BILL OF MATERIAL
PANEL REF.
AFR12
LEGEND
220KV LINE RELAY PANEL CL 95ABCR1,Y1,B1 CIRCUIT LABEL
DESCRIPTION
SPECIFICATION
2312(H) x 700(W) x 750(D)
QTY/ PANEL
1
PVC BLACK 300(W) X50(H) CASE : 2/3Vx3H AUX. SUPPLY : 220V DC CONTACTS : 2M 2B / 2M 2B / 2M 2B SR WIRING DRG. : 8112W00033 ER-XR351x3
1 1
95ABCR2,Y2,B2
ER-XR351x3
21
NUMERICAL DISTANCE PROTECTION RELAY PROVIDED WITH 1)DISTANCES PROTECTION-4 ZONE IMPEDANCE & REACTANCE SETTING: Zone I, II, III, IV: R = 0.05 200 ohms X = 0.05 300 ohms OPERATING DELAY TIME: ZONE I OF DISTANCE RELAY:</=30Msec UNDER FAULT OCCURS WITHIN 0.7 TIMES OF SETTING VALUE Zone II ,III, IV:0 TO 10 SECS
TYPE: CSC101B WITH IEC61850-8-1 STATION COMMUNICATION PROTOCOL AUX SUPPLY : 220 V DC 1A, 110V AC SIZE : 4U X 19
ER
2) DEFINITE TIME ZERO CURRENT PROTCETION(3I0):4 STAGES STAGE 1 TO 4 CURRENT:0.1 TO 100 A TIME: 0 TO 10 SECS 3) INVER TIME ZERO SEQUENCE PROTECTION(3I0-INV) CURRENT:0.1 TO 100 A TIME FACTOR: 0.01 TO 1000 TIME DELAY:0 TO 10 SECS 4)1 & 3 PH.AUTORECLOSER & SYNCHROCHECK PHASE ANGLE: 10 TO 50 DEGREES RECLOSING TIME: 0 TO 10 SECS RECLAIM TIME:5 TO 25 SECS 5)OVER VOLTAGE PROTECTION-2 STAGE STAGE-1,2:1 TO 120 V STAGE-1,2 TIME SETTING:0 TO 60 SECS 6)UNDER VOLTAGE PROTECTION-2 STAGE STAGE-1,2:1 TO 60 V STAGE-1,2 TIME SETTING:0 TO 60 SECS 7)BREAKER FAIL PROTECTION STARTUP CURRENTOF CB FAIL: 0.1 TO 100 A DELAY TIME:0 TO 2 SECS 8) DIRECTIONAL OVER CURRENT PROTECTION: CURRENT, STAGE1,2:0.1 TO 100 A TIME: 0 TO 10 SECS 9) BROKEN CONDUCTOR NEG. SEQ. CURRENT: 0.2 TO 10 A TIME: 0 TO 10 SECS 10)POWER SWING BLOCKING(PSB) 11)SWITCH ON TO FAULT 12)VT FUSE FAIL SUPERVISION 13)DISTURBANCE RECORDER 14)FAULT LOCATOR 15)EVENT RECORDER WHICH STORES UP TO 1000 EVENTS 17)RS485 COMMUNICATION PORT-1 NO 18)ELECTRICAL ETHERNET PORT-1 NO 19)RS232 DEBUGG PORT- 1 NO
LEGEND
DESCRIPTION
EARTH FAULT RELAY PROVIDED WITH 1)HIGHSET O/C PROTECTION (FWD OR REV OR NON DIR): SETTING: 0.05 TO 100 A TIME: 0 TO 60 SECS 2)LOWSET O/C PROTECTION(FWD OR REV OR NON DIR): SETTING: 0.05 TO 100 A TIME: 0 TO 300 SECS 3)HIGHSET E/F PROTECTION(FWD OR REV OR NON DIR): SETTING: 0.05 TO 100 A TIME: 0 TO 60 SECS 4)LOWSET E/F PROTECTION(FWD OR REV OR NON DIR): SETTING: 0.05 TO 100 A TIME: 0 TO 300 SECS 5)INVERSE O/C PROTECTION (FWD OR REV OR NON DIR): SETTING: 0.05 TO 100 A TIME: 0.005 TO 5 SECS SELECTABLE BETWEEN IEC SI OR NI, IEC VI, IEC EI,ANSI LTI 6)INVERSE E/F PROTECTION(FWD OR REV OR NON DIR): SETTING: 0.05 TO 100 A TIME: 0.005 TO 5 SECS SELECTABLE BETWEEN IEC SI OR NI, IEC VI, IEC EI,ANSI LTI 7)OVERLOAD PROTCETION SETTING: 0.2 TO 10 A TIME: 0.1 TO 60 SECS 8)UNDER & OVER VOLTAGE PROTECTION O/V STAGE 1,2: 110 TO 154V(PH TO PH) U/V STAGE 1,2: 66 TO 110V(PH TO PH) O/V & U/V STAGE 1,2 TIMER: 0.1 TO 10.0 SECS 9)THERMAL OVER LOAD PROTCETION SETTING: 0.2 TO 10 A TIME: 6 TO 7200 SECS 10) CIRCUIT BREAKER FAILURE PROTECTION CURRENT SETTING: 0.05 TO 100 A DELAY TIME:0.1 TO 32 SECS 11) VT SUPERVISION 12)DISTURBANCE RECORDER WITH RECORDING FACILITY 13)EVENT RECORDER WHICH STORES UP TO 1000 EVENTS 14)RS485 COMMUNICATION PORT-1 NO 15)ELECTRICAL ETHERNET PORT-2 NO
SPECIFICATION
TYPE: CSC211 WITH IEC61850-8-1 STATION COMMUNICATION PROTOCOL CT SEC : 1A, PT SEC : 110V AUX. SUPPLY :220V DC SIZE : 4U X 19/2
QTY/ PANEL
1
LBBX1/2
CASE : 3N AUX. SUPPLY : 220V DC CONTACTS : 4M S/R WIRING DRG. : 8112W00104 HAND RESET FLAG
ER-AR111x2
CASE : E4 AUX. SUPPLY : 220V DC CONTACTS : 11M S/R WIRING DRG. : 8112W00079
ER-TR112
86
TRIPPING RELAY
CASE : E4 AUX. SUPPLY : 220V DC CONTACTS :10M 2B H/R & E/R WIRING DRG. : 8112W00087
ER-TR241H2
LEGEND
PB6 PUSH BUTTON FOR TRIP RELAY RESET
DESCRIPTION
COLOUR : BLUE
SPECIFICATION
CONTACT : 2 NO + 2 NC DIA : 22.5 mm
QTY/ PANEL
1 4 4
CSS
2 POS., 6 WAYS STAYPUT WITH PISTOL GRIP HANDLE. POSN. : 'IN' - 'OUT' ( IN-4, OUT-2 )
SWITRON
TTS
2 POS., 25 WAYS STAYPUT LOCKABLE, KEY REMOVABLE IN ANY POS. POSN. : 'NORMAL' - 'TRANSFER' ( NOR-4, TRANSFER-21 )
SWITRON
TEST BLOCKS FOR DIST. PROTN. & B/U PROTN. TEST PLUG FOR TEST BLOCKS
ALSTOM/NELSTER ALSTOM
3 3
79X1/X2/X3
ER-AR101*3
CASE : 3N AUX. SUPPLY : 220V DC CONTACTS : 4M SR HAND RESET FLAG WIRING DRG. : 8112W00104
ER-AR111x2
80B1/B2/C1
DC SUPERVISION RELAY
CASE : 3N AUX. SUPPLY : 220V/220V/220V DC CONTACTS : 4B / 4B / 4B S/R REV. FLAG WIRING DRG. : 8112W00106
ER-AR121T*3
80A2/C2/D1
DC SUPERVISION RELAY
CASE : 3N AUX. SUPPLY : 48V/220V/220V DC CONTACTS : 2B / 4B / 4B S/R REV. FLAG WIRING DRG. : 8112W00106
ER-AR121T*3
80A1/30X
ER-AR101/AR121
DS/FL H, TH HS PS FS, LK
DOOR SWITCH WITH FLOURESENT LAMP HEATER, THERMOSTAT HEATER SWITCH POWER SOCKET WITH SWITCH FUSE, LIINK
ANCHOR INDOASIAN
PROTEC/ INDOCUPP
1 1 1 2
TERMINAL BLOCK
ELMEX CONNECTWELL