External static pressure Calculation


AHU-UB_01 Qty.(2) HVAC
Project Al-Hazm Mall Project No. Sheet 10/27 of 27
Designed by M.M Date 4 June 2014 Circ: MA/CAL/10 /File
TOTAL AIR FRICTION FRICTION
E B Br R EQUIV. EQUIV. VELOCITY DROP/100 FT DROP
W H DIA. M FT. FT. FT. FT. FT. LGTH. (FT.) LGTH. (FT.) Fpm IN W.G. IN W.G.
AC SUPPLY DUCT
1 2,400 800 350 566.6 1.8 6.0 10.0 10.0 16.0 857 0.05 0.007
2 1,600 800 250 469.7 2.5 8.2 5.0 5.0 13.2 831 0.05 0.007
3 800 700 150 331 2.1 6.9 5.0 5.0 11.9 837 0.08 0.010
AC SUPPLY DUCTS & FITTINGS 0.024
AC FRESH AIR DUCT
6 100 350 350 382.6 1.0 3.3 0.0 3.3 78 0.00 0.000
AC FRESH DUCTS & FITTINGS 0.000
Abbreviations:
E = Elbow Equivalenght Length 15 Ft. AC SUPPLY DUCTS & FITTINGS 0.024
B = Branch Equivalenght Length 30 Ft. VOLUME DAMPER ( x 3 ) 0.375
Br = Branch Run Equivalenght Length 15 Ft. SUPPLY AIR DIFFUSER 0.150
R = Reducer Equivalenght Length 5 Ft. AC FRESH DUCTS & FITTINGS 0.000
FRESH AIR GRILLE 0.150
SECTION CFM
DUCT FITTINGS
SIZE (MM) LENGTH
prepared by/ Engr.Mohamed Mosaad
SUB-TOTAL 0.699
ADD 10% 0.070
TOTAL FRICTION DROP IN WG 0.769