Standardization of the signals for the disturbance

recorders
The numerical relays now come with 32 Digital Channels in DR.
Sl
No
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

22

23
24
25
26
27

Analog Signal

Digital Signal

R-Phase Current
Y-Phase Current
B-Phase Current
Neutral Current
R-Phase Voltage
Y-Phase Voltage
B-Phase Voltage
Neutral Voltage

R-Phase Main CB Open


Y-Phase Main CB Open
B-Phase Main CB Open
R-Phase Tie CB Open
Y-Phase Tie CB Open
B-Phase Tie CB Open
Z1 Start
Main-I
/II
Carrier
Received
Z2 Start
T2
Z3 Start
T3
Z4 Start
T4
Distance Trip
Stub Enable
SOTF Trip
DEF Start
DEF Trip
DT received Channel
I/II
Bus Bar Protection Trip

Remark

For One and Half Bus


For One and Half Bus
For One and Half Bus

Shall ensure that the


currents of all the feeders
is recorded in case of Bus
Bar Tripping
Line
Reactor To get the disturbance
protection trip
record
for
a
reactor
tripping
Over Voltage Stage-I Shall be helpful to verify
start
the cases of OV tripping.
Over Voltage Stage-I
Trip
Over Voltage Stage-II
Start
Over Voltage Stage-II
Trip
LBB Initiation R-phase Shall be instrumental in
analyzing
bus-bar

maltrippings
28
29
30
31
32

LBB Initiation Y-phase


LBB Initiation B-phase
Main
Bay
LBB
operated
Tie Bay LBB operated
Main-I Trip