Professional Documents
Culture Documents
Function
Reset the frequency inverter to the condition at
delivery from the plant
Start quick commissioning
Check the parameter setting to suit the DIP switch:
Europe 60 Hz, power in hp
Rated motor voltage
Rated motor power
Rated motor frequency
Rated motor speed
Command source (USS)
Frequency setpoint source (USS)
Minimum motor frequency
Maximum motor frequency
Ramp-up time
Deceleration ramp
End of quick commissioning
Enable expert mode
Reference frequency
Data transmission rate: 57,600 b/s
Address (slave)
USS PZD length
USS PKW length
Communication monitoring:
Value 0 without monitoring
Back up data in EPROM
Parameter
P0010
P0970
P0010
P0100
Value
30
1
1
1
P0304
P0307
P0310
P0311
P0700
P1000
P1080
P1082
P1120
P1121
P3900
P0003
P2000
P2010
P2011
P2012
P2013
P2014
230 V
15 hp
60 Hz
1750 rev/min
5
5
0.0 Hz
60.0 Hz
10.0 s
10.0 s
1
3
60.0 Hz
9
1
2
4
115 ms
P0971
CONEXIONES
Adems como es terminacin de bus coloqu los dos INTERRUPTORES DIP en posicin ON