WORKBOOK
Current Transformer
PROTEKSI JARINGAN DISTRIBUSI TENAGA LISTRIK
(i) Data Name Plate Type Measuring Transformer Protection Transformer Class 0.2 10P10 Current ratio 400/5 400/5
(ii) Pengukuran Resistansi Sekunder Type Measuring transformer (class 0.2) Protection Transformer(class 10P10) (iv) Uji Rasio Type Measuring transformer (class 0.2) Protection Transformer(class 10P10) Ratio 50/0.6 50/0.6 Secondary Resistance 0.5 0.5
Email: supriyanto_suhono@yahoo.com.sg
Page 2
Class 10P10
0.392 0.6
Perhitungan CT Pengukuran Knee point = titik ketika kenaikan tegangan 10% akan menghasilkan kenaikan arus 50%.
Maka knee point arus I = 17.66 A Dengan substitusi I ke (*) Maka knee point tegangan V = 9,562 (17.66 A) 0,205 V = 17.225 V
Email: supriyanto_suhono@yahoo.com.sg
Page 4
Dengan substitusi I ke (*) Maka knee point tegangan V = 13,96 ln(69.7 A) - 42,65 V = 16.60 V Tugas buat analisis dari hasil perhitungan; (1) Proses perhitungan knee point (2) Perbandingan CT Pengukuran dan Proteksi