The document summarizes the results of a trial run of an All-In-One product used to control microbiological growth, scale, and corrosion in a 125RT cooling tower system. Key findings over the 7 week trial included: no new algae growth, corrosion, or sludge formation with a bacteria count maintained around 10^5 CFU with a weekly dose of 2 liters of All-In-One. Based on the trial, the document recommends minimum weekly dosing to maintain free halogen levels and control microbiological growth, with recommended monthly dosages ranging from 4 to 32 liters depending on the size of the cooling tower system.
The document summarizes the results of a trial run of an All-In-One product used to control microbiological growth, scale, and corrosion in a 125RT cooling tower system. Key findings over the 7 week trial included: no new algae growth, corrosion, or sludge formation with a bacteria count maintained around 10^5 CFU with a weekly dose of 2 liters of All-In-One. Based on the trial, the document recommends minimum weekly dosing to maintain free halogen levels and control microbiological growth, with recommended monthly dosages ranging from 4 to 32 liters depending on the size of the cooling tower system.
The document summarizes the results of a trial run of an All-In-One product used to control microbiological growth, scale, and corrosion in a 125RT cooling tower system. Key findings over the 7 week trial included: no new algae growth, corrosion, or sludge formation with a bacteria count maintained around 10^5 CFU with a weekly dose of 2 liters of All-In-One. Based on the trial, the document recommends minimum weekly dosing to maintain free halogen levels and control microbiological growth, with recommended monthly dosages ranging from 4 to 32 liters depending on the size of the cooling tower system.
All-In-One Product Profile A biocide with scale and corrosion inhibitor Use for medium to small size commercial and industrial cooling water systems that do not control cooling water pH. Designed to prevent algae and slime build up with good calcium scale and metal corrosion control Data Tested at 125RT Cooling Tower. Dose 2 litre All-In-One every week. No bleed off and cleaning were carried out. TDS maintain at 580ppm, TH 272ppm, PO 4 24.8ppm, Chloride 244ppm, m-alkalinity 268ppm and free Cl 2 1.3ppm Comparison
1 st week 19/7/2007 2 nd week 26/7/2007 Comparison
4 th week 9/8/2007 5 th week 23/8/2007 Comparison
6 th week 30/8/2007 7 th week 7/9/2007 Microbiological Control Date Bacteria Count / CFU 19/7/2007 10 3 26/7/2007 10 4 9/8/2007 10 5 7/9/2007 10 5 Observation and Comments No new development of algae No corrosion sign No sludge formation Bacteria count at 10 5 CFU Require minimum weekly dosage to compliment free halogen losses
Chemical Dosage Recommendation RT 100RT 300RT 600RT Daily Operation Hours 8 - 12 24 8-12 24 8-12 24 Dosage 1L Once/ week 1L Twice/ Week 2L Once/ week 2L Twice/ Week 4L Once/ week 4L Twice/ Week Total Dosage/ Month 4 L 8 L 8 L 16 L 16 L 32 L