SITE INSPECTION AND TEST RECORD

Description:

Contract no.:

REVENUE METER (MAXYS 2510)


Customer:

30531166/00
End Client:

ROYAL COMMISSION

Sheet:

SEC-EOA

Site:

1 of 3

Panel / Designation / Location no.:

Project no.:

Rahima 115/13.8kV New Substation

1. GENERAL DATA AND INFORMATION


DESIGNATION No.
MANUFACTURER
TYPE OF METER
CT RATIO
CT SCALE FACTOR
TRANSFORMER RATIO

: EM1
: Landis&Gyr
: MaxSys 2510
:
:
:

PANEL REF.
BAY No.
SERIAL No.
PT RATIO
PT SCALE FACTOR

:
:
:
:
:

2. GENERAL CHECKS & VISUAL INSPECTION


ITEM
1
2
3

DESCRIPTION
INSPECTION FOR PHYSICAL DAMAGES
VERIFY CONNECTION AS PER DRAWING
CHECK TIGHTNESS OF ALL CONNECTIONS

CHECKED

REMARKS

3. ELECTRICAL TESTS
A. CREEP TEST
APPLIED VOLTAGE
115V
115V

APPLIED CURRENT
0.0 A
0.003 A

Note: Minimum Operating Current = 0.0025 A

B. ACCURACY TEST:
Tested by:
Name

Witnessed by:
Name

Signature & Date:

Signature & Date

REMARKS

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

REVENUE METER (MAXYS 2510)


Customer:

30531166/00
End Client:

ROYAL COMMISSION

Sheet:

SEC-EOA

Site:

2 of 3

Panel / Designation / Location no.:

Project no.:

Rahima 115/13.8kV New Substation

a. FULL LOAD
INJECTED
CURRENT
(A)

INJECTED
VOLTAGE
(V)

115

115

30

115

60

115

90

115

120

115

150

115

180

115

210

115

240

115

270

115

300

115

330

ANGLE

MWATT HOUR
%ERROR
(Standard Meter)

MVAR HOUR
%ERROR
(Standard Meter)

MWATT HOUR
%ERROR
(Standard Meter)

MVAR HOUR
%ERROR
(Standard Meter)

b. LIGHT LOAD
INJECTED
CURRENT
(A)

INJECTED
VOLTAGE
(V)

0.5

115

0.5

115

90

0.5

115

180

0.5

115

270

ANGLE

Note: Maximum expected error = 0.2%

C. DISPLAY TEST
a. Full Load
INJECTED

INJECTED

ANGLE

Time

KWH

Tested by:
Name

Witnessed by:
Name

Signature & Date:

Signature & Date

KVARH

SITE INSPECTION AND TEST RECORD


Description:

Contract no.:

REVENUE METER (MAXYS 2510)

30531166/00

Customer:

End Client:

ROYAL COMMISSION

Sheet:

SEC-EOA

Site:

3 of 3

Panel / Designation / Location no.:

Project no.:

Rahima 115/13.8kV New Substation


CURRENT
(A)

VOLTAGE
(V)

115

115

60

5
5

115

90

115

120

115

330

ANGLE

Time
(Sec)

(Sec)

CALC.

MEAS.

CALC.

MEAS.

b. Light Load
INJECTED
CURRENT
(A)

INJECTED
VOLTAGE
(V)

0.5

115

0.5

115

180

5
5

0.5

115

90

0.5

115

270

KWH
CALC.

KVARH

MEAS.

CALC.

MEAS.

D. MAXIMUM DEMAN READING CHECK


Maximum demand time = 15 min
Calculated MAX. Demand

Measured MAX. Demand

Tested by:
Name

Witnessed by:
Name

Signature & Date:

Signature & Date