You are on page 1of 6

LABORATORIUM SISTEM DISTRIBUSI TENAGA LISTRIK

WORKBOOK

Current Transformer
PROTEKSI JARINGAN DISTRIBUSI TENAGA LISTRIK

Email : supriyanto_suhono@yahoo.com.sg 5/26/2012

(i) Data Name Plate Type Measuring Transformer Protection Transformer Class 0.2 10P10 Current ratio 400/5 400/5

(ii) Pengukuran Resistansi Sekunder Type Measuring transformer (class 0.2) Protection Transformer(class 10P10) (iv) Uji Rasio Type Measuring transformer (class 0.2) Protection Transformer(class 10P10) Ratio 50/0.6 50/0.6 Secondary Resistance 0.5 0.5

(v) Magnetization Curve

Email: supriyanto_suhono@yahoo.com.sg

Page 2

(vi) Burden Class 0.2


Voltage Across Burden (V) Burden Current (A) 0.400 0.6

Class 10P10
0.392 0.6

Perhitungan CT Pengukuran Knee point = titik ketika kenaikan tegangan 10% akan menghasilkan kenaikan arus 50%.

Persamaan kurva karakteristik CT V = 9,562 I 0,205 (*)

Maka knee point arus I = 17.66 A Dengan substitusi I ke (*) Maka knee point tegangan V = 9,562 (17.66 A) 0,205 V = 17.225 V

Email: supriyanto_suhono@yahoo.com.sg

Page 4

CT Proteksi V = 13,96 ln(I) - 42,65 (*)

Maka knee point arus


I = 69.7 A

Dengan substitusi I ke (*) Maka knee point tegangan V = 13,96 ln(69.7 A) - 42,65 V = 16.60 V Tugas buat analisis dari hasil perhitungan; (1) Proses perhitungan knee point (2) Perbandingan CT Pengukuran dan Proteksi

Email: supriyanto_suhono@yahoo.com.sg

Page 6

You might also like