Logic Solver For Tank Overfill Protection: Equation Sensor Subsystem (Level Sensor, 1oo1) Calculation Result
Logic Solver For Tank Overfill Protection: Equation Sensor Subsystem (Level Sensor, 1oo1) Calculation Result
Now we need to calculate the PFDAVG for each subsystem by referring to the failure data in Table 1 (above), the assumptions listed above for T1 and MTTR and the equations in the Appendix. Sensor Subsystem (Level Sensor, 1oo1) EQUATION D DU D T1 2
=
RESULT 1.65E-07
DD
DU
tCE =
+ MTTR +
MTTR
(1.4E-08/1.65E-07)(8760/2+8)+(2.5E-07/1.65E-07)8
674
PFDAVG = (DU + DD) tCE Logic Subsystem (Safety Trip Alarm, 1oo1) EQUATION D DU D T1 2
=
(2.5E-08 + 1.4E-07)674
1.11E-04
RESULT 2.6E-07
DD
DU
tCE =
+ MTTR +
MTTR
(8.6E-08/2.6E-07)(8760/2+8)+(1.7E-07/2.6E-07)8
1457
PFDAVG = (DU + DD) tCE Final Element Subsystem (Actuated Valve, 1oo1) EQUATION D DU D T1 2
=
(8.6E-08 + 1.7E-07)1457
3.8E-04
RESULT 8.4E-07
DD
DU
tCE =
+ MTTR +
MTTR
(2.8E-07/8.4E-07)(8760/2+8)+(5.6E-07/8.4E-07)8
1468
(2.8E-07 + 5.6E-07)1468
1.2E-03
As explained in the Appendix, the PFDAVG for the system is calculated from the sum: PFDSYSTEM = = PFDS + PFDL + PFDFE 1.1E-04 + 3.8E-04 + 1.2E-03
= 1.7E-03
-5-
www.miinet.com