Transformer Test Report - Calculation
Transformer Specification Transformer Efficiency
Capacity 35 kVA Voltage Regulation
Primary DELTA
Secondary STAR
Primary Voltage 415 Voltage If Regulation denotes 0.00 % , Please keep the regula
Secondary Voltage 220 Voltage <2% . Due to the regulation value is almost nearest t
Primary Current 48.7 Amps
Secondary Current 91.15 Amps
Open Circuit Test : Short Circuit Test :
Voltage Applied (Vo) 415 Voltage Voltage Applied (Vs)
Current Consumed (Io) 0.95 Amps Current Consumed - Primary (Is)
Power Consumed (Woc) 243.00 Watts Power Consumed (Wsc)
Woct. 140.30 Watts Wsct.
Cos Փ 0.3559 Cos Փ
Sine Փ 0.9345 Sine Փ
Calculations : Calculations :
Core Loss Componen (Ic) 0.338 Amps Copper Loss Component (Ic)
Core Loss Resistance (Rc) 1227.6 Ω HV side Resistance (Rie)
Magnetising Current (Im) 0.888 Amps Magnetising Current (Im)
Magnetising Reactanc (Xm) 467.4 Ω HV side Leakage Reactance (Xie)
Magnetising Impedanc (Zie) 1313.6 Ω HV side Impedance (Zie)
Power Factor Cosθ (no-load) 0.3559 Power Factor cosθ (full-load)
n
96.01 % >95%
0.00 % <2%
To be fill Manually with Load test Readings
00 % , Please keep the regulation Value, Report results will be generated as per given values
tion value is almost nearest to the ZERO
13.5 Voltage
48.7 Amps
880.0 Watts
508.07 Watts
0.773
0.635
37.635 Amps
0.359 Ω
30.908 Amps
0.437 Ω
0.565 Ω
0.773