You are on page 1of 6

TABLE OF CONTENTS Glossary

Page
Glossary 1 Refer to the figure(s) in the paragraph "Assembling and
disassembling of the heat exchanger" for an explanation
1 Introduction 2 of the designation of parts of the heat exchanger in the text.
1.1 Remarks 2
1.2 Guarantee and liability 2 Conditioned circuit
1.3 Environment 2 Closed circuit with a non-corrosive medium.
1.4 Safety 2
1.5 Inhibitors 2 Unconditioned circuit
Open circuit (for instance seawater) or a closed circuit with a
2 Installation and start-up 2 corrosive medium.
2.1 Receipt 2
2.2 Installation 2 Coating
2.3 Start-up 3 Layer protecting the coated material against corrosion. The
coating separates the coated part from the corrosive medium.
3 Maintenance 3
3.1 Cleaning and inspection intervals 3 Inhibitor
3.2 Anodic protection 3 Additive to a medium flowing through the heat exchanger
3.3 Cleaning of the heat exchanger 3 which –expressly tailored to that medium- reduces the
3.3.1 Mechanical cleaning of the tubeside 3 quickness of chemical reactions like corrosion.
3.3.2 Chemichal cleaning of the shell-/tubeside 3
3.4 Shut down periods 3 Anodes / anodic protection
3.5 Assembling and disassembling of the heat exchanger 3 Introducing a base metal to a more precious metal (on purpose)
3.6 Instructions for gaskets and bolting 5 in order to protect this metal. The part serving as anode is being
3.6.1 Gaskets 5 sacrificed.
3.6.2 Bolting 5

4 Trouble shooting & repairs 5


4.1 Thermal performance too low 5
4.2 Leaking tubes / tube-tubesheet-connection 5
4.3 Leaking gaskets 5

5 Spare parts & tools 5


Appendix A: Instructions for conservation 6
Appendix B: Adresses 6
Appendix C: Constructional directions for entering a 6
P-type heat exchanger in a piping design

The P-type heat exchanger can be subdivided into four sizes:


P10, P13, P20 and P28.
The number indicates the shell size in centimeters. The construc-
tion of the P10 is slightly different from the others. When neces-
sary this manual has special texts (indicated with: "For P10
only:") which apply to the P10 only.

There are two models (P10 only in MV): the IV (Industrial Version)
and the MV (Marine Version). Main difference is the anodes in
the tubeside circuit of the MV. It is pointed out in the text when
there are differences between the two models.

In addition this manual applies to P-heat exchangers with plain


tubes as well as PF heat exchangers with bundles with fins.

P.02.02 1 Manual Bloksma P-type Heat Exchanger


1 Introduction 2 Installation and start-up

1.1 Remarks 2.1 Receipt


* Read this instruction manual before proceeding. At receipt check the packaging and the heat exchanger:
* Important documents besides this instruction manual are * report any damage to Bloksma
the order confirmation, the specification sheet, the * compare the data on the nameplate, confirmation of the
drawing(s) and the sheet with constructional directions order and on the drawing
(appendix C). In the specification sheet the design pressures * check whether or not the correct instruction manual is
and temperatures are listed that must of course not be present by comparing the article number on the cover sheet
exceeded. with the article number of the instruction manual on the
confirmation of order
1.2 Guarantee and liability
The "General conditions of Bloksma B.V." are applicable. Also Always store the heat exchanger in a dry room, free of large
refer to the confirmation of the order for possible additions. temperature changes. When the heat exchanger is not being put
into operation immediately after receipt, follow the "Instructions
Not covered by the guarantee are loss of performance and/or for conservation" (Appendix A).
damage to the heat exchanger as a result of:
* not following the instructions in this manual 2.2 Installation
* replacement with non-original parts Warning: Beware of any rust preventive layers (see "Instructions
for conservation") that might still be present in the heat exchan-
1.3 Environment ger before proceeding.
* The environmental laws and rules of the area where the heat * Remove all protective plugs and covers from the connecting
exchanger is installed, always have to be respected. flanges prior to installation of the heat exchanger.
* Always be on the alert to the possibility of leakage. * A 1- or 3-pass model (tubeside) has to be mounted in such a
* When disposing of the unit at the end of its lifespan, see to it way that shell- and tubeside will be in counterflow.
that this takes place according to the then applicable * Check whether the positions of the vent and drain
regulations. connections on the heat exchanger correspond with the
mounting position of the heat exchanger.
1.4 Safety * Mount the heat exchanger level and square on a flat surface
Some symbols are used in the text to underline safety aspects: in order for the pipe connections to be made without forcing.
* Do not weld anything to the heat exchanger.
* Mount one support in a fixed position, while the other one is
mounted in such a way that it is able to slide in the direction
of the longitudinal axis of the heat exchanger. The heat
Pay attention: depending on the application the heat exchanger exchanger will thus be able to expand under thermal stress.
will be hot during operation * When installing types bigger than P10 vertically, the
waterbox at which the position of the tubesheet is fixedº ,
has to be located on top.
* Before connecting piping to the heat exchanger flanges,
make sure that the gasket surface is clean and free from
scratches and other defects. Always use new gaskets, of the
Maintenance and repair: depressurize both circuits of the heat correct type and tighten the bolts crosswise.
exchanger and let them cool down to ambient temperature. * Take care when lifting the heat exchanger. Use at least two hoops
around the shell of the heat exchanger for lifting purposes.
In connection with safety every Bloksma heat exchanger is * Check for the presence and correct positions of drain/vent
tested under higher pressure than the design pressure before it connections in both circuits.
leaves the factory. This applies to heat exchangers that are not * Install the heat exchanger and the piping in such a manner
tested by a certification agency. that there is still enough room to disassemble (part of) the
heat exchanger (tubebundle, drain plugs, etc.).
1.5 Inhibitors
There can be reasons to add an inhibitor to one of the circuits of ºOn a 2-pass model the side of the heat exchanger at which the
the heat exchanger. Contact a specialised company, which can position of the tubesheet is fixed is always the side where the
also check for harmfulness of the inhibitor to the materials of tubeside medium enters and exits the heat exchanger. On 1-pass
the heat exchanger (see specification sheet). Follow the instruc- models this is the side on which fixation plates are are bolted
tions of the supplier for use of the inhibitor. between waterbox and shell (on the other side distance rings are
bolted between shell and waterbox). Furthermore the side of the
heat exchanger where the serialnumber is, is also the side with
the fixed tubesheet.

P.02.02 2 Manual Bloksma P-type Heat Exchanger


2.3 Start-up chemical solution through the heat exchanger. Another possibility
Do not exceed the design temperatures and design pressures as is disassembling of the heat exchanger and submerging the
stated on the nameplate and specification sheet. Avoid abrupt tubebundle in a tank filled with a chemical solution. Remove any
temperature fluctuations; these can cause leaking of tube-to- plastic partitions (on 2- or 3-pass heat exchangers to divide the
tubesheet or other connections. tubeside circuit) from the tubesheet(s) first.

* Make sure that the cold medium circulation is established There are several international companies (example in Appendix
first, followed by the gradual introduction of the hot medium. B) which supply equipment and fluids for chemical cleaning of
* Vent both circuits. heat exchangers. Their specialized cleaning centres, situated at
* Vent both circuits again when the operating temperatures ports all over the world, are able to give you a cleaning advise or
and pressures are reached. to clean the heat exchanger for you. To give an idea of the
* Check for leakage. possibilities, an example of a cleaning procedure is given below.
Do not deviate from the flows as stated on the specification Please note: The cleaning advice below is just an example.
sheet. Higher or lower velocities can cause erosion or corrosion Cleaning methods and procedures, as well as fluids for cleaning
respectively. will differ depending on the materials of the heat exchanger (see
specification sheet) and the application.
Avoid standstill: at non-conditioned circuits this may cause corrosion.
In case of standstill follow the instructions for shut down periods. This cleaning advise is meant for waterheaters/coolers.

If the heat exchanger is equipped with anodic protection (see Descalant NF (inhibited cleaning agent)
specification sheet) you will have to inspect the anodes (or part * Submerge the tubebundle (time is dependend on the degree
that functions as anode) when you are starting up the heat of fouling) in a tank with dissolved cleaning agent
exchanger after a shut down period. * After cleaning neutralize the tubebundle and the cleaning
agent with a special neutralizing fluid
3 Maintenance * Flush the tubebundle with fresh water
* Dry the tubebundle
If necessary refer to "Assembling and disassembling of the heat
exchanger" for (dis-)assembling instructions. 3.4 Shut down periods
During shut down periods longer than a week the heat exchanger
3.1 Cleaning and inspection intervals has to be drained completely and dried by means of preheated
Preventive maintenance of the heat exchanger is a user responsi- compressed air. In fact this also has to be done during short shut
bility. The tubeside circuit is usually the more fouling side of the down periods (longer than a day) when there is risk of freezing,
heat exchanger. Because the degree of fouling strongly depends and it also applies when a corrosive medium is used in the heat
on the operating conditions we recommend the following: exchanger. After draining a corrosive medium, the heat exchanger
* Inspect the tubeside at least quarterly. has to be rinsed with fresh water. Stopping of the flows, cooling
* Inspect the shellside at least twice a year. down and draining of the heat exchanger has to be done in a
With the results of these inspections you will be able to manner to minimize thermal stresses on the heat exchanger.
determine the required cleaning intervals. Always keep
performing regular inspections. Never stop one of the flows of the heat exchanger while the
other one stays in operation, because of the risk of boiling.
3.2 Anodic protection
Not applicable for IV models. 3.5 Assembling and disassembling of the heat exchanger
The MV models of P-type heat exchangers are fitted with anodic The circumferences of the tubesheets are fitted with three
protection: the tubeside circuit is provided with anodes. When grooves. The two outer grooves carry O-rings (sealing between
inspecting the tubeside of the heat exchanger also inspect the shell- and tubeside). At one of the tubesheets the middle groove
state of the anodes (always drain the tubeside circuit before is for the fixation of the position of the tubebundle by means of
removing the anodes). ‘fixationplates’ (this tubesheet is called the fixed tubesheet).

3.3 Cleaning of the heat exchanger

3.3.1 Mechanical cleaning of the tubeside


The tubes can be cleaned with a tube brush. Use original Bloksma
brushes only; these have the correct dimensions and are of a suitable
material. Other brushes may damage the protective layer that is
in the normal course of events present on the tubewalls.

3.3.2 Chemichal cleaning of the shell-/tubeside


Warning: Chemical cleaning may damage the heat exchanger.
Make sure your supplier of a cleaning agent verifies and
confirms the compatibility of his product with the materials of
the heat exchanger (see specification sheet).

Cleaning of the shellside will normally be necessary seldom.

The shell- as well as the tubeside can be cleaned by circulating a

P.02.02 3 Manual Bloksma P-type Heat Exchanger


In case the heat exchanger is placed vertical, disassemble the
upper waterbox first. This is the side with the fixationplates.
Fasten the fixationplates immediately with the nuts before pro-
ceeding. For P10 only: A vertically placed P10 will always have to
be disassembled completely because the the tubebundle does
not stay in position.

* remove the waterboxes by untightening the nuts


(the fixationplates come loose as well)
* 2- or 3-pass heat exchangers have plastic partitions on the
tubesheet(s) for dividing the tubeside circuit; mark their
position and remove them
* mount the fixationplates again with the nuts (not necessary
when the tubebundle is going to be removed (see step 2))
* remove the first O-ring from both tubesheets
* only for a pressure test: pressurize the shellside again.

Depressurize the shellside again after the pressure test. For P10
only: Remember that the tubebundle is not fixated!

1 2 3 4 5
Step 2: Removing the tubebundle
* drain the shellside circuit, by opening the drain in the lowest
1 Tubesheet 4 Shell point and the vent in the highest point
2 O-ring 5 Tubes * mark the position of the tubebundle
3 Fixationplate * move the tubebundle to one side until the second O-ring
shows (do not move the tubebundle further than necessary)
Figure 1: Schematic drawing of tubesheet construction and remove this O-ring
* move the tubebundle to the other side and remove the
For P10 only: Instead of fixationplates the P10 has a metal spring second O-ring on this side as well
ring in the middle groove of the tubesheet. As soon as the bolts * carefully pull the tubebundle from the shell
are untightened the position of the tubebundle is no longer * support the tubebundle at the baffles when lifting it, but be
fixated. Tubeside inspection or cleaning remains possible, careful not to bend the baffles (this will affect the thermal
but extra attention is required because the tubebundle is not performance of the heat exchanger)
fixed anymore. Except when performinge a pressure test, we
recommend to drain both circuits. Step 3: Assembling
* assemble the heat exchanger in reversed order
For tubeside inspection, shellside pressure testing or (pay attention to the earlier made marks):
cleaning of the tubes with a tubebrush, only the tube- Mounting of the tubebundle (only in case it was removed):
side connections and the waterboxes (these are the * push the tubebundle in the shell (let it stick out of the shell
parts on both ends of the shell, on which the tubeside a little bit)
connections are made) need to be removed (follow step 1 and 3). * mount the inner O-ring on the first tubesheet
Pay attention: when the nuts are untightened the fixationplates * move the tubebundle further and let it stick out a little bit
are also untightened, so the tubebundle comes loose. In order to on the other side of the shell
fixate the tubebundle temporarily, fasten the fixationplates with * mount the inner O-ring on the second tubesheet
the nuts.
Hint: when it is difficult to move the tubebundle through the
For shellside inspection (for instance), the tubebundle shell because the already mounted O-ring is hard to
has to be removed completely (follow step 1, 2 and 3), compress, you can use a strip between tubesheet and
and both circuits have to be drained. waterbox and then tighten two of the four bolts and nuts
* move the tubebundle in its final position
When assembling as well as disassembling follow the
"Instructions for gaskets and bolting". Tubeside assembly:
* mount the outer O-rings on both sides
Step 1: Tubeside disassembling * mount the plastic partitions on the tubesheets of 2- or 3-pass
models
* mount the fixationplates (for P10 only: mount the metal
spring ring)
* mount the waterboxes and all connections
* depressurize both circuits * start-up the heat exchanger again:
* let both circuits cool down to ambient temperature * make sure that the cold medium circulation is established
* drain the tubeside circuit, by opening the drain in the lowest first, followed by the gradual introduction of the hot medium
point and the vent in the highest point * vent both circuits
* mark the position of all parts that will be disassembled, so
they can be mounted in the correct position later on

P.02.02 4 Manual Bloksma P-type Heat Exchanger


* vent both circuits again when the operating temperatures of 2- or 3-pass heat exchangers; the position of the
and pressures are reached tubebundle (this might accidentally be mounted rotated 180°
* check for leakage around its axis))

3.6 Instructions for gaskets and bolting 4.2 Leaking tubes / tube-to-tubesheet connection
It is often very hard to determine whether leakage occurs because
3.6.1 Gaskets of a leaking tube or because of a leaking tube-to-tubesheet con-
Two types of gaskets are being used in this heat exchanger: nection. The shellside of the heat exchanger can be hydrotested,
after disassembling the tubeside. Follow the instructions in
O-rings: After disassembling the heat exchanger never use the "Assembling and disassembling of the heat exchanger".
old O-rings again. Replace them with original Bloksma O-rings. Subsequently pressurize the shellside. After hydrotesting depres-
surize and drain the shellside again. Assemble the heat exchan-
Warning: The O-rings have to be lubricated with a special O-ring ger again.
lubricant (O-ring silicone paste or Parker O-lube) for easy assembly
and a good sealing capacity. Lubricants not suited for O-rings can The tubes are roller expanded into the tubesheet. It is either not
affect the sealing capacity of the O-ring (for instance do never possible (finned tubebundles) or relatively complicated (unfin-
use vaseline). Any warranty claim will be rejected when unsuited ned tubebundles) to replace a leaking tube, but it can be plug-
lubricants are used. ged with soft copper Bloksma plugs (other materials are too
hard and may cause leakage of the adjacent tube-to-tubesheet
Soft metal rings: After disassembly of the heast exchanger never connections) in both tube ends. A maximum of approximately
use the old soft metal rings again. Replace them with new ones 10% plugged tubes will not influence the thermal performance
for good sealing. of the heat exchanger too much. Contact Bloksma when more
than 10% of the tubes is plugged.
3.6.2 Bolting
Check bolts and nuts for damages. Tighten the bolts crosswise 4.3 Leaking gaskets
(see figure 2). This also applies to connecting piping to the heat * Check the gasket surfaces.
exchanger. Make sure the gasket surface is clean (remove dirt * Remove dirt or corrosion residues
and any corrosion residues) and undamaged. * Mount new gaskets

It is possible to determine which of the O-rings is leaking, by


3 1 determining the medium that is leaking from the heat exchanger.

5 Spare parts & tools

Available spare parts and tools for P-type heat exchangers:

* Set of gaskets (four O-rings)


* Soft copper plugs
* Nylon tube brush
* Bolts / nuts
* Complete tubebundle
2 4 * For P10 only: Metal spring ring
* Fixationplates (for types > P10)
* Plastic partitions (not for 1-pass heat exchangers)
Figure 2: (Un-)bolting sequence * Water box
* Cover
4 Trouble shooting & repairs * Anode

When ordering spare parts, please refer to the Bloksma drawing


number (listed on name plate).

4.1 Thermal performance too low


Check:
* whether all connections have been made according to the
drawing
* whether the heat exchanger and the system have been
properly vented
* whether the flows are according to the specification (check
all valves, lines and pumps, as well as the flow directions)
* whether the shell- as well as the tubeside have been cleaned
recently (fouling can cause a drop in performance and an
increased pressure loss; an increased pressure drop is a good
indication that cleaning is necessary)
* whether the heat exchanger has been reassembled properly
after disassembly (the plastic partitions on the tubesheet(s)

P.02.02 5 Manual Bloksma P-type Heat Exchanger


Appendix A: Instructions for conservation Appendix C: Constructional directions for
including a P-type heat exchanger in a
Standard conservation (controlled conditions) piping design.
All heat exchangers supplied by Bloksma are treated with a rust
preventive layer (on both shell- and tubeside). This layer will pro- Pay attention to the following points:
tect the heat exchanger when it is stored at controlled condi- * Level and square mounting possibility.
tions, i.e. inside, in a dry room at constant temperature. When * Bends in the piping have to be located at a distance of at
these conditions are met, the heat exchanger can be stored wit- least three times the nominal diameter of the pipe from the
hout special treatment for a longer period (up till 24 months). inlet of the heat exchanger.
The rust preventive layer can be removed with a mineral solvent * When a vaporizing cryogenic medium is used, the heat
(petroleum). exchanger has to be placed under an angle of 3° - 10°, in order
for the vapor to be able to exit the heat exchanger, helped by
Advise for conservation (uncontrolled conditions) natural circulation.
When the above mentioned storage conditions are not met, you * Check if vent and drain connections are present in both
will have to fill the heat exchanger with an inert gas and all ope- circuits of the heat exchanger (when not on the heat
nings have to be closed airtight (additionally silica gel can be exchanger then make them in the piping).
added to absorb liquids). Alternatively, the heat exchanger can * Put a filter (with a permeability of 3 mm.) before the inlet of
be treated with a rust preventive liquid of a type suited for long both circuits of the heat exchanger.
term conservation. * Stress- and vibration free mounting possibility of the
When necessary contact a specialised company. Take the materi- connections and the supports (fit expansion bellows and/or
als of the heat exchanger (see specification sheet) into conside- silencer blocks when necessary).
ration. Be aware that in uncontrolled storage conditions large * Disassembling possibility of the tubebundle (and other parts
amounts of water can accumulate in the heat exchanger as a like drain and vent plugs).
result of condensation. * Expansion possibility of lockable liquid circuits.
* Danger of freezing of liquid circuits.
Appendix B: Adresses * The design data of the heat exchanger on the specifiation-
sheet and the drawing. For instance the flows: deviating
Chemichal cleaning and products for chemichal cleaning from them can cause unacceptable high or low velocities.
A (temporary) lower flow is acceptable when caused by a
Ashland Chemical Nederland B.V. controlsystem and a conditioned circuit is involved. Avoid
standstill (unless the heat exchanger is drained and flushed
Drew Marine Division with fresh water).
Malledijk 20 * When adding an inhibitor to one of the fluids in the heat
3208 LA Spijkenisse exchanger, always check whether this inhibitor can be
The Netherlands harmful for the materials of the heat exchanger
Telephone : + 31 (0)181-457074 (see specification sheet).
Telefax : + 31 (0)181-625792 * Make sure that in case of flow control (with conditioned
Internet: www.ashchem.com circuits only) this is done gradually (no ‘on-off-control’).
* Although this will almost never occur in practice, Bloksma
reserves the right (according to TEMA RGP-RCB-2) to plug a
maximum of 1% of the tubes.
* Always check whether both fluids are compatible with the
materials of the heat exchanger; Bloksma chooses the
materials judging on the fluids specified by the customer,
but is often not well informed about possible
contaminations, higher or lower than normal degrees of
acidity and other for the choice of materials important
proprties.
* Check whether the materials of the connecting piping are
compatible with the materials of the heat exchanger (when
the materials of the bundle are, from a corrosion point of
view, weak in comparison with the materials of the piping,
the bundle will corrode faster than expected).

www.bloksma.net

P.02.02 6 Manual Bloksma P-type Heat Exchanger

You might also like