You are on page 1of 3

MechaTronics Co.

External static pressure Calculation

AHU-UB_08
Al-Hazm Mall

HVAC

Project

Designed by

Project No.

M.M

Date

CFM

SIZE (MM)

LENGTH

DIA.

FT.

17/27

Circ:

MA/CAL/17

4 June 2014

DUCT
SECTION

Sheet

FT.

FT.

FITTINGS
Br
R
FT.

of

27
/File

TOTAL
EQUIV.

AIR

FRICTION

EQUIV.

VELOCITY

DROP/100 FT

FRICTION
DROP

FT.

LGTH. (FT.)

LGTH. (FT.)

fpm

IN W.G.

IN W.G.

AC SUPPLY DUCT
1

4,725

750

500

666

4.6

15.1

30.0

10.0

40.0

55.1

1221

0.07

0.039

3,150

550

500

573.1

7.7

25.3

30.0

10.0

40.0

65.3

1099

0.07

0.046

1,575

500

350

455.5

6.6

21.7

0.0

21.7

870

0.06

0.013

1,575

500

350

455.5

4.8

15.6

50.0

65.6

870

0.06

0.040

1,050

350

350

382.6

1.1

3.6

0.0

3.6

822

0.07

0.002

525

350

350

382.6

1.2

3.9

0.0

3.9

411

0.02

0.001

15.0

30.0

5.0

AC SUPPLY DUCTS & FITTINGS

0.141

AC RETURN DUCT
6

4,725

550

500

573.1

1.9

6.2

15.0

4,725

550

500

573.1

8.0

26.2

15.0

4,725

550

500

573.1

1.4

4.4

0.0

30.0

0.0

5.0

20.0

26.2

1649

0.15

0.039

0.0

45.0

71.2

1649

0.15

0.105

5.0

5.0

9.4

1649

0.15

0.014

AC RETURN DUCTS & FITTINGS

0.157

Abbreviations:
E = Elbow Equivalenght Length

15 Ft.

AC SUPPLY DUCTS & FITTINGS

0.141

B = Branch Equivalenght Length

30 Ft.

VOLUME DAMPER ( x 3 )

0.375

Br = Branch Run Equivalenght Length

15 Ft.

SUPPLY AIR DIFFUSER

0.150

R = Reducer Equivalenght Length

5 Ft.

AC RETURN DUCTS & FITTINGS

0.157

RETURN AIR GRILLE

0.150

SOUND ATTENUATOR

0.250

SUB-TOTAL

1.223

ADD 10%
TOTAL FRICTION DROP IN WG

prepared by/ Engr.Mohamed Mosaad

0.122
1.345

25th Flr., Chatham House


116 Valero cor. Herrera Sts.
Salcedo Village, Makati City
1227 Philippines
Tel. (632) 887-1391
Fax (632) 887-1172
E-mail mpi@meinhardt.com.ph

prepared by/ Engr.Mohamed Mosaad