Reader or printer drivers
Introduction
The USB cable driver for the LOGO! USB programming cable is also included on the CD-ROM. During the installation process of LSC V6.1 you will be asked if you want to install the driver. HINT: Follow the correct order ! 1. Install the driver (administrator privileges are required!) 2. Then connect the LOGO! USB programming cable with your PC
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Standard Windows
Introduction
Title bar
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Menu bar Symbol bar for program installation Tree structure for fast choice of all generation elements
Control program generation in the overview control plan via drag & drop
Introduction The general help can be activated via the menu item Help -> Content. You can find further information sorted by functional groups in the contents.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example With a mouse click on the desired topic you get detailed information about the corresponding functional group.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example Direct help can be selected via the context menu (right mouse key) of each function.
Introduction The direct help will also be activated via the menu item Help -> Context-sensitive Help. Via mouse pointer you can now select objects, you would like to have help text with.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction You can install program expansions, service packs and additional languages via the menu item Help -> Update Center.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Q1
(drinking water supply)
Cistern control When the water level drops below the level (I1), the drinking water supply (Q1) shall automatically be switched on. When the water level has reached the level (I2), the drinking water supply shall automatically be switched off again.
I3 (Pump OFF)
I2
(drinking water supply OFF)
I1
(drinking water supply ON)
I4
(Pump OFF)
Introduction
How many inputs and outputs are necessary to solve the task?
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example Move the mouse to the desired position. Clicking on the left mouse button inserts the block. Within the tree structure on the left side of the software you can choose quickly and clearly all necessary input and output blocks, markers or constants (high, low) and all basic and special functions and you can place them on the configuration interface. After having chosen an element the following cursor will appear on the configuration interface:
1.
2.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
2. 1.
After placing both inputs I1 and I2 and the output Q1 on the interface a basic function (NOT) is necessary. As already learned in the first step you choose via the tree structure on the left the appropriate function and place it via a simple mouse click.
Introduction
2.
Application example
1.
As the last function element a special function (latching relay) is also necessary. As already learned in the previous steps you choose via the tree structure at the left the appropriate function and place it via simple mouse click.
Introduction
In this programming example the NOT function block could be replaced by a direct negation of the S-input of the latching relay function.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example Via the context menu (right mouse button) on the digital input pins of all function blocks it is possible to negate the signal directly. This is also possible by a double click on the pin.
Introduction
To complete the control circuit you need to connect the blocks with one another:
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
1.
2.
Normally you can directly draw the connection line with the cursor after placing a block. If you are in a different mode, you will have to select the tool to get to the connecting mode. Now move the cursor over the connection pin of a block (a small blue box will be shown) and click the left mouse key. While holding down the key move the cursor to the pin you would like to connect with the first pin, and release the mouse key. The connection is drawn. Continue the same way with the other connections.
Introduction
By inserting text fields the program can be understood more easily. With LOGO! Soft Comfort V6.1 there are several ways of embedding text into the program structure:
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example Adding a comment to each block in the program via the context menu (right mouse key).
Introduction
Wiring By inserting a free text field. Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
1.
A
2.
3.
4.
Introduction
For better program readability, comprehensive names can be assigned to inputs and outputs in addition to the text fields.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
The control program is completed with insertion of function blocks and their connections. To get a reasonable, i.e. a clear view of the prepared control program, some further work is necessary. Placed objects such as function blocks, lines, and text fields can be moved accordingly.
This tool has to be selected, when you want to move function blocks, text fields or connection lines.
Introduction
To design everything more neatly and more clearly, you can align the individual function blocks vertically and horizontally.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
This button has to be activated to align the highlighted function blocks vertically.
Introduction
With special functions and basic functions in addition to the dialogues for comments there also exists one or more dialogues for parameters. Here you can preset set points or settings for each particular function block.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example In the configuration another address can be allocated for each single input and output block. Only inputs and outputs are regarded in the selection when they are not yet assigned in the control program.
Select function block, click right mouse key and select menu item Block attribute. OR Double click with left mouse key on the function block.
Introduction
Additionally there is the possibility to change and check all block attributes centrally.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
For program documentation all used connectors, basic functions and special functions can be displayed.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example A list of all used blocks can be displayed via the menu item Edit -> Go to block. The list comprises information about block number and block type. You can display e.g. which special functions you have used. The abbreviations of the block I1, Q2, B02, etc. can be entered in the search function (block number) and it will be displayed where the block is located in the list. When you complete the dialog field with OK, the desired block will be highlighted in the program.
Introduction
Further information about the program documentation can be viewed via the information window. It is shown at the bottom window frame by default.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example You can access the information window anytime via the menu item View -> Info Window or the F4 key. In the information window the resources used in the program, are displayed with current date and time.
Introduction
Program and plant information can be entered under File -> Attributes on the properties dialogue General. They appear in the program printout in the footer.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
The program including the entered plant data can be viewed from the attribute window under File -> Print preview.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
You can select which documents shall be printed, under Properties in the print preview window. By default the circuit diagram, the parameter list and the list with connection names are selected.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
It makes sense to divide the circuit diagram onto more pages for larger or more complex programs.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Due to the split-up of the program across several pages, connection lines might have to be separated.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Connections can easily be separated by selecting the scissor symbol. The interfaces are clearly labeled with the page number, block number and input pin. Clicking a second time with the scissor symbol on one of the interface placeholders undoes the separation.
Introduction
After configuration and documentation, program testing via offline simulation is the next step.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Now you know that the program can be run in LOGO!, but you still have to check whether your program works the way you intended it. Perhaps you would like to change some parameters. You can effortlessly change input values, check the behavior upon power failure and compare your calculations or expectations with the real behavior of the outputs.
Introduction
An excellent tool is available for program testing. This tool has to be selected when you want to test the program. With the activation of the offline simulation a tool bar for monitoring and operation of inputs and outputs is selected. A plug symbol provides a simulation of power failure to test the behavior in regards to retentivity. For time-critical simulations you can also set the output of a block (forcing), by clicking the output with the right mouse button.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example By clicking on the buttons on the tool bar or on the inputs in the circuit diagram you can change the status of the inputs. The signal run can be tracked with the color change from blue (low signal) to red (high signal) of the connection lines. This makes error tracking a lot easier.
Introduction
As an additional program testing feature, each input can be allocated to a certain switch function.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Each input of a block can be allocated to a certain switch function via the context menu (right mouse key) of an input block. You can chose between pushbutton (n.o. contacts, n.c. contacts), switches and frequency inputs at digital inputs. With frequency inputs the simulated frequency can be adjusted in Hz. With analog inputs the value range and the start value is preset. These parameters can centrally be changed and reviewed as well via the menu item Tools -> Simulation parameters.
Introduction
To protect the program and your know how you can place a valid up to 10-digit password for that program.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example This password protects your program only on LOGO!. There you can not delete, change or view it without the password! To load a password protected program onto a PC, the password is necessary as well. To delete an assigned password, enter Old password and leave New Password empty. To be able to reuse a LOGO! with program and password when password is lost, the password has to be entered incorrectly three times at program deletion. Then the program and the PW is automatically deleted. This can alternatively be done by software. *)
*) since E-Stand 4 (ES4) only possible via software or memory card
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
With LOGO! Soft Comfort V6.1 you have the possibility to either first realize your circuit diagram and then determine the required device via menu item Tools -> Determine LOGO! or you can firstly determine via Tools -> Select Hardware which LOGO! device you want to create your circuit diagram for.
In the device choice you can view for every LOGO! generation which resources are available. All available function blocks or resources are offered in configuration mode depending on the selected version.
Introduction
After testing the program successfully you need to transfer it to the LOGO!. Therefore LOGO! has to be connected with the PC cable to the PC.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
You have to click on this button to transfer a circuit diagram to LOGO!. Before transferring, the LOGO! version required for the configured circuit program, is identified. If the configured circuit program cannot be transferred to the available LOGO!, an error message is displayed and the transfer is aborted.
If the connection between LOGO! and PC is not established correctly, an error message will be displayed.
Introduction
After transferring the program LOGO! has to be set to RUN-mode. Then the program can be tested in real life.
s LOGO! 12/24 RC
s LOGO! 12/24 RC
Program..
Card.. Setup..
I:
s LOGO! 12/24 RC
> Program..
Card..
Setup..
Start LOGO! Q1
ESC OK
> Start
LOGO!
LOGO!
Application example
I3
I2 I1 I4
Introduction
Additional to the offline simulation an online test can be done in FBD and LAD after transferring the program to the LOGO! device.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example To start the online test after transferring the program this button has to be activated . After this the LOGO! device can be set into RUN-mode with this button .To see now the online-status off the device the eyeglasses-symbol has to be activated . Now you can simulate your program online on the device by using the real inputs. If you have to watch function blocks which contain actual values, you have to click at the eyeglasses-symbol below the respective block separately, e.g.:
1.
3.
2.
Introduction
With help of the software you can set the system clock of LOGO! as well. Of course, you can also set the time directly on the device.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example LOGO! and PC have to be connected via the PC cable to transfer the set time to LOGO!, then you have to click on the button Write.
Introduction
With LOGO! you have the possibility to configure an automatic summer / winter clock change. You can do this on the software or directly on the device.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
LOGO! and PC have to be connected via the PC cable to transfer the set summer / winter clock change to LOGO!. Depending on the chosen region this clock change is used.
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
With Set AI3 and AI4 position you can choose to enable the optional AI3 and AI4 on the LOGO! 0BA6 devices that have an option of four analog inputs. Your choices are as follows: 2 AIs: Only AI1 and AI2 corresponding to input terminals I7 and I8 are available for use in your circuit program. 4 AIs: AI1 and AI2 corresponding to input terminals I7 and I8 are available for use in your circuit program. Additionally, AI3 and AI4 corresponding to input terminals I1 and I2 are available for use. Set via software: Double-click at in your circuit program or go to File -> Properties -> Parameter or at LOGO! basic module: Setup > BM AI NUM
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
LOGO! Soft Comfort V6.1 provides a wizard to configure 11-bit analog modems that use standard AT commands and to connect them via an analog telephone line. You can use the modems to transfer circuit programs between LOGO! Soft Comfort V6.1 and LOGO! devices.
Introduction
First you have to make a few settings for you COM-Port: Select in Windows Start -> Settings -> Control Panel -> System -> Hardware -> Device Manager. Then select Ports -> open the properties window of your COM-Port.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example The port settings must be as follows: Bits per second: Data bits: Parity: Stop bits: Flow control: 9600 8 Even 1 None
Introduction
Select the Tools -> Connect Modem menu command to start the wizard. LOGO! Soft Comfort V6.1 displays a dialog that guides you through the configuration process.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
1.
2.
Introduction
First the remote modem has to be configured. This configuration has to be made via a direct connection between PC and modem.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
4.
5.
Every modem that you configure gets a name. In the wizard default AT-commands are already entered which are used of most modems. You can type in other ATcommands if necessary for your modem. Disable default in this case.
Introduction
Next step is to configure the local modem. The procedure is similar to the configuration of the remote modem.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example The modem wizard provides a list of telephone numbers. Here several numbers of remote stations can be entered. Select the number you want to call and click Dial.
7.
8 .
Introduction
After dialing the remote modem, you are able to up-/download the user program, set LOGO! in run/stop and do online- test.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
To be able to reuse a LOGO! with program and password when password is lost, the password has to be entered incorrectly three times at program deletion. Then the program and the PW is automatically deleted. *) In LOGO! ..0BA6 it is possible to delete user program and password by LOGO! Soft Comfort V6.1 . This function is especially helpful for LOGO! pure versions, where it is not possible to delete the program directly on the device via the keys. In generations prior ..0BA6, a memory cartridge was necessary to get the program deleted. Use Tool -> Transfer -> Clear User Program and Password.
Introduction
Use Tools -> Transfer -> Set LOGO! TD Power-on Screen to configure a power-on screen for the LOGO! TD. This screen gets displayed during LOGO! TD powers up.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Other miscellaneous settings can be made via the menu item Tools -> Options.
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
Conveyor controller
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Introduction
I2 (filling)
I3
(light barrier)
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example
Q1
I1
(ON/OFF)
Function description: A bottle filling conveyor shall be controlled. Part 1 The conveyor control is switched on and off via (I1). When the conveyor control is switched on, the conveyor motor (Q1) runs. If the light barrier (I3) is interrupted, the motor shall be switched off. Part 2 When the sensor (I2) detects a bottle, the motor is to be switched off for 3 sec. (filling action). After that the motor runs again.
Introduction
I2 (filling)
I3
(light barrier)
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example Invertierter Eingang Part 1 The conveyor control is switched on and off via (I1). When the conveyor control is switched on, the conveyor motor (Q1) runs. If the light barrier (I3) is interrupted, the motor shall be switched off.
Q1
Function description:
I1
(ON/OFF)
Introduction
I2 (filling)
I3
(light barrier)
Wiring Integrated functions Operation on device LOGO! Soft Comfort V6.1 Application example Part 2 When the sensor (I2) detects a bottle, the motor is to be switched off for 3 sec. (filling action). After that the motor runs again.
Q1
Function description:
I1
(ON/OFF)