Professional Documents
Culture Documents
BC80 System Catalog A6V10218573 HQ en
BC80 System Catalog A6V10218573 HQ en
Building Technologies
1
Hotels
Government buildings
Commercial buildings
Residential complexes
Retail stores
High-quality Siemens
products reliable and
economical.
Your customers are responsible for the protection of their employees, buildings, and assets.
They also experience cost competition. As a
result, they need fire protection components
that deliver reliable fire detection and alarm
signaling, but which are also cost-efficient. Fire
safety products from Siemens position you perfectly to satisfy your customers requirements.
The BC80 system products range from fire detectors to control panels. They are moderately
priced and of reliable quality.
Siemens technology
high cost-effectiveness
BC80 combines high-quality technology with cost-effectiveness, in
procurement as well as operation.
Moderate hardware costs keep the
investment manageable, while the
flexible, expandable installation protects the long-term view genuine
brand quality at an economical price,
for years to come.
BC80
advantages at a glance:
High quality based on decades
of experience, in-depth research,
and state-of-the-art production
technology from Siemens
A flexible solution
expandable and compatible
with future developments
Cost-effective moderate
investment and easy adaptation
to changing requirements
Easy installation
fast protection
Because the BC80 system units have
been designed for easy installation,
buildings can be protected quickly.
BC80 provides polarity-free wiring;
poles can no longer be accidentally
reversed. Therefore, the networking
of BC80 fire detectors, peripheral
equipment, and BC80 control panels
is rapid and accurate. The use of spur
lines and T-Branches (F-Bus) further
simplifies installation.
Easy configuration
fast commissioning
Commissioning of the BC80 system
is supported by an integrated autoconfiguration function; with it, the
system automatically detects all integrated devices (auto-mapping). This
reduces manual configuration to a
minimum eliminating a potential
source of error. You benefit from a
shorter time to a fully-operational
system.
More complex manual programming
can be conducted via the control
panels or by using Windows-based
software.
Easy maintenance
no interruption of operation
All devices displayed on the controllers are shown with both their
address number and position details.
These help your customers assess
error messages as aids to decisionmaking, and you to keep a clear
overview during installation and
maintenance. Devices with conventional technology, such as collective
fire detectors, can also be wired to
the BC80 system via spur lines.
Tracing faulty fire detectors or peripheral devices during system operation
is swift, targeted, and cost-efficient.
Easy expandability
high flexibility
BC80 grows with your customers
requirements. When buildings or
rooms are extended, the BC80 installation can also be expanded, for
example with new T-Branches in the
cabling and expansion cards in the
control panels.
With an expansion card it is possible
to hook up an additional 127 peripheral devices via the F-Bus, as many as
32 additional control panels via the
A-Bus, and up to three B-Bus devices,
such as extinguishing control panels
or interlocking panels. This increases
options for larger projects.
Easy conversion
fast modernization
Existing systems can be replaced and
modernized with BC80 without large
cabling expenditures. Currently installed cables can be used to network
BC80 devices, since neither the fire
detector lines nor the notification
appliance circuits require a shielded
wire. The system can also be linked
with existing peripheral devices,
which saves time and money. Software updates can be uploaded via
the USB port of the control panels.
BC80
advantages at a glance:
Easy installation and fast building
protection thanks to installation
aids and polarity-free non-shielded
cabling
Fast commissioning thanks to
auto-mapping and Windows-based
software
Minimal maintenance with
address and position of all detectors
and peripheral devices needing
service directly indicated
Smooth expansion via card inserts
for control panels and T-Branches
for cabling
Easy modernization through use
of present cabling, compatibility
with existing peripheral equipment,
and simple software uploads
BC80 detectors
detectors should be
positioned*
at least 0.5 m from the wall
max. 12 m from the previous
detector
BC80 manual call points
manual call points should
be positioned*
in a clearly visible location
1.5 m from floor level
Detector positioning
near elevators*
Address points
Quiescent
current (mA)
BDS031
Heat detector
0.71
0.89
BDS051
0.71
0.89
BDS121
0.43
2.86
BDS132
Input module
0.6
3.8
BDS221
Output module
0.61
2.19
BDS152
Isolate module
0.07
0.5
BDS161
10
16
BDS331
10
90
Source
Name
Address points
Quiescent
current (mA)
BC8001
127
48.5
75.7
BC8001E
254
63.3
113.7
BC8001P
Compact controller
with 1 line, printer
127
51.2
97.0
BC8001PE
Compact controller
with 2 lines, printer
254
66.0
135.6
BC8002-1
500
130.0
224.8
BC8002-2
1,000
170.0
352.6
BC8002-3
1,500
210.0
481.4
Load
BC80 at a glance.
Compact
A-Bus
Compact controller
BC8001
F-Bus
Compact controller
BC8001
Input module
BDS132
Manual
call point
BDS121/e
Output module
BDS221
Manual
call point
BDS121/e
Interlocking panel
BT8011
10
Collective
input module
BDS161
Heat detector
BDS031
Collective
heat detector
HI520
Photoelectric
smoke detector
BDS051
Interlocking panel
BT8012
Standard
Collective
photoelectric smoke
detector OP520
F-Bus
Extinguishing panel
BC8013
B-Bus
Legend
A-Bus
F-Bus
B-Bus
11
Building Technologies
Table of Contents
Order No.
BC8001..
l
l
l
l
l
Operating voltage
Battery capacity
Download/Upload
Dimensions (W x H x D)
Weight (without battery)
Data sheet
BC8001
1
127
240 x 128 Backlit
Yes
1000
1 Dry contact (24 VDC / 3 A)
1 OC output
2 Monitored inputs
(Main Power) 187... 242 VAC
50... 60 Hz
24 VDC 7 Ah
USB
370 x 265 x 120 mm
3.0 kg
A5Q00016399A
A6C50000016
BC8001P
A6C50000018
1-1
Order No.
BC8001E Compact Control Unit with 2 F-Bus lines for up to 254
Devices
A6C50000017
BC8001PE
A6C50000019
BC8002..
BC8002 is an advanced control unit based on latest technology to support easy operation and commissioning.
l
l
l
l
l
l
Mains voltage
Operating voltage
Battery capacity
Quiescent current
Fuse
Operating temperature
Relative humidity
Dimensions (W x H x D)
Weight
Data sheet
BC8002-1
220 VAC 50 Hz
23... 30 VDC
24 VDC 17 Ah
40... 100 W
2.0 A
-10... +50 C
95% (40 2 C)
700 x 520 x 120 mm
22 kg
A5Q00016408A
A6C50000029
1-2
Order No.
BC8002-2 wall-mounted Advanced Control Unit for up to 1000
devices
A6C50000030
A6C50000030
BT80..
BT8011 / BT8012 are interlocking panels. It allows manual and automatic control of external equipment. It is usually installed in the fire
control center together with fire alarm panels in order to control
pumps fans etc.
Operating voltage
Quiescent current
Operating temperature
Storage temperature
Relative humidity
Load for each output
Installation height
Data sheet
BT8011
24... 29 VDC
50 mA
0... +50 C
-20... +60 C
95 % Rh
300 4 K
3U
A5Q00016409A
A6C50000032
l
l
l
l
l
l
l
BT8012
A6C50000033
l
l
l
l
l
l
l
1-3
Order No.
BC8013..
l
l
l
l
Operating voltage
Quiescent current
Operating current
Output current
Maximum current per output
Operating temperature
Data sheet
BC8013
24... 28 VDC
40 mA
200 m A
80 m A
200 m A
-20... +40 C
A5Q00016401A
A6C50000038
BC8013H
A6C50000022
1-4
Order No.
HI520 Collective Heat Detector (Rate of Rise and Fix Temperature)
l
Operating voltage
Output voltage
Operating temperature
Storage temperature
Relative humidity
Quiescent current
Alarm current
EMC
Data sheet
OP520
A6C50000009
16... 32 VDC
5... 13 VDC
-10... +50 C
-30... +75 C
95 % (40 2 C)
100 A
1.5 mA
10 V/m
A5Q00016379A
A6C50000010
l
l
Operating voltage
Output voltage
Operating temperature
Storage temperature
Relative humidity
Quiescent current
Alarm current
EMC
Data sheet
SO520
21... 29 VDC
5... 13 VDC
-10... +50 C
-30... +75 C
95 % (40 2 C)
100 A
1.5 mA
10 V/m
A5Q00016380A
A6C50000011
A5Q00016382A
2-5
Order No.
BDS031 Addressable Heat Detector (Rate of Rise and Fix Temperature)
A6C50000001
Operating voltage
Operating temperature
Storage temperature
Relative humidity
Quiescent current
Alarm current
EMC
Data sheet
BDS051
16... 32 VDC
-10... +50 C
-30... +75 C
95 % (40 2 C)
1.0 mA
3.0 mA
10 V/m
A5Q00016383A
A6C50000002
Operating voltage
Operating temperature
Storage temperature
Relative humidity
Quiescent current
Alarm current
EMC
Data sheet
BDS000
16... 32 VDC
-10... +50 C
-30... +75 C
95 % (40 2 C)
1.0 mA
3.0 mA
10 V/m
A5Q00016384A
A6C50000000
2-6
A5Q00016385A
Order No.
A6C50000003
Connected to F-Bus
Installed in the public area such as staircase elevator lobby etc
Device address can be set via a DIP-switch.
A built-in dry contact can be used to activate another equipment.
Mounted on the wall 1.5 meters above the ground.
Electronic part and housing are delivered separately.
Operating voltage
Operating temperature
Relative humidity
Quiescent current
Alarm current
Capacity of dry contact
EMC
Data sheet
24 VDC
-20... +55 C
95 % (40 2 C)
1 mA
3.0 mA
24 VDC / 0.1 A
10 V/m
A5Q00016386A
2-7
Order No.
A6C50000004
Operating voltage
Operating temperature
Relative humidity
Activation current
Quiescent current
Wiring Capacity
Data sheet
BDS152
24 VDC
-20... +55 C
95 % (40 2 C)
3mA
1 mA
1.0 1.5 mm
A5Q00016394A
A6C50000005
l
l
l
l
l
Operating temperature
Relative humidity
Activation current
Pass through voltage
Wiring Capacity
Data sheet
2-8
-20... +50 C
95 % (40 2 C)
0.5 mA
1 VDC
1.0... 1.5 mm
A5Q00016395A
Order No.
A6C50000006
l
l
l
Alarm voltage
Fault voltage
Normal voltage
Alarm current
Operating temperature
Quiescent current
Relative humidity
Wiring Capacity
Data sheet
BDS221
Operating voltage
Operating temperature
Relative humidity
Activation current
Quiescent current
Relay output
Status LEDs
Wiring Capacity
Data sheet
24 VDC
-10... +50 C
95 % (40 2 C)
3 mA
1 mA
125 VAC / 0.6 A
24 VDC / 2 A
Steady output - Steady ON
Pulse Output - Flashing
1.0... 1.5 mm
A5Q00016398A
2-9
Type
TP8000
Order No.
A6C50000028
TP8000 Printer
A thermal sensitive printer is used to print events.
Data sheet
BCE8001
A5Q00016403A
A6C50000024
l
l
Data sheet
BCC8001
Data sheet
BT8002
A5Q00016402A
A6C50000035
A5Q00016405A
A6C50000034
l
l
l
l
The operation panel consists of the main board BCC8002 the CPU
board BCC8011 LCD and the keypads and LED's as indicators.
Connected with other control units via A-Bus.
Connected with interlocking panels line cards extinguishing panels
via B-Bus.
Download/Upload port on the CPU board.
BT8002 Operation panel features also numerical keys and loud
speaker.
A communication port for connection to a management station is
built-in.
Data sheet
3-10
A5Q00016413A
Type
BCB8001
Order No.
BCB8001 Wall-mounted Power Supply (8A)
Input voltage
Output voltage
Operating temperature
Relative humidity
Protection
Battery
Data sheet
BCC8002
A6C50000039
A6C50000036
A5Q00016407A
3-11
Type
BCM8001
Order No.
BCM8001 Line Card for BC8002 Advanced Control Unit
A6C50000037
Number of loops
Number of addresses
Max. load factor
Wiring Capacity
Max. distance per line
Resistor per line
Capacitor per line
Protection
Connectable field devices
Operating voltage
Quiescent current
Data sheet
3-12
4
127 (on one loop)
150 (for each loop)
RVS1.0... RVS1.5
1000 m
300
300 nF
Short protection
Over voltage protection
BDS Series
Modulated 16... 32 VDC
Full load: 200 mA
No Load: 110 mA
A5Q00016410A
Type Index
Type
BC8001
Description
BC8001 Compact Control Unit with 1 F-Bus line for up to
127 Devices
Order No.
A6C50000016
Page
1-1
BC8001..
BC8001..
1-1
BC8001E
A6C50000017
1-2
A6C50000018
1-1
BC8001PE
BC8002-1
A6C50000019
A6C50000029
1-2
1-2
BC8002-2
1-3
BC8002-3
1-3
BC8002..
BC8013
BC8002..
A6C50000038
1-2
1-4
BC8013..
BC8013H
BC8013..
A6C50000022
1-4
1-4
BCB8001
BCC8001
A6C50000039
A6C50000035
3-11
3-10
BCC8002
BCE8001
A6C50000036
A6C50000024
3-11
3-10
BCM8001
BDS000
A6C50000037
A6C50000000
3-12
2-6
BDS031
2-6
BDS051
BDS031 Addressable Heat Detector (Rate of Rise and Fix Temper- A6C50000001
ature)
BDS051 Addressable Optical Smoke Detector
A6C50000002
2-6
BDS121
BDS132
A6C50000003
A6C50000004
2-7
2-8
BDS152
BDS161
A6C50000005
A6C50000006
2-8
2-9
BDS221
BT80..
A6C50000007
BT80..
2-9
1-3
BT8002
BT8011
A6C50000034
A6C50000032
3-10
1-3
BT8012
HI520
1-3
2-5
OP520
SO520
A6C50000010
A6C50000011
2-5
2-5
TP8000
TP8000 Printer
A6C50000028
3-10
BC8001P
www.siemens.com/buildingtechnologies
12