GAS TURBINE
STARTUP
OBJECTIVES
HYDERABAD
HYDERABAD
Flame is
detected in
NO YES FSR cuts back to
2 out of 4 scanner
WARM-UP value.
Failure to Ignite alarm and is steady
appears Turbine on Crank for 2 secs
WARM UP displayed
Mode
GAS TURBINE ENGINEERING - FES
8
Contd
HYDERABAD
Warm Up Timer starts 60 seconds).
Compartment vent Fans started.
Fired Starts Counter incremented. Fired Hours timer energised.
N0
FULL SPEED NO LOAD Displayed
If Auto Synch permissive are OK, Generator and line are present
and above minimums, the Control System will modulate FSR to
bring Speed to match the station line frequency and closes
Generator Breaker when Phase angle is OK.
HYDERABAD
HYDERABAD
HYDERABAD
HYDERABAD
GAS TURBINE
OPERATIONS
HYDERABAD
PARAMETERS
Pressure Temperatures
HYDERABAD
PARAMETERS
OTHERS GENERATOR
Vibrations Voltage
Noise, Rubs Current
Startup Time Load
Coast Down Time Stator Temperatures
Fired Starts
Fired Hours
GAS TURBINE ENGINEERING - FES
17
HYDERABAD
OPERATIONAL DIAGNOSTIC
Start up
Load Hunting
Combustion Trouble
Lower Loads
Higher Temperatures
HYDERABAD
GAS TURBINE
SHUTDOWN
HYDERABAD
HYDERABAD
HYDERABAD
HYDERABAD
HYDERABAD
STANDBY INSPECTION
GAS TURBINE
PROTECTIONS
HYDERABAD
Protection System
Electrical Protection systems
>>Over Speed
>>High Exhaust Temperature
>>Low Lube Oil Pressure
>>Low Trip Oil Pressure
>>High Lube Oil Temperature
>>Loss of Flame
>>High Vibration
GAS TURBINE ENGINEERING - FES
27
HYDERABAD
HYDERABAD
TTRX
A
A>B OR
TTKOT2 B
A
A>B To
TTKOT1 B LATCH Master
SET
L86MR1 RESET Protection
Alarm &
Trip
GAS TURBINE ENGINEERING - FES
29
HYDERABAD
TTXM TTKOT2
Temp.
Feedback TTKOT3 TRIP
ALARM
TTRX(Temp. Control
Reference)
HYDERABAD
Vibration protection
Standard Vibration Measurements used for
Tripping GT are Velocity Type on Bearing
Housing
Alarm setting = 0.5 / sec
Trip setting = 1.0 / sec
Total System is Tested for Integrity during
Turbine Shut Down by Mark IV / V Panel
GAS TURBINE ENGINEERING - FES
31
HYDERABAD
Vibration Protection
If All Gas Turbine Sensors
are Disabled or Faulty
OR T
OR T
If 2 or more Generator START
sensors Disabled or faulty INHIBIT
HYDERABAD
Vibration Trip
Adjacent Sensor
OPTVTD
RESET
HYDERABAD
BB 1 +
_
A
A >B T
B OR
BB 2
Vibration
LK39DIFF Differential
Alarm
OTHER SIMILAR
GROUPS
HYDERABAD
Combustion Monitoring
Exhaust Temperature Spreads are the
Result of Uneven Combustion in all the
Combustion Chambers
Combustion Monitoring is Built in
Mark IV/V
Combustion Monitoring is Enabled after
Machine Reaches FSNL
GAS TURBINE ENGINEERING - FES
35
HYDERABAD
HYDERABAD
Trip Conditions
1. TTXSP1 > TTXSPL and
TTXSP2 > 0.8 TTXSPL and
The two Lowest TCs are adjacent
2. TTXSP1 > 5 TTXSPL and
TTXSP2 > 0.8 TTXSPL and
The 2nd and 3rd Lowest TCs are Adjacent
3. All Spreads are > TTXSPL
Trip : Any of the above Conditions exists
for more than 9 Sec