Protection functions
1MRS757644 B
4.4.4.10
Technical data
Table 365:
Characteristic
Value
Operation accuracy
Start time1)2)
IFault = 2.0 x set Start
value
Minimum
Typical
Maximum
22 ms
24 ms
25 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Suppression of harmonics
1) Negative-sequence current before = 0.0, fn = 50 Hz, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
3) Start value multiples in range of 1.10 to 5.00
4.5
Voltage protection
4.5.1
4.5.1.1
Identification
Function description
Three-phase overvoltage protection
4.5.1.2
IEC 61850
identification
PHPTOV
IEC 60617
identification
3U>
ANSI/IEEE C37.2
device number
59
Function block
GUID-871D07D7-B690-48FD-8EA1-73A7169AE8BD V2 EN
Figure 234:
620 series
Technical Manual
Function block
445