Reference: BGR Letter Ref. No. GID-0208-T/00415 dated 19.02.2014
Reference: Letter No. OPGC/BOP/0259/05-04-2014 Date: 05.04.2014 Subject: Comments on SINGLE LINE DIAGRAM FOR 400kV SWITCHYARD RELAY & METERING Comment Resolution Sheet: 1 SL. No.
OPGCL / DCPL Comments
Date: 05.04.2014
BGR Replies / Resolution
Date: 16.04.2014
OPGCL / DCPL Response
Date: 24.04.2014
Document Number: GID-208-EL-ACA-XJ-2203 R3
1.
Please provide separate PS class CT core for 87 HV of
GT in the GT bay and the tie bay.
Noted & incorporated.
Noted
2.
Separate PS class CT core shall be considered for 87HV
GT as per meeting with BHEL on 25.03.2014
Noted & incorporated.
Noted
DEVELOPMENT CONSULTANTS PRIVATE LIMITED