You are on page 1of 2

Tolok ukur Boiler Feed Water, dari :

DREW AMEROID INTERNATIONAL, BOONTON USA


Ref. Paper W. Herman, Consultant,
J.S. Blecher, Principle Consultant

Syllabus :
Water Treatment Program for Steam Generating System Originally presented at
corrosion 1979/NACE Meeting, Atlanta, Georgia.
March 12-16, 1979.
Drum
Pressure
(psig)
0 - 300
301 - 450
451 - 600
601 - 750
751 - 900
901 - 1000
1001 - 1500
1501 - 2000

BOILER FEED WATER GUIDELINES


Iron
Copper
Total
Electrical
(ppm Fe)
(ppm Cu)
Hardness
Conductivity
(ppm CaCO3) (Mhos/Cm2
)
0,100
0,050
0,300
< 20
0,050
0,025
0,300
< 20
0,030
0,020
0,200
< 20
0,025
0,020
0,200
< 20
0,025
0,015
0,100
< 20
0,020
0,015
0,050
< 20
0,010
0,010
< 0,001
< 20
0,010
0,010
< 0,001
< 20

pH

56
56
56
56
56
56
56
56

BOILER WATER GUIDELINES


Drum
Silica
Total Alkalinity
Specific
Pressure
(ppm, SiO2)
*
Conductance
pH (Max)
(psig)
(ppm CaCO3)
***
(mHos/cm)
0 - 300
150
700
7000
10,5 11,5
301 - 450
90
600
6000
9,5 10,5
451 - 600
40
500
5000
9 10
601 - 750
30
400
4000
9 10
751 - 900
20
300
3000
9 10
901 - 1000
8
200
2000
8,5 9,5
1001 - 1500
2
0 **
150
8,5 9,5
1501 - 2000
1
0 **
100
89
*
Minimum level or OH Alkalinity in Boilers below 1000 psi must be
individual specified with regard to Silica solubility and other components
of Internal treatment.
**
Zero in these cases refers to free Sodium or Potassium Hydroxide
Alkalinity
***
Unadjusted at 25 oC

Modificated by PT. TEKNOLINDO

You might also like