Logic Solver for Tank Overfill Protection

SECTION 1

Logic Subsystem (Safety Trip Alarm, 1oo2) EQUATION D DU D DU D T1 2 T1 3


=

CALCULATION = DD D DD D 1.7E-07 + 8.6E-08 =

RESULT 2.6E-07

DD

DU

tCE =

+ MTTR +

MTTR

(8.6E-08/2.6E-07)(8760/2+8)+(1.7E-07/2.6E-07)8

1480

tGE =

+ MTTR +

MTTR

(8.6E-08/2.6E-07)(8760/3+8)+(1.7E-07/2.6E-07)8

992

PFDAVG = 6((1-D) DD+ (1-)DU)2tCEtGE = + D DDMTTR+ DU (T1/2+MTTR)

2((0.9x1.7E-07)+(0.9x8.6E-08)2 1480x992 + (0.1x1.7E-07x8) + (0.1x8.6E-08)((8760/2)+8)

3.80E-05

Final Element Subsystem (Actuated Valve, 1oo1) EQUATION D DU D T1 2


=

CALCULATION = DD D 5.6E-07 + 2.8E-07 =

RESULT 8.4E-07

DD

DU

tCE =

+ MTTR +

MTTR

(2.8E-07/8.4E-07)(8760/2+8)+(5.6E-07/8.4E-07)8

1468

PFDAVG = (DU + DD) tCE

(2.8E-07 + 5.6E-07)1468

1.2E-03

The PFDAVG for the system is calculated from the sum: PFDSYSTEM = = PFDS + PFDL + PFDFE 1.11E-05 + 3.80E-05 + 1.2E-03

= 1.3E-03

Referring to Table A.1 (Appendix) shows this is comfortably in the SIL 2 range (10-4 to < 10-2)

Design, Installation and Operational Considerations

In the case where redundant channels are used to support a voting configuration (1oo2 in the SIL 2 overfill protection system), the voting is implemented by simply wiring the relay contacts from the two STA. This ensures that a trip from either STA will de-energize the solenoid, as shown in Figure 4.