Harmonic Filter Calculations

Harmonic Filter Calculations:


SYSTEM INFORMATION: Filter Specification (e.g., 5): Three-Phase Capacitor Bank Rating: Rated Capacitor Bank Current: Nominal Bus Voltage: Capacitor Bank Current (actual): Filter Tuning Harmonic (e.g., 4.7): Capacitor Impedance (wye): Capacitor Impedance (delta): Filter Reactor Impedance: Filter Full Load Current (actual): Filter Full Load Current (rated): Transformer Nameplate Rating: Transformer Nameplate Impedance: Load Harmonic Current: Utility Harmonic Current: CAPACITOR DUTY CALCULATIONS: Harmonic Filter RMS Current: Harmonic Capacitor Voltage: RMS Capacitor Voltage: CAPACITOR LIMITS: (IEEE Standard 18-2002) Peak Voltage: RMS Current: KVAr: RMS Voltage: Limit 100% 100% 100% 100% Contingency 120% 135% 135% 110%

Enter Title Here

5 th 500 kVAr 481 Amps 480 Volts 384.9 Amps 4.7 th 0.7200 2.1600 0.0326 403.2 503.9 1500 6.00 Amps Amps kVA %

Power System Frequency: Capacitor Voltage Rating: Capacitor Frequency Rating: Derated Capacitor Size: Total Harmonic Load: Filter Tuning Frequency: Capacitor Rating (wye): Capacitor Rating (delta): Filter Reactor Rating: Fundamental Frequency Compensation: Utility Side Voltage Distortion (Vh): (Utility Harmonic Voltage Source) Load Harmonic Current: Maximum Total Harmonic Current:

60 Hz 600 Volts 60 Hz 320 kVAr 500 kVA 282 Hz 3684.15 F 1228.05 F 0.0865 mH 335 kVAr 1.00 % 180.4 Amps 223.1 Amps

30.00 % Fund 42.7 Amps

460.8 Amps 55.6 Volts 505.8 Volts

Fund. Freq. Capacitor Voltage: Maximum Peak Voltage: Maximum Peak Current: FILTER CONFIGURATION:

502.8 Volts 558.4 Volts 626.2 Amps


480 Volt Bus

Actual 93% 96% 81% 84%

Value 558 461 404 506

Xl =

0.0326

500 kVAr @ 600 Volts

FILTER REACTOR DESIGN SPECIFICATIONS: Reactor Impedance: Fundamental Current: RMS Current Requirement: TOLERANCE EVALUATION: Capacitor Tolerance: Reactor Tolerance: 0.00 2.50 + 10.00 2.50 0.0326 403.2 Amps 460.8 Amps Reactor Rating: Harmonic Current: Voltage Requirement: 0.0865 mH 223.1 Amps 277.1 Volts Tuning Range 4.43 4.76

ftuned = fno min al

1 (1 + t r )(1 + t c )

Information contained in this document is subject to change without notice. Electrotek assumes no responsibility for any damages resulting from use of the information contained within. Copyright 2000-2003 Electrotek Concepts, Inc. All rights reserved.

Electrotek Concepts, Inc.

2/19/2003