8. Measure the current flowing thro FT in the Feeder panel A phase CT circuit.
(Approximately it will come 0.5 A).
9. Measure the Current flowing in the Relay is 0 Amps and the relay will not
sense any fault current for trip. This shows the Stability of the Differential
relay.
10. Switch off the primary injection test kit.
11. Now to check the operation of the relay, swap the polarity S1-S2 for any one
the incomer CT circuit or the feeder CT circuit.
12. Inject the current again in the same phase; the relay will operate to trip the
circuit. Measure the current in the Relay (Approximately it will come 1A), it
reads summation of the incomer and feeder secondary current to operate the
relay. This shows the Sensitivity of the Differential relay.
13. Turn off the Injection test kit.
14. Normalize the CT circuit back as per the system.
15. Similarly follow the above same procedure for B phase and C phase and also
for the other Outgoing feeders
PRD BY Lakshmanan
Page 1 of 3
REFERENCE
CIRCUIT
STABLE SYSTEM
87A
Reference
Circuit
Panel
Ref.
CT
Ratio
87B
87C
Injected
Primary
Current
Test Circuit
Panel
Ref.
REFERENCE
CIRCUIT
CT
Ratio
UNSTABLE SYSTEM
87A
PRD BY Lakshmanan
87B
TEST
CIRCUIT
87C
Page 2 of 3
Differential Current
(Secondary)
R-PH
TEST
CIRCUIT
Y-PH
B-PH
Status
Reference
Circuit
Panel
Ref.
CT
Ratio
PRD BY Lakshmanan
Test Circuit
Panel
Ref.
CT
Ratio
Injected
Primary
Current
Page 3 of 3
Differential Current
(Secondary)
R-PH
Y-PH
B-PH
Status