Professional Documents
Culture Documents
GeneratorRotor 2
GeneratorRotor 2
C
B
A
Figure 2 Shaft vibration changes proportional to the MVAR
variation.
The SB-C22 generator was tested at 130 MW while the
MVAR was varied from -30 to 65 MVAR. The results
revealed serious condition of thermal sensitivity shown in
figure 2. The reactive power is -30 MVAR at point A then it
was increased to 65 MVAR at point B. The vibration
reached to point C in 40 minutes while the reactive power
was fixed. Afterward, the vibration was decreased
immediately while the reactive power was reduced. The
results on the generator SB-C22 had been concerned as a
critical reversible thermal sensitivity problem. Therefore the
unit was shutdown to perform the repair work.
May 2004
Nov 2003
75
50
75
Exs
Exs
50
Tus
Tus
25
25
0
-75
-50
-25
0
0
25
50
75 -75
-50
-25
-25
-25
-50
-50
-75
Unit: mp-p
25
50
75
-75
0.4
0.35
Casing vibration (in/s
0.3
0.25
0.2
0.15
0.1
0.05
0
700
750
800
850
900
950
1000
Field current(A)
BB1
BB2
BB4
BB5
BB7
BB8
BB9
CONCLUSION
The thermal sensitivity problem due to vent holes blockage
which is taken place on the two generators shows that the risk
of thermal sensitive rotor can be governed under appropriate
monitoring and testing. This thermal sensitivity contributes to
the reversible vibration, nevertheless, the generator is still able
to operate if the vibration does not exceed the limit. Otherwise,
the problem is needed to mitigate.
REFFERENCES
[1] Ronald J. Zawoysky, Wiliam M. Genovese, Generator
Rotor Thermal Sensitivity-Theory and Experience,
GE Power Systems, New York, April, 2001
[2] GEPS Energy Services, Investigation of Thermal
Sensitivity, Product/Technical Support-Asia, June, 2003