GAS TURBINE
STARTUP
GAS TURBINE ENGINEERING - FES
2
HYDERABAD
OBJECTIVES
To smoothly start,Accelerate and bring the Gas Turbine to full Speed No Load Condition
3
HYDERABAD
All MCC modules are switched ON' and are kept on Auto Lube Oil Level is OK & Oil temp. normal Select Cooldown On and ensure that the AC Lube Oil Pumps starts & Ratcheting is OK. Start EOP and ensure that the pressure developed is OK Cooling Water level is OK Visual Inspection of Machine is OK
GAS TURBINE ENGINEERING - FES
Normal Start
HYDERABAD
Contd
GAS TURBINE ENGINEERING - FES
Contd
HYDERABAD
6
HYDERABAD
Contd
CRANKING Displayed
1. Turbine reaches cranking speed (about 19%). 2. The Turbine is purged for 5 min. 3. Turbine Purge Timer times out.
FIRING Displayed
1. Ignition Relay is energised (2TVX. Spark Plugs are energised 2. 60 sec Firing Timer is started.
NO
HYDERABAD
On Liquid YES
Energises Liquid Fuel Trip Solenoid (20 FL) Energises Fuel Pump Clutch Solenoid (20 CF) Permissive for Fuel Bypass valve to operate as established by the digital command FQROUT Starts Booster Atomizing Air Compressor
Fuel Stroke Reference (FSR) is set to Firing Value Opening of GCV / closing of Bypass valve depends on this. Flame is detected in 2 out of 4 scanner and is steady for 2 secs
YES
WARM UP displayed
Contd
HYDERABAD
Warm Up Timer starts 60 seconds). Compartment vent Fans started. Fired Starts Counter incremented. Fired Hours timer energised. After warm-up time, Diesel Engine Accelerates to its full speed FSR is increased at a predetermined rate to accelerate the Turbine.
ACCELERATING Displayed At approximately 55 to 60% speed, starting Clutch is automatically disengaged. Diesel Engine cuts back to idle speed and is stopped after 5 min cooldown timer. Turbine is now self sustaining and accelerates on its own At ~ 80 % speed, IGV is opened to 57 deg ( 20 TV-IGV solenoid is energised ) At ~ 95 % speed, Compressor Bleed Valves are closed Aux Lube Oil Pump & Aux Hydraulic Pumps are stoped Turbine Exhaust Frame Cooling fans are started (88 TKI & 2)
GAS TURBINE ENGINEERING - FES
HYDERABAD
On GAS N0
Yes
Enables Manual Raise/Lower of Turbine Speed Reference to Synchronize the Unit. If Auto Synch permissive are OK, Generator and line are present and above minimums, the Control System will modulate FSR to bring Speed to match the station line frequency and closes Generator Breaker when Phase angle is OK. Depending upon Load Mode Selection , Turbine is Loaded to the Reference and load maintained. PART LOAD / PRE SELECTED LOAD/ BASE LOAD Displayed
GAS TURBINE ENGINEERING - FES
10
HYDERABAD
11
HYDERABAD
12
HYDERABAD
13
HYDERABAD
14
HYDERABAD
GAS TURBINE
OPERATIONS
GAS TURBINE ENGINEERING - FES
15
HYDERABAD
PARAMETERS
Pressure Temperatures Lube Oil Header Brg. Drains Comp. Inlet Comp. Discharge Exhaust Wheelspace Cooling Water Outlet
Lube Oil Hydraulic Oil Trip Oil Comp. Discharge Inlet Air Filter DP Cooling water
16
HYDERABAD
PARAMETERS
OTHERS GENERATOR
Voltage Current Load Stator Temperatures
Vibrations Noise, Rubs Startup Time Coast Down Time Fired Starts Fired Hours
17
HYDERABAD
OPERATIONAL DIAGNOSTIC
18
HYDERABAD
Do not Force any Logic for Startup Do not attempt Subsequent Starts Without Troubleshooting if M/C trips during Startup Record the trends & Analyze present Operation
>>Load Vs Exhaust Temperatures >>Load Vs CPD >>Load Vs FSR >>Load Vs Vibration
Use trend Data from Mark IV/V to Notice incipient GAS TURBINE ENGINEERING - FES Problems
19
HYDERABAD
GAS TURBINE
SHUTDOWN
GAS TURBINE ENGINEERING - FES
20
HYDERABAD
21
HYDERABAD
22
HYDERABAD
23
HYDERABAD
24
HYDERABAD
STANDBY INSPECTION
When Unit is not run for a long time Crank the Turbine once in a Fortnight to drive away Moisture Check Battery system, Oil levels etc.
25
HYDERABAD
GAS TURBINE
PROTECTIONS
GAS TURBINE ENGINEERING - FES
26
HYDERABAD
Protection System
Electrical Protection systems
>>Over Speed >>High Exhaust Temperature >>Low Lube Oil Pressure >>Low Trip Oil Pressure >>High Lube Oil Temperature >>Loss of Flame >>High Vibration
GAS TURBINE ENGINEERING - FES
27
HYDERABAD
Mechanical Protections
>>Over Speed Bolt >>Trip Out Devices Based on Low Trip Oil >>Manual Emergency Trip Device
GAS TURBINE ENGINEERING - FES
28
HYDERABAD
A A>B B
OR
TTKOT1
A A>B B
L86MR1
29
HYDERABAD
TTKOT2 TTKOT3
TRIP
ALARM TTRX(Temp. Control Reference)
30
HYDERABAD
Vibration protection
Standard Vibration Measurements used for Tripping GT are Velocity Type on Bearing Housing Alarm setting = 0.5 / sec Trip setting = 1.0 / sec Total System is Tested for Integrity during Turbine Shut Down by Mark IV / V Panel
GAS TURBINE ENGINEERING - FES
31
HYDERABAD
Vibration Protection
If All Gas Turbine Sensors are Disabled or Faulty
OR
If All Generator Sensors are are Disabled or Faulty
OR
If 2 or more Generator sensors Disabled or faulty
GAS TURBINE ENGINEERING - FES
T START INHIBIT
32
HYDERABAD
Vibration Trip
Adjacent Sensor OPTVTD
OR
L39VGTT
RESET
Any Trip and Any Alarm from another Sensor
OR
Any Trip if 2 Sensor Inputs or Disabled
RESET
GAS TURBINE ENGINEERING - FES
33
HYDERABAD
L39VGT
BB 1 BB 2
LK39DIFF
+ _
A A >B B OR T
34
HYDERABAD
Combustion Monitoring
Exhaust Temperature Spreads are the Result of Uneven Combustion in all the Combustion Chambers Combustion Monitoring is Built in Mark IV/V Combustion Monitoring is Enabled after Machine Reaches FSNL
GAS TURBINE ENGINEERING - FES
35
HYDERABAD
36
HYDERABAD
Trip Conditions
1. TTXSP1 > TTXSPL and TTXSP2 > 0.8 TTXSPL and The two Lowest TCs are adjacent 2. TTXSP1 > 5 TTXSPL and TTXSP2 > 0.8 TTXSPL and The 2nd and 3rd Lowest TCs are Adjacent 3. All Spreads are > TTXSPL
Trip : Any of the above Conditions exists for more than 9 Sec
GAS TURBINE ENGINEERING - FES