You are on page 1of 3

MechaTronics Co.

External static pressure Calculation


AHU-B5_G01
Al-Hazm Mall

HVAC

Project

Designed by

Project No.

M.M

Date

4 June 2014

DUCT
SECTION

CFM

SIZE (MM)

LENGTH

B
FT.

DIA.

FT.

FT.

15.0

1/27

Sheet
Circ:

FITTINGS
Br
R
FT.

of

27

MA/CAL/1

/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

5.0

20.0

26.6

991

0.04

0.012

AC SUPPLY DUCT
1

4,475

1000

450

719.2

2.0

6.6

4,475

1000

450

719.2

3.0

9.8

30.0

5.0

35.0

44.8

991

0.04

0.020

3,580

900

400

642.9

2.2

7.2

30.0

5.0

35.0

42.2

993

0.05

0.021

3,133

900

350

597.3

4.0

13.1

30.0

5.0

35.0

48.1

1006

0.06

0.027

2,238

700

350

533.2

4.0

13.1

30.0

5.0

35.0

48.1

902

0.05

0.026

1,341

600

250

413.7

3.6

11.8

30.0

5.0

35.0

46.8

898

0.07

0.034

894

500

200

337

2.2

7.2

5.0

20.0

27.2

902

0.09

0.025

447

500

150

286.8

4.2

13.8

5.0

5.0

18.8

623

0.06

0.011

15.0

AC SUPPLY DUCTS & FITTINGS

0.176

AC RETURN DUCT
8

4,475

650

550

653

4.0

13.1

15.0

10.0

25.0

38.1

1202

AC RETURN DUCTS & FITTINGS

0.07

0.027
0.027

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.176

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC RETURN DUCTS & FITTINGS

0.027

RETURN AIR GRILLE

0.150

SUB-TOTAL
ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.878
0.088
0.966

prepared by/ Engr.Mohamed Mosaad

prepared by/ Engr.Mohamed Mosaad