Professional Documents
Culture Documents
System Design Summary For Electric Heat Tracing For 'Pipe Line'
System Design Summary For Electric Heat Tracing For 'Pipe Line'
SR NO.
LINE NO.
PIPE SIZE
(NB)
PIPE SIZE
(OD)
PIPE LENGTH
(MTR)
ROCKWOOL
INSULATION
THICKNESS
(MM)
NO OF VALVES
(NOS.)
NO OF
FLANGE
(NOS.)
1
2
3
4
5
A
B
D
E
F
20
80
100
150
200
0.75
3
4
6
8
18.0
6.0
42.0
576.0
96.0
100
100
100
100
100
24
0
20
66
2
0
12
60
152
13
738.0
RRL/HT/14-15/DE-005
24-Apr-12
R0
OFFER REFERENCE
DATE
REVISION
MAINTENANCE
TEMP ( OC)
HEAT LOSS
(W/M)
TRACER
OUTPUT (W/M)
TRACER
MODEL
TRACER PER
UNIT
LENGTH OF
PIPE
TRACER PER
NO OF
VALVE
TRACER PER
NO
OF FLANGE
40
NO OF
SUPPORTS
(NOS.)
6
2
14
96
16
140
140
140
140
140
6.91
9.17
9.83
10.93
11.86
49.00
49.00
49.00
49.00
49.00
20VPL2-CT
20VPL2-CT
20VPL2-CT
20VPL2-CT
20VPL2-CT
1.0
1.0
1.0
1.0
1.0
0.21
0.28
0.30
0.33
0.36
0.04
0.06
0.06
0.07
0.07
R0
HB
KP
REVISION
PREPARED BY.
CHECKED BY.
TRACER PER
NO OF
SUPPORT
TOTAL TRACER
LENGTH (MTR)
OPERATING
CURRENT
(A)
1.3
6.3
7.3
8.3
9.3
30.9
19.3
153.8
1405.0
246.5
7.0
4.4
34.9
318.7
55.9
1855.5
NC
APPROVED BY.