Accuracy of Current Transformers

Permissible Current in a Busbar | Accuracy of Current Transformers | Important Warning for CT's As per IEC 60044-1 "Instrument transformers - current transformers"
Accuracy class 0,1 0,2 0,5 1 3 Error @ 0,05In 0,4% 0,75% 1,5% 3% Error @ 0,2In 0,2% 0,35% 0,75% 1,5% Error @ 0,5In 3% Error @ In 0,1% 0,2% 0,5% 1% Error @ 1,2In 0,1% 0,2% 0,5% 1% 3%

Ratio errors accuracy classes

Accuracy class 0,1 0,2 0,5 1 3

Phase displ.@ 0,05In 15' 30' 90' 180' -

Phase displ.@ 0,2In 8' 15' 45' 90' -

Phase displ.@ In 5' 10' 30' 60' -

Phase displ.@ 1,2In 5' 10' 30' 60' -

Phase displacement accuracy classes

Accuracy class 0,2S 0,5S 5P 10P

Error @ 0,01In 0,75% 1,5% -

Error @ 0,05In 0,35% 0,75% -

Error @ 0,2In 0,2% 0,5% -

Error @ In 0,2% 0,5% 1% 3%

Error @ 1,2In 0,2% 0,5% -

Composite error at rated accuracy limit current 5% 10%

Ratio errors classes S and protection

Accuracy class 0,2S 0,5S 5P 10P

Phase displ.@ 0,01In 30' 90' -

Phase displ.@ 0,05In 15' 45' -

Phase displ.@ 0,2In 10' 30' -

Phase displ.@ In 10' 30' 60' -

Phase displ.@ 1,2In 10' 30' -

Phase displacement classes S and protection