Professional Documents
Culture Documents
Differential Characteristic 100mva 220 - 110kv
Differential Characteristic 100mva 220 - 110kv
CT:
Winding/Leg Name: CT Current Prim: CT Current Sec: CT Grounding: Gnd CT Prim Current: Gnd CT Sec Current: Gnd CT Grounding: Primary 300.00 A 1.00 A tow. Prot. Obj. 200.00 A 1.00 A n/a Secondary 600.00 A 1.00 A tow. Prot. Obj. 800.00 A 1.00 A n/a
.
Protection device:
Reference Winding: Ibias Calculation: Zero Seq. Elimination: Standardize Using: Ground CT Used: Idiff>: Idiff>>: Itol rel: Itol abs: Primary ( |Ip| + |Is| ) / K1 (K1 = 2.00) IL-I0 PO nominal current No 0.20 In 8.00 In 12.50 % 0.05 In tdiff>: tdiff>>: ttol rel: ttol abs: 0.03 s 0.03 s 12.50 % 0.01 s
.
Test Module
Name: Test Start: User Name: Company: OMICRON Diff Operating Characteristic 27-Aug-2010 16:36:11 Ankit Shah VARDHMAN ASSOCIATES Version: Test End: Manager:
.
2.20 27-Aug-2010 16:37:15
.
Test Settings: .
General Settings:
Testing: Max. Test Time: Prefault: Prefault current: Vout enabled: GPS enabled: Primary / Secondary 1.50 s No 0.00 In No No Delay Time: Prefault time: Vout winding: GPS side: 0.25 s 0.000 s Primary Primary
.
Search Test Settings:
Ignore Default Char.: Resolution Relative: No 0.10 % Resolution Absolute: 0.010 In
.
Binary Outputs
Bin. out 1: Bin. out 2: Bin. out 3: Bin. out 4: 0 0 0 0
Ibias [In]
.
State: 5 out of 5 points tested. 5 points passed. 0 points failed. General Assessment: Test passed