Professional Documents
Culture Documents
Chart Energy & Chemicals IOM Manual
Chart Energy & Chemicals IOM Manual
TABLE OF CONTENTS
Page
2
3
4
6
7
10
13
15
16
17
18
19
20
21
24
25
26
27
28
FOREWORD
I.
INTRODUCTION
A. Configuration
B. Codes and Materials of Construction
II.
INSTALLATION
A. Arrival Inspection
B. Storage
C. Lifting and Handling
1. Single Exchangers
2. Multiple Exchanger Assemblies
3. Cold Boxes
4. Core-in-Kettle Assemblies
D. Mounting and Bracing
1. Support Angle Mounting System
2. Pedestal Base Mounting System
3. Cold Boxes and Core-in-Kettle Assemblies
E. Pipe Connections
1. Pipe Loads
2. Connection Configurations
a. Slugged
b. Flanged
c. Weld Prepared
3. Transition Joints
F. Venting
G. Insulation
III.
TESTING AND OPERATION
A. Field and/or Shop Proof Testing
B. Fouling and Corrosion Protection
1. Filtering
2. Hydrate Suppression (Methanol Injection)
3. Corrosion Protection
C. Start Up, Operation and Shut Down
IV.
MAINTENANCE
A. Field and/or Shop Leak Testing
1. Pressure Decay Test
2. Air-Soap Test
3. Nitrogen-Trace Gas Test
B. Cleaning
1. Deriming, Back Flushing, and Drying
2. Back Puffing
C. Mothballing
D. Repair and Service
E. Warranty and Liability
FOREWORD
The following instructions are Chart recommendations regarding installation, operation, and maintenance of Chart
brazed aluminum plate-fin heat exchangers, assemblies, and Core-in-Kettle assemblies.
Chart instructions are based on extensive experience, including more than 50 years in the design and manufacture
of heat exchangers for low temperature applications, including air separation and liquefaction, natural gas
processing and liquefaction, helium liquefaction, and hydrogen, ethylene, and other light
hydrocarbon product recoveries.
THROUGHOUT THIS MANUAL, SAFETY ITEMS ARE HIGHLIGHTED IN CAPITAL LETTERS AND LABELED WITH
THE CAUTION MARK SHOWN HERE.
THESE ITEMS SHOULD BE READ WITH CARE AND THOROUGHLY UNDERSTOOD PRIOR TO ANY INSTALLATION,
OPERATION, OR MAINTENANCE OF CHART EQUIPMENT. FAILURE TO PROPERLY FOLLOW INSTRUCTIONS SO
DESIGNATED COULD RESULT IN RUPTURES OR EXPLOSIONS OR OTHER DANGEROUS SITUATIONS WHICH
COULD CAUSE SERIOUS PERSONAL INJURY OR DEATH.
DO NOT MAKE MODIFICATIONS TO THE EQUIPMENT OR DEVIATE FROM THE PROCEDURES RECOMMENDED IN
THIS MANUAL.
THE CONTRACTOR OR OWNER INSTALLING CHART EQUIPMENT SHOULD PAY CLOSE ATTENTION TO THESE
RECOMMENDED PROCEDURES ALONG WITH ANY LIFTING AND HANDLING INSTRUCTIONS PROVIDED WITH
INDIVIDUAL UNITS.
When these recommendations are followed, extended and reliable service from a Chart heat exchanger, Core-inKettle, or assembly can be expected.
Recommended procedures do not, of course, cover all possible variations in equipment design or provide
answers to all specific installation and operating questions which may occur.
If for any reason these recommendations cannot be followed, Chart Energy & Chemicals must be contacted for
further information.
I. INTRODUCTION
I. A. Configuration (See Figure I, inside cover)
Chart brazed aluminum plate-fin heat
exchangers are constructed of aluminum.
The basic construction consists of layers of
corrugated fins which are furnace brazed
between parting sheets. The exchanger
dimension created by this stack of layers
is referred to as the stack height dimension
of the exchanger.
The rectangular plate-fin block created
by this stack of layers is also referred to as
a core and is normally specified by its
outside block dimensions of W (width)
times H (stack height) times L (length).
A heat exchangers size, number of layers,
type of fins, stacking arrangement, and
stream circuiting will vary depending on
the application requirements. The basic
components of a brazed aluminum heat
exchanger are as follows.
I. A. 1. Nozzles
Nozzles are the pipe sections used to
connect the heat exchanger headers to the
customer piping.
I. A. 2. Headers
Headers are the half cylinders which
provide for the distribution of fluid
from the nozzles to or from the ports of
each appropriate layer within the heat
exchanger.
I. A. 4. Distributor Fins
Distributor fins distribute the fluid between
the port and the heat transfer fins. The
distributor fin used adjacent to a port is
called a port fin. The distributor fin used
between a port fin and a heat transfer fin is
called a turning fin. The typical distributor
fin thickness is .016 inch.
I. A. 5. Heat Transfer Fins
Heat transfer fins provide an extended
heat transfer surface. All fins, both
heat transfer and distributor, provide a
connecting structure between the parting
sheets, thereby creating the essential
structural and pressure holding integrity of
the heat exchanger. Typical heat transfer
fin thicknesses are .007, .008, .010, and
.016 inch.
I. A. 6. Parting Sheets
Parting sheets (sometimes referred to as
separator sheets) contain the fluids within
individual layers in the exchanger and also
serve as primary heat transfer surface.
Typical parting sheet thicknesses are .040,
.080, and .125 inch.
I. A. 7. Outside sheets
Outside sheets (sometimes referred to as
cap sheets) serve as the outside parting
sheets. They are typically .25 inch thick
and serve as the outer protective surface
of the exchanger as well as a land for weld
attachment of the headers.
I. A. 3. Ports
Ports are the openings in either the side
bar or the end bar, located under the
headers, through which the fluids enter
or leave individual layers.
C.
COMPONENT - TYPICAL MATERIALS
(Aluminum Alloy)
Outside Sheets
Parting Sheets
Side and End Bars
Heat Transfer Fins
Distributor Fins
Headers & Nozzles
Flanges
Support Angles
Lifting Lugs
3003
3003
3003
3003
3003
5083*
6061-T6*
6061-T6*
5083*
II. B. 4.
The storage area should be located where
the heat exchanger is not subjected to
vibration.
II. B. 5.
Avoid a location where other work activity
or falling objects will be in the vicinity of the
stored heat exchanger. External denting of
the heat exchanger can damage the internal
matrix of the heat exchanger and cause leakage.
II. B. 6.
Avoid a location which is subject to large
fluctuations in temperature (especially
below 32F), or high humidities when
the exchanger is not sealed and weather proofed, as this can cause condensed water
to accumulate in the exchanger and freeze
when the exchanger is placed in storage or
operation. Water freezing inside the heat
exchanger can damage its internal matrix.
II. B. 7.
Heat exchangers must be properly
covered and sealed in such a manner that dirt,
sand, water, or foreign materials cannot
enter open nozzles, ports, or through any
other access into the heat exchanger.
For heat exchangers that are shipped pressurized,
dry air or nitrogen with a dew
point of 32F or less should be sealed in
each stream during storage. The dry air
or nitrogen pressure should be 15 psig
or one third the stream design pressure
whichever is less. Periodically, the heat
exchanger should be checked to ensure
that the pressure is maintained.
For heat exchangers which are not shipped
with pressure and do not have welded
shipping covers on the nozzles, all nozzle
openings on the heat exchanger should
be covered and sealed while the unit is in
a dry condition.
II. B. 8.
Cold boxes are constructed to be both
air and water tight. Prior to storage, all
closed openings should be inspected for
sealing. Precautions should be taken to
avoid water, dirt, sand, etc., from entering
the cold box during storage. Cold boxes
should be stored in the horizontal position
with the weight concentrated at the cold box
structural frame members in accordance with
the Chart drawing. If the cold box is to
FIGURE IV
TYPICAL METHOD FOR ROLLING HEAT EXCHANGER FROM
SHIPPING ATTITUDE TO ALTERNATE SIDES.
(UNCRATED EXCHANGERS)
10
11
12
13
II. D. 1. e.
Bolts employed to secure the exchanger
to the supporting surface must be finger
tight only. (Note: This requirement applies
to all mounting systems, angle type
and pedestal base type.) Do not use lock
washers. Use a double nut or interrupt
the bolt threads to prevent the nut from
working loose. Wrench tightening the
bolts could allow relatively small horizontal
pipe loads applied to either end of the
exchanger to develop bending moments
on the exchanger which may produce
unacceptable stress concentrations at the
support angles.
II. D. 1. f.
To avoid excessive bending moments on
the support angle itself, the supporting
surface must not extend beyond 1.0 inch
of the exchanger side bar face. A distance
of 0.5 inch is recommended.
II. D. 1. g.
The support system should be safeguarded
by the provision of a sway brace, located
at the opposite end of the exchanger
away from the main support angles or
pedestal base, whenever the total external
loads (pipe, wind and earthquake) are
sufficient to cause lateral movement of
the exchanger.
A close fit between the exchanger scuff
plate and the sway brace is required
since ambient to operating cryogenic
temperatures at this position can produce
.12 inch clearance from thermal contraction.
Scuff plates can be furnished on the
exchanger by Chart.
Do not fasten any sway brace directly to
the exchanger! The exchanger must be
free to move in the vertical direction.
II. D. 1. h.
For reversing (air separation service)
exchangers, supporting directly from
the bottom (warm end) manifolds is
acceptable if provided for on the Chart
assembly drawing. Warm end manifolds
for reversing exchangers should always
be provided with sumps and drains of
adequate size to return any condensed
water from the manifold piping so that
water will not be entrained in the fl uid
stream or slugged into the exchanger
during pressure reversals.
14
Slugged End
Location for
field cut off
Blind Flange
15
OVERPRESSURIZATION OF A HEAT
EXCHANGER OR ASSEMBLY WITH
SLUGGED ENDS NOT DESIGNED FOR
PRESSURE TEST PURPOSES COULD RESULT
IN A RUPTURE OF THE SLUGGED
ENDS AND CAUSE SERIOUS PERSONAL
INJURY OR DEATH.
Prior to removing the plug or pressure
gauge from the shipping valve, be sure the
valve is in the closed position. Exercise
caution and accepted safety procedures for
removal of a plug from a pressure vessel.
16
FIGURE X
TYPICAL TRANSITION JOINTS
FOR PIPING CONNECTIONS
ALUMINUM
STAINLESS
STEEL
CHART
Bolting recommendations:
Down to -50F
Below 50F
Stud Diameters thru 1.5
Studs
SA193 B7
SA320 B8 CL2
Nuts
A194 GR 2H
Below 50F
Stud Diameters above 1.5
STAINLESS
STEEL
SA320 B8M2
SA194 GR 8
SA194 GR 8
(in)
5/8
7/8
1
1-1/8
1-1/4
1-3/8
1-1/2
1-5/8
1-3/4
1-7/8
2
2-1/4
2-1/2
2-3/4
3
TPI
Torque
(ft lbs)
13
11
10
9
8
8
8
8
8
8
8
8
8
8
8
8
8
25
50
92
142
217
313
438
596
771
1000
1250
1552
1883
2717
3750
5021
6563
Torque
Increments
ALUMINUM
DO NOT REMOVE
WELD
Y & CHE
17
.
Place a chill block or damp rags on the
aluminum/steel overlapping bond area.
If damp rags are used, care should be
taken to keep the rags or cloths damp. A
dry cloth will allow the joint to become
excessively hot. Temperature in the
aluminum/steel overlapping area must
be held to a maximum of 300F (149C),
unless higher temperatures are permitted
by the joint manufacturer.
When installing a loose transition joint,
weld the stainless steel end first whenever
possible. This will provide a larger
sink for the heat generated by the aluminum
welding.
Use weld techniques and sequences to
minimize the heat input.
Care should be taken to avoid non-uniform
heating, weld sequences or weld techniques
which would cause isolated high stress areas,
i.e. "Block Welding,"local repair welds, or other
similar types of localized welding.
When installing or working with flange
reinforced transition joints:
Do not loosen the nuts or bolts.
Do not attempt to pry the flanges
apart.
No internal gasket is used with this part.
Servicing is not required.
Loads on transition joints are to be maintained
within allowable limits See II. E.
1.
II. F. Venting
External venting of inactive or non
operational internal zones of some
exchangers is required when specified
on the Chart drawing. Examples of
inactive zones that require venting are:
1) the modular space formed by welding
together two exchanger blocks; 2) the
dead corner of a reversing stream warm
end distributor employing the slant bar
drainability feature; 3) the space formed
between two tandem streams having
adjacent side headers at mid exchanger;
or 4) other special cases.
18
19
20
21
MICALS, INC.
22
CHART
23
IV. MAINTENANCE
Beyond the precautions for installation and
operation already recommended in these
instructions, no periodic maintenance is
required for these exchangers. It is recommended
that a maintenance log be kept to
record normal operating procedures, any
plant upsets, shut downs, and any operating
conditions available.
24
P1 T2
P2 = --------T1
Where
P=
T=
1=
2=
Absolute Pressure
Temperature (R or K)
Initial Reading
Final Reading
25
CHA
26
27
RT ENERGY & C
PRESSURIZATION OF AN IMPROPERLY
REPAIRED EXCHANGER COULD RESULT
IN A RUPTURE OF THE HEAT EXCHANGER
AND CAUSE SERIOUS PERSONAL INJURY
OR DEATH.
IV. E. Warranty and Liability
Chart will warrant to the Buyer for a
period of twelve (12) months from
date of equipment start-up, but not to
exceed eighteen (18) months from date
of shipment, whichever occurs first, that
the equipment provided: (1) is free from
defects in material and workmanship; (2) is
new and in accordance with Chart brazed
aluminum heat exchanger specification
and drawings; and (3) has the performance
(i.e., capacities and ratings) set forth in
Chart brazed aluminum heat exchanger
specification and drawings. Chart brazed
aluminum heat exchanger specification
and drawings which govern this entire
warranty are those which are submitted
specifically for this equipment by Chart
and approved as final by the Buyer. The
express warranties defined above do not
apply to defects or performance problems
resulting from corrosion, erosion, and/or
deterioration.
Chart does not warrant equipment performance
and/or mechanical design: (1)
if the equipment is operated at process
conditions, including, but not limited to,
flowrates, temperatures, pressures, fluid
compositions, mean temperature differences,
and turndown conditions which
are more severe than those specified on
Chart brazed aluminum heat exchanger
specification and drawings; (2) if the equipment
is not operated within the conditions
specified on the equipment nameplate (for
pressure testing, when not specified on the
equipment nameplate, the governing pressure
vessel code shown on the nameplate
shall apply to pressure testing limits); (3)
for damage due to improper installation,
operation, or maintenance; or (4) for damage
resulting from external forces applied
to the equipment from the connecting
piping or support system which exceed
those conditions specified in Chart brazed
aluminum heat exchanger specification
28
FIGURE XII
TYPICAL CHART BRAZED ALUMINUM HEAT EXCHANGER NAMEPLATE
FIGURE XIII
TYPICAL CHART
BRAZED ALUMINUM
HEAT EXCHANGER
ASSEMBLY DRAWING
NOTE: A copy of a Chart
assembly drawing can be
obtained by contacting Chart
with the serial number of the
exchanger.
TV CERT
Certificate Registration
No. 12 100 4343