You are on page 1of 2

SERVICE.

CO

Safe Ring Switchgear Test

CUSTOMER

ASTOON HOSPITAL

SWGR NAME

PROJECT

Installing new RMU 13.8 KV

SWGR NO.

PLANET NO.

Main Substation

CUBICLE TYPE

SAFE RMU

SAFE RING

A. MECHANICAL CHECK AND VISUAL INSPECTION:

Item
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

Description

Checked

Inspect for physical damage / defects.


Check nameplate information for correctness.
Check the alignment and smoothness of operation.
Check quality of paint work.
Check proper operation of all mechanical interlocks.
Check for correct breaker position indications.
Check for correct spring status indication.
Check for proper alignment of the breaker primary and secondary
contacts.
Check SF6 gas with normal pressure
Check that all grounding is securely connected.

B. INSULATION TEST: (5kV)


PHASE

TEST VALUE ()

RED - GND
YELLOW - GND
BLUE - GND
RED YELLOW
RED BLUE
YELLOW BLUE

1.054 T
1.173 T
1.183 T
7.09 T
6.07 T
8.44 T

C .BUSBAR CONTACT RESISTANCE @ (100A) DC

ABB
NAME

SIGN

DATE

Engr. Yazen Saleh

23/01/2015

ASTOON HOSPITAL
NAME

SIGN

DATE

:
Page 1 of 2

OK
OK
OK
OK
OK
OK
OK
OK
OK
OK

13.8kV

SERVICE.CO

Safe Ring Switchgear Test

CUSTOMER

ASTOON HOSPITAL

SWGR NAME

PROJECT

Installing new RMU 13.8 KV

SWGR NO.

PLANET NO.

Main Substation

CUBICLE TYPE

MEASURED RESISTANCE()
480
300
370

PHASE
R
Y
B

F. REMARKS

SIGN

DATE

SAFE RING

REMARKS
OK
OK
OK

HI POT TEST FOR THIS TYPE OF SAFE RING UNIT IS N/A (AS PER ABB FACTORY )
INFORMATION).

ABB
NAME

SAFE RMU

Engr. Yazen Saleh

23/01/2015

ASTOON HOSPITAL
NAME

SIGN

DATE

:
Page 2 of 2

13.8kV