ECS -700 Engineering Configuration Training

Domain and control Configuration

Content

General Introduction
VF builder configuration
I/O Builder configuration
Tag Builder configuration

General Introduction
VisualField
VisualField

Domain config

VFSysbuilder

Down load

VF Config

Control config
VFExplorer

HMI config

HMI

Publish

General introduction
Configuration server

chief engineer station


station
HMI configuration
HMI configuration
Process
Process control
control
configuration

open

save

extended engineer extended engineer


station
station

..

extended engineer
station

guration
HMI confi
configuration
Process control
configuration

General introduction
extended engineer station

extended engineer station

save configuration

configuration server
chief engineer station

extended engineer station

1+2+3
2

General introduction
VF
VF builder
builder
chief engineer station

VFExplorer
VFExplorer
extended engineer station

VFLaunch
VFLaunch
operation station/server

VF builder

Domain configuration
1

Create a project

: Launch VF builder on Chief engineer station (configuration

server)
:: File--New
Set the name of the project and the creator.
The default saving path: D:\SUPCON_PROJECT
: Set as default
To set current project as the default project which will be configured

Domain configuration

Domain configuration
2

Control domain configuration


: Add control domain
Set the name , description and domain address.
:: Add control station
Set the name, description, control station s address
and select the engineer who has the authority to configure it.

Domain configuration
Add control domain

Domain configuration
Add control station

Domain configuration
3

Operation domain configuration

: Add operation domain


Set the name , description.
Set the engineer who can configure it
Set the control domain to be monitored.
:: Add server
Set the name, description and the server
servers address.
Note: when the operation domain is added, a server is already
there. If you add one more then these two server will be redundant.
: Add operation node
Set the name, description and the operation s address.

Domain configuration
Add operation domain

Domain configuration
Add server or operation node

Domain configuration
4

Engineer

: Add engineer group


Set the name and description.
Set the project management authority
Set the authority to configure control station or operation domain.
:: Add engineer
Set the name, password and description.

Domain configuration
Add engineer group

Domain configuration
Add engineer

Domain configuration
5

Common default setting

: Common default settings

:: Engineering unit
You can add some new engineer units here.

:: Security
Select the level of the tags which need to be acknowledged when
operated in HMI.

Domain configuration
6

Backup project

backup project
:: File
File
The default name: project name +date +time

I/O Builder configuration

Control configuration
1

Open from configuration server

select the control station and open it from configuration server,


meanwhile you lock this station and other engineer station can t do the
configuration for this control station.
Means the control station was locked by the local engineer station .
Means the control station was locked by other engineer station.

Control configuration
2

Hardware configuration

controller

I/O link
module

IO
module

rack

IO
channel

Control configuration
select the control station, open hardware configuration
Step 1
1
controller configuration
Step 2
2
Main parameter
redundant
process control network
extended IO network
debug (AO\DO)
fast scanning period2050ms)
local rack scanning period

Control configuration
add IO link module
Step 3
3
virtual IO link module: local cabinet
IO link module : local cabinet
remarkSC0, SC1, SC2, ., SC7
Step 44
add cabinet
remarkSC0-0, SC0-1, SC0-2, SC0-3
Step 55
add IO module
Step 66
set IO channel

Control configuration
Standard signal input module(AI711-S)
module configuration parameter
redundancy Yes\No
scanning period200ms \ 50ms

channel configuration parameter


channel switch open \ close
signal type voltage, current (power distribution\ external power
distribution)
range ( free range )

Control configuration
TC signal input module(AI721-S)
module configuration parameter
redundancy Yes\No
scanning period1000ms \ 300ms
Cold junction compensation: on-site (forbid the modify function)/ on-site (allow
the modify function) /remote

channel configuration parameter


channel switch open \ close
signal type voltage, TC
range ( free range )

Control configuration
RTD signal input module(AI731-S)
module configuration parameter
redundancy Yes\No

channel configuration parameter


channel switchopen \ close
signal typeRTD
Scanning mode: two wired\three wired\four wired
range ( free range )

Control configuration
Analog signal output module(AO711-S)
module configuration parameter
redundancy Yes\No

channel configuration parameter


channel switch open \ close
signal typecurrent
range ( free range )
Fault security: output hold\ output the preset value

Control configuration
Digital signal input module(DI711-S)
module configuration parameter
redundancy Yes\No
signal typepassive contact \ active contact
dithering process: open\ close

channel configuration parameter


filter 4 \ 8 \ 16 \ 32ms
latchopen\ close
dithering parameterN

Control configuration
Digital signal output module(DO711-S)
module configuration parameter
redundancy Yes\No

channel configuration parameter


power distribution type: power distribution\external power distribution
output type: status\pulse width
Fault security: output hold\ output the preset value

Control configuration
scan and upload
upload all the connected hardwareconfirm to delete all the
scanning all
all
current modules
upload the new added hardwareconfirm to
scanning new added
added
re place the current module.

debug status
channel real time data
real time data
data
channel diagnosis data
diagnosis data
data

Control configuration
Add online

Hardware configuration scanning

Scanning channel to generate tag information

Adjust parameter, download configuration online

Tag Builder configuration

Control configuration
3

Tag configuration

select a control station then open the tag table


Step 1
1
scan tags form channel
Step 2
2
generate tag table automatically according to hardware
scan all
all
configuration
generate new tags according to the modification of
scan new added
added
hardware configuration

Control configuration
tag property setting
Step 3
3
tag name \ description
basic properties
properties

channel properties
properties
AI - address \ run cycle \ signal conversion \ range \ alarm\ fault processing
\ supervision setting
AO - address \ run cycle \ signal conversion \ range \ alarm\ supervision setting
DI- address \ signal conversion \ alarm\ fault processing \ supervision setting
DO- address \ signal conversion \ alarm\ supervision setting
set the configuration of some tag as the type template
the new added
type template
template
template
tag will follow its information.

modify in batch

Control configuration
Analog input tag
basic properties :

name \ description \ address \tag run cycle

range properties:

range \ extended range \ over range alarm \unit

alarm properties :

alarm (disable, enable) \ alarm limit \ limit alarm hysteresis

signal conversion process


Linear Sqrt change the real signal to project signal \ extraction of square root
Small signal cut
Change rate alarm

fault processing : hold set range maximumset range minimum

Control configuration
Analog output tag
basic properties :

name \ description \ address \tag run cycle

range properties:

range \ extended range \ over range alarm \unit

alarm properties :

alarm (disable, enable) \ alarm limit

signal conversion process


Direct/reverse output selectiondirect/reverse output

Control configuration
Digital input tag
basic properties : name \ description \ address
alarm properties :ON/OFF status \ positive/negative transition sensing
signal conversion process: input negative: disable/enable
fault processing : hold ON/OFF

Control configuration
Digital output tag
basic properties :

name \ description \ address

alarm properties :ON/OFF status


signal conversion process: output negative: disable/enable

Control configuration
Some other settings
parameter upload \ download
tag debugging
tag usage \ vacant channel\ check tag properties \ check all tags
check
check

Control configuration
4

Compile

Check whether the configuration is correct.

Download

Off line download


Download the configuration of engineer station directly to the control station
totally, without any comparison

Online download
Check the modification of the configuration, then download online.

Thanks