Design Flexibility : Mini Feeder Pillar

Designed & Manufactured based on Customers Requirements


(1) Phase and Neutral Busbar
(2) Earth Busbar
(3) Incoming Termination Link
(4) Support Insulator
(5) Steel Cable Clamp
(6) Disconnecting Link
(7) 100 Amps Din Type Fuse Base
(8) Outgoing Termination Link

Low Voltage
Feeder Pillar

Mini Feeder Pillar Features


Rated Current

: 400A - 2 Nos. (Incoming)


: 160A - 6 Nos. (Outgoing)

Rated Operational Voltage

: 440 Volts

Rated Insulation Voltage

: 1000 Volts
Outdoor & Indoor Design

Rated Short Circuit withstand : 6kA/1 sec


strength with fuse link
Cable Termination

: 300 sq. mm (Incoming)


: 70 sq. mm (Outgoing)

Fuse Base

: 160A (suitable for DIN Fuses)

Enclosure

: Suitable for outdoor

Degree of Protection
for Enclosure

: IP54

Overall Size (L H W)

: 650mm 1245mm 340mm

Application Standards

Fuse Base

Fuse

:
- VDE 0636 Pt 1 & 21
- NH Fuse 100A

LV Switchgear &
Control Gear assembly

- IEC 60439-1

Degree if protection

- IEC 60529

| Compact & Robust |


| Safe & Reliable Operation |
| Vandalism Protection |
| Customised Solutions |

Type-Test Certification

Current Transformers
One set of 3 nos busbar mounted rectangular/ring type current
transformers are mounted on phase busbar beside incoming
link for metering indication.

Responding To Your Needs


Current
Transformer

Technical Data

The low voltage feeder pillar comprises of the following components :

Feeder Pillar Enclosure

Busbars

Current Transformer

Instrument Panel

Incoming Units

Outgoing Units

Instrument Panel
Instrument panel complete with
Fully insulated thermal type ammeter for maximum demand indication

Cartridge type fuses to facilitate the connection of auxiliary loads


Cartridge type fuses


Ammeter with maximum


demand indication

Enclosure
The metal enclosure is made of sheet steel of minimum 2mm thickness, mounted on a steel base
frame of minimum 3mm thickness. Enclosure is suitable for outdoor application. The enclosure is
fitted with 2 hinges lockable doors, with padlocking facilities and arranged to open through >120
degrees for maximum access. Watershed roof is provided to prevent the accumulation of water.
Ample ventilation is provided to permit natural circulation of air. The ventilation apertures are
screened to prevent the entry to vermin and foreign objects. The enclosure is fitted with lifting lugs.

Busbars

Busbars

The busbars consists of the following :

One set of 3 phase copper busbars

One number copper neutral bar having current rating equivalent to phase bar

One number copper earth bar for system earthing


On request the phase and neutral busbars are insulated with heat shrinkable tubings. Detachable
fuse holder housings are directly assembled on to the phase busbars.

(e.g. lighting, portable tools)

13 amps 3 pin switched socket outlet

Energy meter (option)

Major Compartments/Components

(1) Phase and Neutral Busbar

(2) Earth Busbar and Cable Clamp

(3) Incoming Units

(4) Outgoing Units

(5) Current Transformer

(6) Instrument Panel

Outgoing Units

Fuse unit consists of 3 nos. true grip type insulated fuse carriers to provide a hinge action at the
bottom contacts for circuit closing and to accommodate various ratings of J slotted pattern HRC
fuses (BS88-5). The neutral phase is provided with detachable hinge bolted type solid link.

Incoming Units

Link unit consists of 3 nos. through-grip type insulated link carriers to provide a hinge action at the
bottom contacts for circuit closing and to accommodate tinned solid copper links for the phases and
a detachable hinged bolted type solid link in the neutral. Alternatively, the J slotted pattern HRC
fuses can be accommodated upon request.

* Higher rating is available upon request.

Standards

EA Tech Specs 37-2 (LV Distribution Fuse board)

IEC 60439-1 (LV Switchgear and controlgear assemblies)

IEC 60269-1 (LV Fuses)