The Student Distribution Test Feeder

W. H. Kersting Milsoft Utility Solutions March 2009

s
IS VLGS

Reg

2 Line

I3ld
Y Load

I4ld
Delta Load Motor

IR VLGR

I2 VLG2

VLG1

I3 VLG3

It

I4 VLL4

IM

abc

The one diagram of the student test feeder is shown above. Data for this system are as follows: Equivalent System:
kVLL s := 115 Vpus := 1.05000 Z1sys := 5.6261+ j 27.408 Z0sys := 18.5865+ j 122.4028 on 115 kV side on 115 kV side kVLN s := kVLL s 3 kVLN s = 66.3953

Source Operating Voltages:


nominal phase A-B voltage: operating PU voltage: operating A-B voltage: ELL:= 115000e Epu := 1.05 ELL:= ELLE pu ELL = 120750 arg( ELL ) deg = 30
j 30 deg

Substation Transformer:
kVA := 12000 kVLN lo := kVLL lo 3 kVLL hi := 115 Delta Wye kVLL lo := 12.47

kVLN lo = 7.1996

Zpusub := .01 + j .1 Per-unit

Three Single-Phase Step Regulators Connected Y-Y:


Potential transformer ratio: Npt := 7200 120 Npt = 60

Current transformer primary rating: CTp := 500 CTc := 0.1 CT := CTp CTc volts Zohms = 49 + 100j Ohms CT = 5000

Compensator settings: RComp := 4.9 Zohms := XComp := 10.0

RComp + j XComp CTc

Set desired voltage level: Vset := 125

Distribution Three-Phase Line:


2.5' a b 3.0' 4.0' 4.5' c

n 25.0'

Phase Conductors: 336,400 26/7 ACSR Neutral Conductor: 4/0 6/1 ACSR Length of line: 2.0 miles

Motor Transformer:
kVAx := 2500 Y kVLLx hi := 12.470 Y kVLLx lo := .480

Zpux := .010 + j .050

Node 3 Wye Connected Three-Phase Load:


kW3 := 2000
1 2

PF3 := .95
1 2

Lagging Lagging Lagging

kW3 := 1500 kW3 := 1000


3

PF3 := .95 PF3 := .90


3

Node 4 Delta Connected Load:


kVA4 := 400
1 2

PF4 := .9
1 2

Lagging Lagging Lagging

kVA4 := 500 kVA4 := 300


3

PF4 := .85 PF4 := .95


3

The Induction Motor Data:


kVA := 1200 Rs := 0.0053 Rr := 0.007 Xm := 4.0 VLL:= 480 Xs := 0.106 Xr := 0.12 per-unit Prot := 0 per-unit per-unit

Operating Slip = 0.005