CTY TNHH MTV CN CHUNG TN
Service Department
70,ng ch Khim,P14,Q11,H Ch Minh,Vit Nam
Tel; 0963 132 983
Fax: 38617442
MV Circuit Breaker Maintenance Test Report
Customer: INTEL
Address: SHTP, Dist. 9, Ho Chi Minh city
Substation: ATM-CENTER (HTB)
Object/panel: BB01
Manufacturer:
SCHNEIDER
Serial:
02SE0810021
Specification:
24 Kv -630 A
Type:
Evolis
INSULATION MEGGER TEST :
Test set used: KYORITSU 3121
According to NETA Standard
Phase on test
Testing voltage
(V)
Standard
In Mega ohms
Result
In Mega ohms
Remark
L1 L2+L3+grounding
2500
5000
>100000
OK
L2 L1+L3+grounding
2500
5000
>100000
OK
L3 L2+L1+grounding
2500
5000
>100000
OK
L1 L1 (Opening)
2500
5000
>100000
OK
L2 L2 (Opening)
2500
5000
>100000
OK
L3 L3 (Opening)
2500
5000
>100000
OK
CONTACT RESISTANCE TEST:
Test set used: MOM 690A
According to Manufacturer standard
Phase of test
Testing ampere
(A DC)
Standard
In Micro ohms
Result
In Micro ohms
Remark
L1
100
70
30
OK
L2
100
70
29
OK
L3
100
70
30
OK
MAIN CONTACT TIMING TEST:
Test set used: MPRT 8415
Standard
Result
Standard
Phase of test
Close time
Close time
Open time
(ms)
(ms)
(ms)
According to Manufacturer standard
Result
Remark
Open time
(ms)
L1
74
69.7
46
43.7
OK
L2
74
69.6
46
43.6
OK
L3
74
69.6
46
43.6
OK
NUMBER OF OPERATION : 132
REMARK :
Done By:
DUONG VAN DONG
Date:
Witnessed By:
NGUYEN THUAN HOA
Date:
MV Circuit Breaker Maintenance Test Report
10 DEC 2011