Simatic ET 200M IM 153-2 Interface Module: Description Technical Specifications
Simatic ET 200M IM 153-2 Interface Module: Description Technical Specifications
1
Introduction
______________
2
Description
______________
SIMATIC
ET 200M
IM 153-2 Interface Module
Product Information
08/2007
A5E01208335-01
3
Technical specifications
______________
Safety Guidelines
Safety Guidelines
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE
indicates that an unintended result or situation can occur if the corresponding information is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and
operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes
in this documentation qualified persons are defined as persons who are authorized to commission, ground and
label devices, systems and circuits in accordance with established safety practices and standards.
Prescribed Usage
Note the following:
WARNING
This device may only be used for the applications described in the catalog or the technical description and only
in connection with devices or components from other manufacturers which have been approved or
recommended by Siemens. Correct, reliable operation of the product requires proper transport, storage,
positioning and assembly as well as careful operation and maintenance.
Trademarks
All names identified by are registered trademarks of the Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights of the
owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Siemens AG
Automation and Drives
Postfach 48 48
90327 NRNBERG
GERMANY
Ordernumber: A5E01208335-01
08/2007
Table of contents
1
Introduction................................................................................................................................................ 5
1.1
Introduction ....................................................................................................................................5
1.2
Description................................................................................................................................................. 9
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
Technical specifications........................................................................................................................... 17
3.1
3.2
Figures
Figure 2-1
Figure 2-2
Table of contents
Introduction
1.1
Introduction
Scope
This Product Information supplements the ET 200M IM Distributed I/O Device Operating
Instructions (EWA-4NEB7806006-01 07), Edition 02/2006, and describes the new features of
the interface modules:
IM 153-2; order number 6ES7153-2BA02-0XB0
IM 153-2 (outdoor); order number 6ES7153-2BA82-0XB0
The following information applies equally to both interface modules. If differences exist, the
relevant module will be identified explicitly.
Introduction
1.1 Introduction
Additional documentation
You will find the following supplementary documentation online at:
http://support.automation.siemens.com/WW/view/en/ with the corresponding entry ID
Name of manual
Description
Operating Instructions
ET 200M Distributed I/O Device
Entry ID: 1142798
Manual
S7-300 Automation System
Module Data
Entry ID: 8859629
Configuring Manual
ET 200M
Signal Modules for Process Automation
Manual
Automation System S7-300
Fail-Safe Signal Modules
Entry ID: 19026151
Manual
ET 200M Distributed I/O Device
HART Analog Modules
Entry ID: 22063748
Manual
Isochrone Mode
Entry ID: 15218045
Product Information
Reassigning parameters in RUN mode
Entry ID: 14835140
Introduction
1.2 Compatibilities between the versions of IM 153-2
1.2
With regard to properties and features, the IM 153-2BAx2 interface module is fully
compatible with its predecessor versions. In addition, there are individual new features
available. You will find detailed information in the following table.
Functions /
Properties
2BA..
00
01
02
00
RS 485 interface
Fiber-optic interface
12 modules can be operated after the
interface module
SYNC, FREEZE
Module change during operation
Direct data exchange
Direct data exchange with F-modules
Expanded diagnostics
96-byte diagnostic frame
x
x
x
x
x
x
as of
E07
with 1 ms precision
outside of S7-400
For maximum of 32 DI per slot
Redundancy 1
Flying redundancy
2AB..
(FO)
01/81 02/82
2BB..
(FO)
00
01
00
x
x
x
x
x
x
x
x
x
x
x
x
x
x
as of
E06
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
as of
E07
as of
E06
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Clock synchronism 1
Identification and maintenance data (I&M)
x
x
(I&A)
x
x
x
x
x
x
(I&A)
Introduction
1.2 Compatibilities between the versions of IM 153-2
Interface module with order number 6ES7153-
Update via PROFIBUS DP
Update via SIMATIC Micro Memory Card
RC network with 10 M for unearthed
configuration
(1 M)
as of
E03
x2
x
x
x2
x
x
DPV1 mode
as of
E09
as of
E08
IQ-sense
x
(as of
FW
V3.0.1)
x
(as of
FW
V3.0.1)
E = module version
1 SYNC, FREEZE should not be used for these functions.
2 not when operating with the bus module BM IM/IM 6ES7195-7HD00-0XA0
3 supports expanded diagnostics with the 96-byte diagnostic frame in the spare part scenario
Description
2.1
Module count
A maximum of 12 modules can be operated with the IM 153-2BAx2 interface module,
compared to 8 modules previously.
Configuration variants
The following configuration variants are available for the IM 153-2BAx2 with up to
12 modules:
Standard configuration with rail and bus connectors between the modules
Configuration with active bus modules for the "Module change during operation" and/or
"Redundancy" functions
The modules (up to a maximum of 12) are installed and connected according to the
description in the ET 200M Distributed I/O Device ET 200M Operating Instructions.
Configuration
The modules (up to a maximum of 12) are configured as usual:
With STEP 7 V5.4 + SP 3 or later
With a GSD file (SI04801E.GSG)
Restrictions
Use of the high-accuracy time stamp (1 ms accuracy) is only possible with 8 modules. In this
case, a maximum of 8 input modules can be inserted after the IM 153-2BAx2 interface
module in the ET 200M.
2.2
Description
2.3 Support for I/O modules with expanded input data
2.3
6WDQGDUGLQSXWGDWD
DOOE\WHVDUHFRQVLVWHQW
%\WH
%\WH
%\WH
%\WH
6XEVWLWXWHYDOXHVDUHGHWHUPLQHG
IURPWKHPRGXOHW\SH
HJ)))+IRUDQDORJ
VLJQDOPRGXOHV
&RQVLVWHQF\OLPLW
([SDQGHGLQSXWGDWD
DOO[E\WHVDUHFRQVLVWHQW
7KHVXEVWLWXWHYDOXHVDUH
XSWR
PD[
E\WH
The expanded input data are updated in longer time intervals than the "standard" input
data.
2.4
10
Description
2.4 Time stamp of a maximum of 32 digital inputs per slot
Within S7-400, the parameters for the digital inputs whose signals are to be time-stamped
are assigned the same as previously with STEP 7.
Outside S7-400, the parameter assignment is made using data record 240. The parameter
assignment data in data record 240 for assigning the time stamping parameters is structured
as follows:
%\WH
&RQWHQWPHDQLQJ
9HUVLRQ,'
5HVHUYHG
1XPEHURIVORWVWR
UHV
7LPHVWDPSLQJGHDFWLYDWHG
6ORWQXPEHUWR
UHV
')
'DWDIRUPDW')
1XPEHURIGLJLWDOLQSXWV
1XPEHURI',
:LWKRXWYDOXHVWDWXV
:LWKYDOXHVWDWXV
ELWDIWHU6
5HVHUYHG
5HVHUYHG
',
',
',
',
',
',
',
',
',
',
',
&RQWUROE\WHZLWKFRQWUROELWV
',Q 7LPHVWDPSLQJGHDFWLYDWHG
7LPHVWDPSLQJGHDFWLYDWHG
7LPHVWDPSLQJDFWLYDWHG
0HVVDJHLQFRPLQJZLWKHGJH
7LPHVWDPSLQJDFWLYDWHG
PHVVDJHLQFRPLQJZLWKHGJH
&RQWUROE\WHZLWKFRQWUROELWV
',
&RQWUROE\WHZLWKFRQWUROELWV
',
',
',
',
',
',
&RQWUROE\WHZLWKFRQWUROELWV
',
',
&RQWUROE\WHZLWKFRQWUROELWV
6WDUWLQJIURPKHUHQHZVORWQXPEHUVDPHDVDERYHVWDUWLQJZLWKE\WH
UHV
6ORWQXPEHUWR
HWFXSWRODVWVORWQXPEHUDQGWKHDVVRFLDWHGFRQWUROE\WHV
Figure 2-1
11
Description
2.5 Diagnostics with the IM 153-2BAx2
2.5
12
Description
2.5 Diagnostics with the IM 153-2BAx2
%\WH
%\WH
%\WH
6WDWLRQVWDWXVWR
0DVWHU352),%86DGGUHVV
%\WH
%\WH
%\WH
+LJK%\WH
/RZ%\WH
0DQXIDFWXUHU,'
([SDQGHGGLDJQRVWLFV
%\WH
%\WH
,GHQWLILHUUHODWHGGLDJQRVWLFV
'39
%\WH
0RGXOHVWDWXV
%\WH
%\WH
%\WH
%\WH
%\WH
%\WH]
+6WDWXVRQO\ZLWKWKH
6+DQGVWDQGDUG
UHGXQGDQF\
%\WH]
%\WH
&KDQQHOVSHFLILF
GLDJQRVWLFV
E\WHVSHUHUURU
PHVVDJH
0D[
%\WH
,QWHUUXSWVRQO\LQWHUUXSW
SHUVODYHGLDJQRVWLFIUDPH
LVSRVVLEOH
1HZO\DVVLJQHGELWV
Figure 2-2
13
Description
2.6 Parameter assignment/operation of HART field devices by means of PDM
2.6
Starting situation
For the HART field devices, the following starting situation exists:
The HART field devices are connected to HART input/output modules.
The HART input/output modules are distributed among 12 slots of an ET 200M with
IM 153-2BAx2.
Parameter assignment/operation
For the starting situation described above, the following requirements apply to parameter
assignment/operation of HART field devices:
EDD (for ET 200M) Version V1.1.8 or higher
EDD (Electronic Device Description) is required to set up HART field devices. It is
included on the PDM Device Library CD (as of Edition 2, dated 2007) supplied with PDM.
PDM V6.0 SP3
Note
If an older PDM version is used together with the EDD indicated above, an error message
is not issued.
However, then HART field devices on HART input/output modules that plug into slots 12
to 15 cannot be operated.
2.7
14
Description
2.8 Supplement to Chapter 9.3.8 of the operating instructions
2.8
Error type
11111B
2.9
31D
Error text
Meaning
Remedy
15
Description
2.9 Additional details added to Chapter 9.3.10 of the operating instructions
16
Technical specifications
3.1
17
Technical specifications
3.2 Technical specifications of the IM 153-2BAx2
3.2
Technical specifications
IM 153-2BAx2
Manufacturer ID
801EH
SI04801E.GSG
40 x 125 x 117
Weight, approx.
360 g
PROFIBUS DP interface
Baud rates
Up to 12 MBaud
Yes
Interface
RS 485
FREEZE capability
Yes
SYNC capability
Yes
PROFIBUS addresses
1 to 125 permissible
Yes
Yes
Accuracy class
10 ms / 1 ms
Time resolution
466 ps
Message buffer
1s
Time stamping
Time format
Current consumption at 24 V
Max. 0.6 A
Inrush current
3.0 A
Max. 1.5 A
I2t
0.1 A2s
5.5 W
18