Written dimensions on these drawings shall have precedence over scaled dimensions.

Contractor shall verify and be responsible for all dimensions and conditions on the job. OB+Architecture Inc. must be notified immediately in writing of any variation from the dimensions and conditions shown on these drawings. Field verify all conditions prior to laying out or fabricating associated work. Bring to the architect's attention any deviation from designed conditions and field conditions prior to ordering
materials and installing work, and cooperate with architect to modify such conditions at no additional cost to the owner, architect or architect's consultants. Shop details must be submitted to the architect's office and reviewed by the architect prior to ordering materials, fabrication and delivery to the job site, unless otherwise provided for under the specific contractual agreement between the architect and client. OB+Architecture Inc. expressly reserves its common law copyright and other
property rights in these documents. These documents are not to be reproduced, changed, or copied in any form or manner whatsoever, nor are they to be assigned to a third party without first obtaining the written permission and written consent of OB+Architecture Inc. In the event of unauthorized use of these documents by a third party, the third party shall hold OB+Architecture Inc. harmless and agrees to remunerate OB+Architecture Inc.
for such use in an amount equal to the original fee for the original documents, plus legal fees, court costs, collection fees and other costs.

AIR CONDITIONING UNIT SCHEDULE


DX. COOLING COIL DATA ELECTRIC HEATING COIL

FAN DATA

AC #

OUTSIDE
AIR

AREA
SERVED

CFM

MIN
EXT.
E.S.P.

MBH
TOT

HP

MBH
SENS

KW

ELECTRICAL

STAGES

TOTAL
MCA

MOCP

VOLTS

PHASE

AC - 1

LOBBY
EXAM
RECEPTION

180

2000

60

37.5

45

208

AC - 2

TREATMENT

200

2400

72

13.5

54.8

60

208

AC - 3

KENNEL

200

1000

0.5

30

7.5

69

70

208

AC - 4

DOG WARD

295

9.7

12

15

120

AC - 5

CAT WARD

295

9.7

12

15

120

NOTES:

EER

SEER MANUFACTURER/MODEL

13

WEIGHT

SEE NOTE #

TRANE TSC060

1, 3 - 9

TRANE TSC072

1, 4, 6 - 12

13

TRANE 4TCC3030

1, 3 - 9

14.3

FRIEDRICH MO9YF

2, 7, 8

14.3

FRIEDRICH MO9YF

2, 7, 8

11.3

ROOF CAP

CANT STRIP BY
GENERAL
CONTRACTOR

PREFAB 18 GA
GALV. STL. STRUCT.
ROOF CURB.

ROOFING BY
GENERAL
CONTRACTOR

WOOD NAILER
INSULATION

1.
2.

PACKAGED SLAB-MOUNTED A/C UNIT WITH HORIZONTAL DUCT CONNECTIONS


DUCTLESS SPLIT SYSTEM HEAT PUMP WITH 9.7 MBH HTG, 8.2 HSPF, WASHABLE FILTERS, WIRELESS REMOTE, AND R410A. OUTDOOR AIR
DUCTED FROM AC-2.
3. STANDARD MOTOR AND DRIVE
4. MOTORIZED OUTDOOR AIR DAMPER
5. 1" 30% EFFICIENT PLEATED FILTERS WITH ACTIVATED CARBON EQUAL TO DAYTON RELIABLE
6. FOIL FACED INSULATION
7. SINGLE POINT WIRING KIT
8. NEC DISC. BY ELECTRICAL TRADE
9. 7 DAY, TIME OF DAY PROGRAMMABLE THERMOSTAT WITH OVER-RIDE
10. OVERSIZED MOTOR AND DRIVE
11. 2" 30% EFFICIENT PLEATED FILTERS WITH ACTIVATED CARBON EQUAL TO DAYTON RELIABLE
12. PROVIDE UNIT-MOUNTED SA DUCT SMOKE DETECTOR WITH RELAY

PT WOOD BLOCK
2" x 2" x 1/4"
SUPPORT ANGLECOORDINATE
LOCATIONS AND
OPENING SIZES
WITH STRUCTURE
INSTALLATION COMPLIES WITH
120 MPH WIND LOAD PER FBC

NOTES:

1. COORDINATE ROOF
PENETRATIONS AND
WATER PROOFING
WITH GENERAL
CONTRACTOR.

VENTILATOR SCHEDULE

ROOF CURB DETAIL

SCALE: NO SCALE

ADVANCE REVIEW

issued:

A/C UNIT ANCHORAGE

21 JULY 2008

revised:

SCALE: NO SCALE

ROOF / METAL DECK

ROOF CAP
WOOD

3
8"

WASHER

STRAP TO STRUCT.

3
8"

x 5" LAG BOLT THRU


UNIT RAIL INTO WOOD
ON CURB @ 6" ON
CENTER

NUT, BOLT, WASHER

2" WIDE STRAP


(GALV. STEEL)

CURB

ROOF

NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.

ROOF CURB
BIRD SCREEN
ALL-ALUMINUM WALL PROP. FAN WITH OSHA INLET GUARD AND 120 VAC MOTOR-OPERATED SHUTTER
STARTER AND DISCONNECT BY ELECTRICAL TRADE
CEILING EXHAUST FAN W / ALUMINUM CEILING GRILLE, BACKDRAFT DAMPER & SPEED CONTROLLER
INTERLOCK WITH LIGHT SWITCH
CONTROL WITH ON/OFF SWITCH
INTERLOCK BOTH OUTDOOR AIR MOTOR-OPERATED DAMPERS, EF-1, EF-2, AND WALL SWITCH
GRAVITY EXHAUST VENTILATOR

ROOF CAP - CURB TIE DOWN DETAIL


SCALE: NO SCALE

50% FACTOR FOR


EVENTS LESS THAN 3 HR

TOTAL OA REQD

SCALE: NO SCALE

AHU & A/C

OUTDOOR AIR (OA) CALCULATIONS


RECEPTION /
WAITING @ 20 CFM

DUCT HANGER DETAIL


CLEANOUT

SEAL SPIN-IN FITTING


WITH MASTIC.

VETERINARY
STAFF
@ 20 CFM

ROUND
(UNINSULATED)

GALV. STEEL

4" (A/C UNITS)


3" (AHUs)

SPIN-IN FITTING WITH


VOLUME DAMPER (WHERE
SHOWN ON PLAN)

TOTAL OA SPEC

MIN. 1.5" WIDE


GALV. STRAP

AC - 1

CENTRAL
FLORIDA

CLEANOUT

ANIMAL
HOSPITAL
1201 ALAFAYA TRAIL

address:

NECK MOUNTED VOLUME


DAMPER (WHERE SHOWN
ON PLANS)

AC - 2

OVIEDO, FLORIDA

AC - 3

32765
CEILING
RIGID DUCT
(LOW
PRESSURE)

project
number:

SEE PLAN FOR


ROUTING

DIFFUSER

2007-12

DIFFUSER, REGISTER, GRILLE SCHEDULE


FACE SIZE

NECK SIZE

TITUS MODEL NO. SEE NOTE NO.

DIFFUSER DETAIL

SCALE: NO SCALE

CONDENSATE DRAIN DETAIL


SCALE: NO SCALE

MECHANICAL ENGINEER
A. PETER TANKEL, P.E.
702 DENTON ROAD
WINTER PARK, FL 32792
PE 41231

ROOF/METAL DECK

2" WIDE GALV. STEEL


STRAP TO
STRUCTURE
GALV. STEEL DUCT

BAR JOIST (TYP)


#10 SELF TAPPING SHEET
METAL SCREWS
THROUGH DUCT WALL

MIN. #12 GALV. STEEL


WIRE

title:

HVAC DETAILS,
CALCULATIONS &
SCHEDULES

R-6 (INSULATED)
2" THICK 1# DENSITY
F.G. DUCT WRAP
WITH GLASS FAB
AND MASTIC JOINTS

NOTES:
1.
2.
3.
4.
5.
6.
7.

COORDINATE FRAME TYPE WITH ARCHITECT SPECIFIED CEILING / WALL TYPE.


STEEL CONSTRUCTION, OFF WHITE FINISH.
PROVIDE MANUAL VOLUME DAMPER ACCESSIBLE THROUGH NECK.
ALUMINUM CONSTRUCTION, OFF WHITE FINISH.
RETURN AIR FILTER GRILLE WITH 1" T/A FIBERGLASS MEDIA.
SQUARE TO ROUND INSULATED ADAPTOR.
SIGHT-PROOF DOOR GRILLE.

2" WIDE GALV.


CHANNEL
1.5" DUCTBOARD
R-6.0 (GLASS FAB/
MASTIC)

drawn:

reviewed:

date:

TRAPEZE DETAIL
SCALE: NO SCALE

TRAPEZE DETAIL

lman:

SCALE: NO SCALE
sheet setup:

JLP
OB / RG
21 JULY 2008

PS-M3.1
MOJA-HVAC

sheet
number:

M3.1