Section 4

Protection functions

1MRS757644 B

4.4.4.10

Technical data
Table 365:

MNSPTOC Technical data

Characteristic

Value

Operation accuracy

Depending on the frequency of the current


measured: fn 2 Hz
1.5% of the set value or 0.002 x In

Start time1)2)
IFault = 2.0 x set Start
value

Minimum

Typical

Maximum

22 ms

24 ms

25 ms

Reset time

< 40 ms

Reset ratio

Typical 0.96

Retardation time

< 35 ms

Operate time accuracy in definite time mode

1.0% of the set value or 20 ms

Operate time accuracy in inverse time mode

5.0% of the theoretical value or 20 ms3)

Suppression of harmonics

DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,

1) Negative-sequence current before = 0.0, fn = 50 Hz, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
3) Start value multiples in range of 1.10 to 5.00

4.5

Voltage protection

4.5.1

Three-phase overvoltage protection PHPTOV

4.5.1.1

Identification
Function description
Three-phase overvoltage protection

4.5.1.2

IEC 61850
identification
PHPTOV

IEC 60617
identification
3U>

ANSI/IEEE C37.2
device number
59

Function block

GUID-871D07D7-B690-48FD-8EA1-73A7169AE8BD V2 EN

Figure 234:

620 series
Technical Manual

Function block

445