The document provides specifications for a 20 pair steel wire armoured instrumentation cable. It specifies that the cable contains 20 twisted pairs of 7/0.53mm diameter solid copper conductors with polyethylene insulation, aluminum-polyester tape screening, solid polyethylene bedding, galvanized steel wire armouring, fire retardant black PVC sheathing. Key specifications include a minimum bending radius of 6 times the cable diameter, maximum conductor resistance of 13 ohms/km, minimum insulation resistance of 5000 megohms/km, maximum capacitance of 115pF/m, maximum temperature rating of 65°C, and maximum voltage rating of 300/500V RMS.

Uploaded by

amilasri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
184 views2 pages

Specification For Control Cables

The document provides specifications for a 20 pair steel wire armoured instrumentation cable. It specifies that the cable contains 20 twisted pairs of 7/0.53mm diameter solid copper conductors with polyethylene insulation, aluminum-polyester tape screening, solid polyethylene bedding, galvanized steel wire armouring, fire retardant black PVC sheathing. Key specifications include a minimum bending radius of 6 times the cable diameter, maximum conductor resistance of 13 ohms/km, minimum insulation resistance of 5000 megohms/km, maximum capacitance of 115pF/m, maximum temperature rating of 65°C, and maximum voltage rating of 300/500V RMS.

Uploaded by

amilasri
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

SPECIFICATIONS FOR A 20 PAIR STEEL WIRE ARMOURED

INSTRUMENTATION CABLE

Standard

: BS 5308 : Part 1

Number of pairs/
Conductor Type

: 20 Nos twisted pairs of stranded 7/0.53mm diameter solid plain


annealed copper conductor as per BS 6360

Min bending radius

: 6 x Overall diameter

Max Conductor resistance

: 13 /km at 200C

Min insulation resistance

: 5000 M/km at 200C

Max mutual capacitance

: 115 pF/m at 1 kHz

Max L/R ratio

: 40 H/

Insulation

: Polyethylene as per BS 6234

Screen

: Collectively screened with Aluminum-Polyester tape

Bedding

: Solid Polyethylene as per BS 6234

Armouring

: Galvanized Mild Steel Wire as per BS 1142/BS EN 10257-1

Sheathing

: Fire Retardant Black color PVC as per BS 7655

Cable Identification

: Each pair shall be clearly numbered & color coded for easy
identification

Max operating Temperature : 650C


Max working Voltage

: 300/500V r.m.s.

Test voltage

: 1000V r.m.s. between conductors and between conductors


and screen/armour

SPECIFICATIONS FOR A SINGLE PAIR STEEL WIRE ARMOURED


INSTRUMENTATION CABLE

Standard

: BS 5308 : Part 1

Number of pairs/
Conductor Type

: 01 No twisted pair of stranded 7/0.53mm diameter solid plain


annealed copper conductor as per BS 6360

Min bending radius

: 6 x Overall diameter

Max Conductor resistance

: 13 /km at 200C

Min insulation resistance

: 5000 M/km at 200C

Max mutual capacitance

: 115 pF/m at 1 kHz

Max L/R ratio

: 40 H/

Insulation

: Polyethylene as per BS 6234

Screen

: Screened with Aluminum-Polyester tape

Bedding

: Solid Polyethylene as per BS 6234

Armouring

: Galvanized Mild Steel Wire as per BS 1142/BS EN 10257-1

Sheathing

: Fire Retardant Black color PVC as per BS 7655

Cable Identification

: Each pair shall be clearly numbered & color coded for easy
identification

Max operating Temperature : 650C


Max working Voltage

: 300/500V r.m.s.

Test voltage

: 1000V r.m.s. between conductors and between conductors


and screen/armour