TEST CERTIFICATE OF TRANSFORMER Client Plant Location 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.

8 Gujarat State Electricity Corporation Ltd. UKAI TPS-Unit-6 - HCSD System TRANSFORMER 2 ; 6.6 / 0.433 KV Name Plate details of transformer: Make : AREVA Serial Number : D 10502 Voltage ratio : 6.9 / 0.433 KV Rating : 2500 KVA No. of taps : 05 Tap changer : OFF LOAD Vector group : Dyn11 % Impedance : 5.86%

Macawber Beekay Private Ltd.

Tested on Tested by Witnessed by

14.12.2013 Nitish Singh

VC Patel

2.0 Insulation Resistance test: Insulation resistance test between Values in M. Ohms 3.0

HV E(5000 V)

HV LV(5000 V)

LV E(500V)

2.2 G

2.2 G

23 M

Voltage ratio and tap continuity test: Applied voltage: RY: 430 V; YB: 427 V; BR: 430 V Measured voltage, Volts Tap position RY YB BR RN YN 1 2 3 4 5

BN

Tap continuity OK OK OK OK OK

25 26 27 27 28

25 26 27 27 28

25 26 27 27 28

13 14 14 15 15

13 14 14 15 15

13 14 14 15 15

4.0

Magnetic balance test : Tap position : 3(CENTRE TAP) Applied voltage, Volts YB BR RY YB

Measured voltage, Volts BR RN YN BN

RY

424 223.8 113.2

316.2 430 316.9

106.5 207 431.2

28.1 24.8 7.7

7.9 24.2 28.4

20.2 0.66 20.71

16.12 8.33 4.32

12.00 16.12 11.98

4.04 7.93 16.32

Nitish Singh M/s MBPL

VC Patel/Gaurav Omar M/s GSECL

5.0 Vector group test: R - r shorted and 3 - Phase supply given to HV side of transformer keeping tap position at 3rd tap Conditions to be fulfilled by vector group Dyn11 when R - r shorted are : 1. VRY = VRn + VYn 2. VYb = VYy 3. VBb < VBy Measured voltage readings are as follows: RY RN YN YB Yy Bb By

431
6.0

13
Magnetizing Current test: Phases

415

407

407

405

432

Current Value, milli A 7.0 Winding Resistance test: 1) AT Primary side: Tap position 1 2 3 4 5 1) AT Secondary side: Tap position 3

42.9

31.3

29.4

Value in m RY YB BR

140.1 136.7 133.5 130.0 126.7

139.8 136.4 133.0 129.7 126.5

140.1 136.7 133.5 130.1 127.0

Value in m RY YB BR RN YN BN

0.616

0.624

0.631

0.473

0.482

0.462

7.0 Conformity test: Sr. No. 7.1 7.2 8.0 Abnormality, if any Remarks

Description

Remarks OK OK

Visual external damage to any part of the transformer

: TESTED AS ABOVE

Nitish Singh M/s MBPL

VC Patel/Gaurav Omar M/s GSECL