You are on page 1of 26

NEWLINK

Cabling Systems

J4

NEWLINK Entrenamiento Tcnico

NEWLINK
Cabling Systems

TIA / EIA 568-B.1


Distancias en el backbone
A

NEWLINK
Cabling Systems

HC HC
B

MC IC
C

ES
Horizontal Cross-connect ...... HC Intermediate X-connect Main Cross-connect ..... IC .......... MC

A UTP Balanceado - VOz UTP Balanceado - DATA Fibra Multimodo Fibra Monomodo 800 90 2000 3000

B 300 90 300 300

C 500 90 1700 2700


3

NEWLINK

Cuarto de Telecomunicaciones - TR
Requerimientos para el cuarto
AREA DEL PISO (m2) No. USUARIOS
@ 10 m2 / User

Cabling Systems

No. PUERTOS
2,5 tomas por usuario

GABINETES
RACKS

TR AREA (m2)

DIMENSIONES Sugeridas
Wall-mounted : 0,9m x 0,7m x 0,7m

200 500 1000 1500 1750 2000 2250

20 50 100 150 175 200 225

50 125 250 375 438 500 563

Wall Cabinet 12 RHUs 1 x 7 ft 1 x 7 ft 2 x 7 ft 2 x 7 ft 2 x 7 ft 2 x 7 ft

0.7 3.3 3.8 4.4 5.3 5.6 6

2,2m x 1,5m x 2,5m 2,4m x 1,6m x 2,5m 2,2m x 2,0m x 2,5m 2,4m x 2,2m x 2,5m 3,7m x 1,5m x 2,5m 2,5m x 2,4m x 2,5m

Note : Para espacios muy grandes, divida el piso en mdulos y luego aplique el mismo criterio

NEWLINK

Equipment Room - ER
Room Physical Requirements
TOTAL AREA (m2) No. USERS
@ 10 m2 / User

Cabling Systems

ER AREA (m2)

DIMENSIONS Suggested
3,0m x 2,0m x 2,5m 5,0m x 3,0m x 2,5m 5,0m x 4,0m x 2,5m 8,0m x 4,0m x 2,75m 12,0m x 5,0m x 3,0m 10,0m x10,0m x 3,0m

DEMAND kVA

A/C CAPACITY TR

200 500 1000 2000 5000 10000

20 50 100 200 500 1000

6 9 14 24 54 104

5 10 17 32 77 152

3 3 4 6 11 19

Note : Data is a reference, depend on several factors and particular considerations for each site. i.e. Offices, School, Bank, Hospital

NEWLINK

Cuarto de equipos - ER
Requerimientos para el cuarto
TOTAL AREA (m2) No. USUARIOS
@ 10 m2 / Usuario

Cabling Systems

AREA (m2)

DIMENSIONES Sugeridas
3,0m x 2,0m x 2,5m 5,0m x 3,0m x 2,5m 5,0m x 4,0m x 2,5m 8,0m x 4,0m x 2,75m 12,0m x 5,0m x 3,0m 10,0m x10,0m x 3,0m

DEMANDA kVA

A/C CAPACIDAD TR

200 500 1000 2000 5000 10000

20 50 100 200 500 1000

6 9 14 24 54 104

5 10 17 32 77 152

3 3 4 6 11 19

Note : Los datos son de referencia, depende de muchos factores y de consideraciones especiales para cada sitio. ejemplo: oficinas, escuelas, bancos, hospitales

NEWLINK
Cabling Systems

Conduit Capacity for Telecommunication Cables

EXTERNAL DIAMETER (mm) 4.6 CONDUIT DIAMETER


Inches mm Flex (mm)
CAT3 4p

5.6
CAT5E 4p

6.1
CAT6 4p

7.9
CAT3 25p

13.5
CAT5 25p

BOX SIZES Width Lenght Height 2" 2" 2" 3" 3" 3" 4" 4" 5" 5" 6"

CABLES QUANTITY 1 2 3 5 8 14 18 26 40 60 1 2 3 4 7 12 16 22 36 50 1 2 3 6 10 15 20 30 40 1 2 3 4 6 12 14 20 1 1 2 4 6 7 14

1/4" 3/8" 1/2" 3/4" 1" 1 1/4" 1 1/2" 2" 2 1/2" 3" 4"

8.0 12.0 15.0 20.0 25.0 35.0 40.0 50.0 70.0 75.0 100.0

8.5 12.0 16.5 22.5 28.5 36.0 47.5

2" 2" 4" 4" 4" 6" 8" 8" 10" 12" 12"

4" 4" 4" 12" 16" 20" 27" 36" 42" 48" 54"

Ejemplo
13 m

NEWLINK
Cabling Systems

47 m

25 m

40 m

35 m

ESPACIO
13 m
195 m 2 425 m 2

NEWLINK
Cabling Systems

1280 m 2

750 m 2

47 m

1175 m 2

120 m 2

250 m 2

AREA TOTAL = 4195 m 2

25 m

40 m

35 m

AREAS DE TRABAJO
13 m
20 AT 42 AT

NEWLINK
Cabling Systems

128 AT

75 AT

47 m

117 AT

12 AT

25 AT

TOTAL = 419 AT

25 m

40 m

35 m

CUBRIMIENTO DEL CUARTO DE TELECOMUNICACIONES


13 m

NEWLINK
Cabling Systems

60 m

60 m

47 m

25 m

40 m

35 m

UBICACION DE LOS CUARTOS DE TELECOMUNICACIONES

NEWLINK
Cabling Systems

13 m

60 m 47 m

60 m

25 m

40 m

35 m

NEWLINK
Cabling Systems

CALCULOS
419 reas de trabajo en total 2 tomas por cada rea de trabajo 838 cables UTP divididos in dos (2) cuartos de telecomunicaciones Utilizacin del 40 % Las bandejas principales deben planearse para 1050 cables

CAMINOS DE LAS BANDEJAS


13 m

NEWLINK
Cabling Systems

47 m

25 m

40 m

35 m

ACCESO INALAMBRICO
13 m

NEWLINK
Cabling Systems

47 m

25 m

40 m

35 m

NEWLINK
Cabling Systems

NEWLINK
Cabling Systems

NEWLINK
Cabling Systems

NEWLINK
Cabling Systems

NEWLINK
Cabling Systems

NEWLINK
Cabling Systems

NEWLINK
Cabling Systems

NEWLINK
Cabling Systems

CENTRO DE DATOS

TR-L CT PRINCIPAL EDIFICIOS ADM TR-A1 TR-B1 TR-IT1 ENTRADA DEL SERVICIO

BIBLIOTECA PABELLON A PABELLON B IT- LABS

ENTRADA DEL SERVICIO

ESQUEMAS DE UN BACKBONE CAMPUS

ENTRADA DEL SERVICIO & CUARTO DE TELECOMUNICACIONES CUARTO DE EQUIPOS Y PRINCIPAL DE TELECOMUNICACIONES

NEWLINK
Cabling Systems

TR-H4

TR-H3

3
TR-H2 + DATA CENTER

TR-H1

1
ENTRADA DEL SERVICIO

EDIFICIO ADMINISTRATIVO. ESQUEMA DEL BACKBONE

ENTRADA DEL SERVICIO & CUARTO DE TELECOMUNICACIONES CUARTO DE EQUIPOS Y PRINCIPAL DE TELECOMUNICACIONES

You might also like