You are on page 1of 2

Water vapor saturation pressure check

enter T (K) 288.70556 K


ai
1
2
3
4
5
6
7

MW dry air
MW water

ai (T-273.15)i-1

6.1117675
0.4439861
1.43E-02
2.65E-04
3.02E-06
2.04E-08
6.39E-11

28.965
18.015
1 atm

6.1117675
6.90645
3.461537
0.997579
0.176972
0.01857
0.000905

Air Cooler
76.7 F
297.98333333 K
73.30 % humidity in
pw_v =

pw_v = 17.67378 mb(millibar)


pw_v = 0.017443 atm

0.022697313 atm (with humidity in)

lb dry air/lb total

0.9857610574

lbs dry air/s

143.91105158
2.0787402693

lbs water/s

Refrigeration Duty
h_in dry air
###
h_out dry air
###
Cp_water vapor
0.445
hv - hl (60F) =
1059.36

Btu/lb
Btu/lb
Btu/lb-F
Btu/lb
dQ/dt Air (out -in)
dry air
#MACRO? Btu/s
water
-15.448158311 Btu/s
condesation -518.86589397 Btu/s
Total duty

#MACRO? Btu/s
#MACRO? tons

145.5 lb/s
Air Cooler
60 F
288.70555556 K
100% humidity

% humidity in
pw_v =

atm (with humidity in)

0.017442664 atm

lb dry air/lb total

0.9890793923

lbs dry air/s

143.91105158 lb/s
1.5889484195 lb/s

lbs water/s

0.489792 lb/s
water condensation rate

You might also like