5 th 500 kVAr 481 Amps 480 Volts 384.9 Amps 4.7 th 0.7200 2.1600 0.0326 403.2 503.9 1500 6.00 Amps Amps kVA %
Power System Frequency: Capacitor Voltage Rating: Capacitor Frequency Rating: Derated Capacitor Size: Total Harmonic Load: Filter Tuning Frequency: Capacitor Rating (wye): Capacitor Rating (delta): Filter Reactor Rating: Fundamental Frequency Compensation: Utility Side Voltage Distortion (Vh): (Utility Harmonic Voltage Source) Load Harmonic Current: Maximum Total Harmonic Current:
60 Hz 600 Volts 60 Hz 320 kVAr 500 kVA 282 Hz 3684.15 F 1228.05 F 0.0865 mH 335 kVAr 1.00 % 180.4 Amps 223.1 Amps
Fund. Freq. Capacitor Voltage: Maximum Peak Voltage: Maximum Peak Current: FILTER CONFIGURATION:
Xl =
0.0326
FILTER REACTOR DESIGN SPECIFICATIONS: Reactor Impedance: Fundamental Current: RMS Current Requirement: TOLERANCE EVALUATION: Capacitor Tolerance: Reactor Tolerance: 0.00 2.50 + 10.00 2.50 0.0326 403.2 Amps 460.8 Amps Reactor Rating: Harmonic Current: Voltage Requirement: 0.0865 mH 223.1 Amps 277.1 Volts Tuning Range 4.43 4.76
1 (1 + t r )(1 + t c )
Information contained in this document is subject to change without notice. Electrotek assumes no responsibility for any damages resulting from use of the information contained within. Copyright 2000-2003 Electrotek Concepts, Inc. All rights reserved.