and control
Start up function objective
18%
L14HP Spare speed signal
19%
95%
L14HF At field flashing speed
90%
18%
L14HM Minimum Firing Speed
15%
50%
L14HA Accelerating speed
46%
96.4%
L14HS Min operating speed
94.8%
60%
L14HC Auxiliary Cranking
50% Speed Relay
8.4%
L14HT Cool down Slow Roll
3.2% Start Speed Relay
Start up control
14.4%
30.6%
0.05%/s
5%/s
1 sec Start up
FSR
Start up curve
Fire shut down
Fire shut down is an improvement over
the former fuel shut off at L14HS drop o
ut by maintaining flame down to lower s
peed to reduction the strain develop on
hot gas path part
100 %
FSRMAX -- Max Fuel Reference
FSRSD
L83SDSET-- Preset FSRSD to Existing FSR -- Shut
down
FSR
L83SDMIN-- Set FSRSD to FSRMIN
Signal %
0.25 s
0.1 %/sec
5 %/sec
0.05 %/sec
0.1 %/sec
1 %/sec
0.1 %/sec
0.1 %
L83JSD1
GT. Trip
FSRSD-FSRMIN >0.1 %
Flame ON TNH<30%
1 Can off
Speed control
The speed control system control the sp
eed and load of the gas turbine to main
tain speed at 100% at any load
Speed control software will change FSR
in proportion to the difference between
TNH(turbine speed)and TNR(speed ref.)
Turbine drive generator operating spee
d range normally from 95%-107%
Start up reference speed is 100.3%
Speed droop
Droop speed control is the proportional
control changing the FSR in proportion t
o the difference between actual turbine
speed and turbine speed reference as t
he equation below
(TNR-TNH)x Droop gain+FSRNL =FSRN
Droop control algorithm
100 %
10.5
1sec
14.7 %
Droop control curve
Synchronizing control
TNR for synchronizing is 100.3% to kee
p the generator faster than the grid
If frequency has varied enough the spe
ed matching circuit adjust TNR to maint
ain turbine speed 0.2 to 0.4 % faster th
an the grid
Turbine speed reference TNR
Speed control schematic
Auto synch logic
Synch permissive logic
System line voltage
109%
86.5%
Generator volts
109%
86.5%
Line Frequency
50.5Hz
49.5Hz
Generator frequency
50.5Hz
49.5Hz
Synch speed matching permissive
Auto synch permissive logic
Temperature control
The temperature control system will limi
t fuel flow to gas turbine to maintain int
ernal operating temperature within gas
turbine limitation of turbine hot gas pat
h parts.
Firing temperature is the temperature e
xists at first stage nozzle. This temperat
ure must be limited by control system
Firing temperature
It is impractical to measure temperature
direct to the combustion chamber or at t
he turbine inlet So, the control system co
ntrol the exhaust temperature instead.
Firing temperature as a function of fuel fl
ow (FSR)
FSR temp. control curve are used as back
up to primary CPD. Bias temp.
Exhaust temperature control
18 Chromel alumel TC are installed at e
xhaust plenum to sent signal to Mark V
Exhaust temperature control soft ware
1.Temperature control command
2.Temp control bias calculation
3.Temp reference selection
Temperature control FSR.
Exhaust temp control command
Is the temperature control command (TTRXB)
compare the exhaust temperature control set
point(TTXM).The soft ware program converts
the temperature error to fuel stroke reference
signal FSRT
Temperature control bias
Firing temperature limit by linearized fu
nction of exhaust temperature and CPD
backed up by linearized function of exh
aust temperature and FSR
Temperature control Bias
Exhaust temperature (TX)
FSRMAN
Liquid fuel flow control
FSR1V1 Fuel splitter
Mixed Fuel Operation
FSRSU
FSRSD DC
FSR2 FSROUT Gas
FSRT Min FSR
Fuel
GCV.
Servo mA Servo
sel Splitter
Com-
Com-
valve FG. Flow Control
FSRN mand 96GC
mand
FSRMAN
DC
SRV. mA
SRV. FPRGOUT Servo
Servo
Com-
Com-
valve FG. Press Control
mand 90SR
mand
GCV. Schematic diagram
Gas control valve out put
Master protective
Gas Ratio Valve Open
SRV. Out put signal
3 sec
Gas control valve not
following reference trip
5%
5 sec
Rated
MW
LOAD NO MIXED OK
MIXED No
MIX
30 MW
NO MIXED
0 30 60 90 100 % GAS
100 70 40 10 0 % LIQ
Modulate Inlet Guide Vane
Protect compressor pulsation by modulat
e during the acceleration of gas turbine t
o rated speed.
IGV modulation maintain proper flow an
d pressure to combustion.
Maintain high exhaust temperature at lo
w load when combined cycle application.
Modulate IGV control scheme.
IGV. Control control reference
(CSRGV)
L83GVMAX
CSRGV
86 DGA
(IGV CONTROL
REFERENCE)
CPD.
IGV
TNH. part
Speed MIN
SEL
57 DGA
CLOSE MAX
IGV SEL
OPEN MAN
L83GVMAN
TTRX
L83GVSS IGV
MIN TEMP
371 c SEL CON X CSRGVX
TROL
+
1120 c
TTXM
IGV. Control Algorithm from Mark V
Temp Control and
Manual Control Ref
519 o F
Compressor Temperature Ratio
Speed Correction Factor
o
F
Max Comp Inlet Flange Temp
CPD.
IGV
TNH. part
Speed MIN
SEL
57 DGA
CLOSE MAX
IGV SEL
OPEN MAN
L83GVMAN
TTRX
L83GVSS IGV
MIN
371 c SEL
TEMP
CON X CSRGVX From Where ?
TROL
+
1120 c
TTXM
CSRGVX
TTXM
TTRX
2 deg F
X
CSKGVDB
L83GVDB Min
SEL X
TTRXGVB
700 F
2048 F
L83GVSS CSRGVX
TNGV X
2 deg F
CSKGVTPG X X
CSKGVTC 4 sec
T
V = OUT IGV
1+TS
CSRGV V MAN
RESET
L83GVMAN_CMD OUT =V
TTRX
L83REC
TTRXC
CPD +X X
+
X
8.058 prs_R
Conner
27.342 F/ prs L83JTN = Temperature select logic(by damper&fuel)
Slope
N = 0 Operate open cycle mode on Gas fuel
L83JTN
N = 1 Operate Combined cycle mode on Gas fuel
N = 2 Operate open cycle on mode Liquid fuel
N = 3 Operate Combined cycle mode on Liquid fuel
For example show value of curve N= 1
IGV. Operation curve
IGV. Fault detection
Position feedback
IGV [96TV-1] DGA
TCQA-REG-CUR IGV
control servo current %
5 SEC