Steve Turner Beckwith Electric Co., Inc.: Testing Numerical Transformer Differential Relays
Steve Turner Beckwith Electric Co., Inc.: Testing Numerical Transformer Differential Relays
Steve Turner
Beckwith Electric Co., Inc.
INTRODUCTION
Commissioning versus Maintenance Testing
Types of Transformer Differential Protection:
Restrained Phase Differential
High Set Phase Differential
Ground Differential
INTRODUCTION
Topics:
Transformer Differential Boundary Test
(Commissioning)
Ground Differential Sensitivity Test
(Commissioning/Maintenance)
Harmonic Restraint for Transformer Inrush
(Maintenance)
Commissioning
Common Practice:
Test all numerical relay settings
verify settings properly entered
Easily facilitated using computer
automate test set & store results
Hundreds of tests are possible
numerical relays have many settings
Commissioning
Final Goal
Ensure the transformer is properly protected
for the particular application
46
RG
E
+
46
RG
ZT
I2
46
3RG
ZT
ZT
I1
Y
Y
87
* Simulate Through Current
Differential Characteristic
Operating Equations
Id = |I1 I2|,
Differential Current
Differential Characteristic
Id
% = Y *100%
X
)
%
(
t
n
e
Perc pe
Slo
Minimum
Pickup
(per unit)
Y
X
Ir
Differential Characteristic
Id
ent
Perc
e
Slop
Minimum
Pickup
ion
g
e
R
Trip
gion
e
R
k
Bloc
Ir
Matrix
[]
Id
Ir
[ ][]
1 -1 *
I1
I2
Inverted Matrix
[]
I1
I2
[ ][]
1
- 1
Id
Ir
Differential Characteristic
Test Current Equations
I1 = 0.5*Id + Ir, Winding 1 Test Current (per unit)
I2 = -0.5*Id + Ir, Winding 2 Test Current (per unit)
Differential Characteristic
Test Points
Minimum Pickup = 0.2 per unit
Id
Slope = 28.6%
ent
Perc
e
Slop
3
Minimum
Pickup
Ir
Differential Characteristic
Test Points (Per Unit)
Id
Ir
I1
I2
0.2
0.3
0.4
0.2
0.2
0.7
0.8
0.6
0.4
1.4
1.6
1.2
0.6
2.0
2.3
1.7
TABLE 1
I1
Y
Y
87
* Simulate Through Current
DAB WINDING
IA1relay = IA1/TAP1
WYE WINDING
IB1relay = IB1/TAP1
IC1relay = IB1/TAP1
TAP# =
MVA#
kV#LL*CTR#*SQRT(3)
Id
Ir
I1
I2
0.2
0.7
0.8
0.6
IA1test = 0.8*TAP1
IA2test = 0.6*TAP2*SQRT(3)
External
IG
I0
-90o
IG
Directional Element
INTERNAL
EXTERNAL
IG2
IOP
CTCF*3I0(2)
W3
delta
345 kV
230 kV
wye
W1
wye
W2
Characteristics
Auto-Transformer
Model
ZHM = 0.01073 per unit
ZHL = 0.04777 per unit
ZML = 0.03123 per unit
ZH =
Z HM Z HL Z ML
2
ZM =
Z HM Z ML Z HL
2
ZL =
Z HL Z ML Z HM
2
TAP2 =
600 MVA
345 kV * 240 * SQRT(3)
600 MVA
230 kV * 400 * SQRT(3)
= 4.18
= 3.77
2
2
2 1/2
4
Ieven = (I + I )
CONCLUSIONS
CONCLUSIONS
Transformer Differential Boundary Test
(Commissioning)
Ground Differential Sensitivity Test
(Commissioning/Maintenance)
Harmonic Restraint for Transformer Inrush
(Maintenance)
QUESTIONS