then reverted to the original spongy lead by subsequent charging. Thus, a negative plate keeps equilibrium between the amount which turns into spongy lead by charging and the amount of spongy lead which turns into lead sulphate by absorbing the oxygen gas generated at the positive plate. The oxygen recombination principle can be shown by the following reaction : 1. 2. Reaction at positive plate : H2O = O2 + 2e = =
(1) PbO (3) To reaction (1) (4) To reaction (3) To reaction (2) (2)
PbSO4 + 2H + 2e
3.
Thus, the oxygen recombination technology makes the battery virtually maintenance Free.
Section 3 : Technical Specification of 1000 AH Battery 1. 2. 3. 4. Capacity of the Battery @ 10 Hr. rate : 1000 AH discharge to 1.75 ECV Nominal Voltage per cell of fully : 2.0 V charged battery at 27oC Open Circuit Voltage (OCV) of fully : 2.15 V charged battery at 27oC Recommended Float Voltage Condition (i) Terminal Voltage of Charger 2.25 V/Cell (ii) Float charging current at 2.25 V/cell : Maximum current to be limited to 20% of the rated AH Recommended Boost charging condition : 2.30 V/Cell for quick charging at 27oC Internal resistance of the cell : 0.257 milli ohms Life Expectancy of the Battery : 4000 Cycles at 20% Depth of Discharge or 20 years under Float condition Containers : (i) Material : Polypropylene (Spl. Grade) (ii) Thickness of wall : 2.3 mm (Approx.) Container and cover - Polypropylene Co-polymer housed in a steel tray - Spun glass micro porous matrix Page 55 of 58
5. 6. 7. 8.
Safety valve Positive plate Negative plate Terminal Self discharge Charging Float charge Boost charge Connectors Life expectancy
- Explosion proof, pressure-regulating and selfresealing type - Patented MFX alloy - Lead Calcium alloy - Integral lead terminal with solid copper core - Less than 0.5% per week - Current limited, constant potential - 2.25 VPC at 27oC with a max. current limit of 20% of rated capacity in amperes - 2.30 VPC at 27oC with a max. current limit of 20% of rated capacity in amperes - Heavy-duty, lead plated copper connectors - Float service at 27oC upto 20 years - Cycle duty at 27oC 80% DOD 1200 Cycles - Cycle duty at 27oC 20% DOD 4000 Cycles
Section 4 Freshening Charge General Batteries lose some charge during transportation as well as during the period prior to installation. A battery should be installed and given a freshening charge after receipt as soon as possible. Battery positive (+) terminal should be connected to charge positive (+) terminal and battery negative (-) terminal to charger negative (-) terminal. The charge intervals for storage is given in the tale below. RTTC NAGPUR Page 56 of 58
Temp in 0 c 32 37 42 47 52
Storage beyond this period without freshening charge can result in excessive sulphation of the plates. Requirement of Charger It is preferable to have the following characteristics in the battery charger being used with these batteries High voltage cut-off at 2.37 VPC Low voltage trip at 1.60 VPC Voltage ripple to be limited to 2 % of rms.
Voltage regulation to be limited to 1 % Constant Voltage Method Constant voltage is the only charging method recommended. Most modern chargers are of the constant voltage type. Determine the maximum voltage that may be applied to the system equipment. This voltage, divided by the number of cells connected in series, will establish the maximum volts per cell (VPC) that may be used. Table B lists recommended voltages and charge times for the freshening charge. Select the highest voltage the system allows but not exceeding 2.37 volts per cell to perform the freshening charge in the shortest time period. The charging current should be limited to a maximum of 20% of the rated capacity in Amps. Table B Cell Volts 2.25 2.30 Time 30 hrs 12 hrs
RTTC NAGPUR
Page 57 of 58
Note : Time periods listed in Table B are for temperatures from 15 oC to 40oC. For temperatures below 15oC double the number of hours. Charging The charging current should be limited to a maximum of 0.2 times of AH Capacity. Widely accepted charging methods use a current of 0.1xC10 (C10 = AH Capacity when discharged at 10 hr rate) Example: A 2000 AH VRLA battery is to be charged as under 0.2 x 2000 0.2 x 2000 = 400 Amps or 0.1 x 2000 = 200 Amps ( as per TEC recommendation) Raise the voltage to the maximum value not exceeding 2.37 volts per cell permitted by the system equipment. When charging current has tapered and stabilized (no further reduction for three hours), charge for the hours shown in the above table or until the lowest cell voltage ceases to rise. Correct charge time for the temperature at the time of stabilization. To determine lowest cell, monitoring should be performed during the final 10% of the charge time.