TM1600
Circuit Breaker Analyzer System
NOTICE OF COPYRIGHT & PROPRIETARY RIGHTS
2008, Programma Electric AB. All rights reserved.
The contents of this manual are the property of Programma Electric AB. No part of this work may be reproduced or transmitted in any form or by any means,
except as permitted in written license agreement with Programma Electric AB. Programma Electric AB has made every reasonable attempt to ensure the
completeness and accuracy of this document. However, the information contained in this manual is subject to change without notice, and does not represent
a commitment on the part of Programma Electric AB. Any attached hardware schematics and technical descriptions, or software listings that disclose source
code, are for informational purposes only. Reproduction in whole or in part to create working hardware or software for other than Programma Electric AB
products is strictly prohibited, except as permitted by written license agreement with Programma Electric AB.
TRADEMARK NOTICES
Megger and Programma are trademarks registered in the U.S. and other countries. All other brand and product names mentioned in this document are
trademarks or registered trademarks of their respective companies.
Programma Electric AB is certified according to ISO 9001 and 14001.
Programma Electric AB
Eldarvgen 4
Box 2970
SE-187 29 TBY
Sweden
Programma Electric AB
ZP-BL04E
Contents
1 Safety...............................................................................5
2 Power supply...................................................................5
3 TM1600 controls, indicators and terminals...................6
4 How to operate the breaker..........................................8
4.1 Safety.............................................................................8
4.2 Simple close or open operation.......................................9
4.3 Close-open (trip-free)......................................................9
4.4 Open-delay-close-open ..................................................9
4.5 Close-open-close............................................................9
4.6 How the TM1600 breaker operation unit operates........10
5 How to connect the timing channels to the breaker 12
5.1 Safety instructions.........................................................12
5.2 Single breaking unit per phase......................................13
5.3 Two or more breaking units in series per phase.............13
5.4 Single breaking unit with preinsertion resistor...............14
5.5 Two or more breaking units with preinsertion resistors..14
5.6 Preinsertion resistance less than 250 ohms....................15
5.7 Preinsertion resistance higher than 3000 ohms.............15
5.8 Live auxiliary contacts....................................................16
5.9 Coil control pulse..........................................................16
5.10 How the timing channels operate...............................17
6 How to measure............................................................18
6.1 Normal recording . .......................................................18
6.2 How to start timing from an arbitrary event .................18
Programma Electric AB
ZP-BL04E
1 Safety
Symbols on the instrument
Caution, refer to accompanying documents.
Warning
Before making any live connections to the TM1600, make sure
that it is connected to protective earth (ground), by the separate
ground cable.
When the TM1600 is connected to a wall socket, the socket must
be a grounded power outlet.
Follow local safety regulations for work on high-voltage circuit
breakers.
Before connecting the TM1600 to a high-voltage breaker, make
sure the breaker is closed and earthed (grounded) on at least one
side.
Never do any work on a circuit breaker unless the control circuits
of the breaker are disconnected from the TM1600 control outputs.
Disconnect all the connected leads and the power plug and then
turn off the power before dismounting any part of the TM1600.
Safety instructions
Important
Read the manual and comply with the following
instructions before using TM1600.
Always comply with local safety regulations.
Programma Electric AB
ZP-BL04E
2 Power supply
The TM1600 can be powered from any AC or DC source,
100-250 V. Power can also be supplied from the built-in, auto-charged batteries.
For charging time refer to section 9.2.
Battery operation time is typically at least one hour at normal use.
Programma Electric AB
ZP-BL04E
7. START of breaker operation and recording switch. Recording starts only if the Ready lamp is on. See sections
4.7 and 6.1.
17. TRIG OUT. Output for synchronous start of other equipment. Short-circuits the terminals at instant of triggering. Used when several TM1600s are used together. See
section 6.4.
12. READY for measuring button. Enables the timing channels. 1st touch: Prepares for normal recording. Enables
the timing channels throughout 90 s. 2nd touch: Provides
long-term monitoring (optional). See section 6.3. 3rd
touch: Disables recording.
Programma Electric AB
ZP-BL04E
Programma Electric AB
ZP-BL04E
4.4 Open-delay-close-open
1] Connect the breaker as shown in Fig. 4.2 or 4.3.
2] Select O-C-O on the SEQUENCE switch.
] Set the CLOSE DELAY to the desired value, 300 ms
(0.30) for example.
4] Set the OPEN DELAY to zero (0.00).
5] Start breaker operation with the START switch.
4.5 Close-open-close
1] Connect the breaker as shown in Fig. 4.2 or 4.3 with
one important difference: Interchange the wires
that run from the TM1600 to the coils.
Figure 4.3. Separate supply voltages.
Programma Electric AB
ZP-BL04E
Control pulses
The first pulse in a sequence is synchronized with time measurement.
Pulse delay (as set on the corresponding thumbwheel) is measured
from the start of the previous pulse.
A pulse lasts until the load is interrupted or until 320 ms has
elapsed. If no load is connected, the pulse lasts for 320 ms.
Programma Electric AB
ZP-BL04E
10
Main contact
a-contact
Trip pulse
Trip coil current
b-contact
Close pulse
Close coil current
1. The 300 ms delay of the close pulse is based on the beginning of the first trip pulse.
2. The second trip pulse starts simultaneously with the close pulse, since the delay time for
the trip pulse was set to zero.
Programma Electric AB
ZP-BL04E
11
Figure 5.1.
12
Figure 5.2.
Figure 5.3.
Programma Electric AB
ZP-BL04E
13
Figure 5.4.
14
15
Figure 5.8.
Figure 5.9.
Programma Electric AB
ZP-BL04E
16
Protection circuits
Measuring circuit
The measuring circuit can be set in three modes: Contact mode for
timing main contacts, Resistance mode for timing resistor contacts
and Voltage mode for detecting of a voltage.
Input mode
Short curcuit
current
Open circuit
voltage
Sense current
Max external
resistance
Voltage mode
120-180 mA
50-60 V
25-30 V
12-15 mA
80-100 mA
80-100 mA
3 kohms
250 ohms
The timing channels are active when the READY lamp is on. In normal
use, the Ready state lasts for 90 s.
In Resistance and Contact modes, an internal volage source drives a
current through a connected closed contact. The maximum current
is limited to a preset level. A rectifying diode is connected in series
with the voltage source. It permits one channel in Contact mode to
be connected in parallel with any number of channels in Resistance
mode.
In Voltage mode no internal voltage source is present. The load on
an external source is about 4-10 Watts. The input is not polarity
dependent.
Figure 5.10. Schematic diagram of one TM1600 timing channel in
Contact or Resistance mode.
Programma Electric AB
ZP-BL04E
17
6 How to measure
7 Printout
The desired report format can be selected with the PRINT MODE
switch.
Report No.
1
2
3
4
5
6
7
8
Format
Table of events in channel-number order. Graph of events,
compressed time scale.
Table of events in channel-number order.
Table of events in chronological order.
Graph of events, linear time scale. Overview with autoscale.
Optional
Static states of timing channel inputs.
MA61. Breaker summary + test diagram Built-in printer.
MA61. Breaker summary + test diagram External printer.
Programma Electric AB
ZP-BL04E
18
8 Paper reload
3]
4]
Paper feed is blocked when the paper runs out. Proceed as follows
to reload.
1]
2]
Programma Electric AB
ZP-BL04E
19
5]
6]
Put the printer back into its holder and make sure that it is
securely locked.
First check the output fuses. The fuses are rated 12 A, quick-acting,
ceramic type, 6 x 32 mm, Programma ordering No.33-07147. Do
not use fuses of any other type.
The breaker operation unit can be checked by connecting its outputs to a timing channel set in Contact mode. The pulse duration
will be approx. 320 ms if the load is low or if the load is not interrupted. The delay times can also be checked by means of a timing
channel.
Programma Electric AB
ZP-BL04E
20
Warning
It is absolutely necessary to have the TM1600
cover connected to earth (ground) during this
check. Use mains power that is galvanically isolated from earth (ground).
Programma Electric AB
ZP-BL04E
21
10 MA61
10.1 Control and front panel
1.
2.
3.
4.
5.
6.
7.
8.
9.
Transducer connections
Programma Electric AB
ZP-BL04E
22
Below closed
BR
Breaker mode
CHAN
CLS
Df
DISP
ENG
Language selection
FILE
GR21
GR22
GR23
I-SUMR
MON
NB
Non-breaker mode
OFF
ON
OPN
POS
PR
REP
SC
SETUP
SYS
System setup
X-GRP1
Programma Electric AB
ZP-BL04E
23
External printer
Olivetti JP 50
Kodak Diconix
1.1.14
ORG ?
OPERATOR ?
REFERENCE ?
TEST OBJECT
COMMENT
0 19
0 19
0 19
3 19
6 59
1.2
SYS: CONTR ENG
Jan011995 00:00
1
SETUP: PR REP SYS
MEAS.TIM: 1000ms
4
D 1000.0ms 916
4096mV 01010101
4.1
PR: 1000ms/d MOD
0000 - - > 1000 ms
2
PR: 500ms/d MOD
X-GRP1 ISUMR SC
SETUP PRINT FILE
DISP MON CHAN
5
E
TM1-8
9999.9 mm
0101 0101
4.1.1
16 OFF
POS 31
Programma Electric AB
ZP-BL04E
2.1
F' OFF
500m/s/d POS 16
2.2
At closing level
Df 010.0 10.0mm
2.2
BC 050.0 050.0mm
Df 010.0 010.0ms
3
DATA MEMORY: 1
SAVE
RECALL
6.1
A:STROKE 999.9mm
CLS 18.1 OPN 71.4%
Breaker Mode (BR)
6
Channel:
CLS OPN
A
BR
Channel:
Channel:
NonBreaker Mode (NB)
6.2
A:-4/+4 Z-9999mV
-9999.999 mm /V
Channel:
Channel:
Channel:
CLS OPN
E
F
NB
24
A
BR
2.2
AT CLOSING LEVEL
Df 010.0 010.0 mm
POS 31
1] When you enter the DISP menu, the time is set for
Programma Electric AB
ZP-BL04E
26
provides a print-out that covers the interval between the displayed time values.
] Move the cursor to the MOD field. Enter the
MOD(ify) menu.
4] Select a small print scale factor to magnify the curve.
Set the open level to POS(ition) 2, so that you will be
able to see the whole curve.
4.1.1
A ON
10 mm/d
POS 2
4
A 42.0 ms
1-8
132 mm 1110 0000
27
12 Supplement
For software revision R04A (TM1600) + R06A (MA61) and onwards.
Note If you have changed the date or time, use the ENTER
button to leave the menu.
Programma Electric AB
ZP-BL04E
order.)
] Set channel A to BR mode. Refer to section 11.2 for
further motion parameters. Set channel B and C to
NB mode.
B: 0/+1 Z+000mV
+1000.000 mV/V
Programma Electric AB
ZP-BL04E
29
13 Printout example
Programma Electric AB
ZP-BL04E
30
Subject to change without notice. Printed matter No. ZP-BL04E Doc BL0485EE 2008