Automatic Boiler Controls: 62B-208-1 11 AUG 00
Automatic Boiler Controls: 62B-208-1 11 AUG 00
62B-208
62B-208-1 11 AUG 00
Functions
MEASURE
COMPARE
COMPUTE
CORRECT
62B-208-2 11 AUG 00
62B-208-3 11 AUG 00
62B-208-4 11 AUG 00
Combustion Control
Maintains steam drum or SUPERHEATER outlet pressure Within 5 PSI of SETPOINT during steady state conditions
62B-208-5 11 AUG 00
Combustion Control
MEASURES STEAM PRESSURE
ACC
MANIPULATES THE FORCED DRAFT BLOWERS & FUEL OIL CONTROL VALVE
62B-208-6 11 AUG 00
Combustion Control
MEASURES STEAM PRESSURE ACC
FORCED DRAFT BLOWER
MANIPULATES AIR FLOW TO THE BOILER BY INCREASING/DECREASING THE SPEED OF THE FORCED DRAFT BLOWER
62B-208-7 11 AUG 00
Combustion Control
MEASURES STEAM PRESSURE
ACC
MANIPULATES FUEL FLOW TO THE BOILER BY INCREASING/DECREASING FUEL FLOW TO THE BURNERS
Combustion Control
MEASURES STEAM PRESSURE
ACC
FORCED DRAFT BLOWER
62B-208-11 11 AUG 00
Water Level
+/-1 inch of Normal
MANIPULATES THE FEEDWATER CONTROL VALVE TO REGULATE FEED FLOW TO THE BOILER
62B-208-12 11 AUG 00
SFT
DLT
FWCV
FFT
62B-208-13 11 AUG 00
DLT
FWCV
FFT
FFC
FWCV POS FWC A/M
62B-208-14 11 AUG 00
62B-208-15 11 AUG 00
62B-208-16 11 AUG 00
Swell
Increase in STM demand:
More STM leaves BLR. Drum press starts decreasing. STM bubbles in GEN tubes expand. WTR level appears to swell.
Swell
Automatic combustion CONTRL system (acc sys) senses decrease in drum press and increases firing rate Drum press increases and regains SETPOINT WTR LVL decreases as bubble size decreases
62B-208-18 11 AUG 00
Swell
WTR reaches normal and get slightly below normal Automatic boiler control system (ABC sys) will increase feed flow to match STM flow WTR LVL achieves normal
62B-208-19 11 AUG 00
Shrink
During a DWN PWR MANUEVER shrink has the opposite effect :
Co wants all stop -- man overboard! Throttle closes STM drum press rises WTR level lowers or shrinks
62B-208-20 11 AUG 00
Shrink
Acc sys decreases firing rate Drum press regains SETPOINT WTR LVL increases WTR LVL reaches normal, and slightly above normal ABC sys decreases feed flow
62B-208-21 11 AUG 00
62B-208-23 11 AUG 00
62B-208-24 11 AUG 00
62B-208-25 11 AUG 00
62B-208-27 11 AUG 00
62B-208-29 11 AUG 00
FDB
FOCV
MFP
62B-208-31 11 AUG 00
62B-208-32 11 AUG 00
RESET
REDUCER 80 PSI
ALARM PRESSURE SWITCH
Modes Of Operation
Automatic
Remote MAUNUAL Local manual
62B-208-34 11 AUG 00
THE END
62B-208-35 11 AUG 00
62b-208
62B-208-36 11 AUG 00