Winding Visual inspection; measure insulation resistance, Terminal box; grounding connection Clean inside of terminal box; refasten bolts,function test RCU, Temperature monitoring of bearings and windings, Record and trend all three phase currents and verify the currents are balanced and do not exceed nameplate rating. Perform IR check between motor leads and ground. This determines condition of the ground insulation. MOV Visually inspect for any electrical or mechanical damage. Replace worn or damaged components. Open electrical enclosure. Inspect & tighten all electrical connections. Check lubrication consistency and level. Fill or replace if required,FUNCTION TEST,CLEAN THE ELECTRICAL TERMINAL BOX. IR check between motor leads and ground,check the open close indication and position switch, torque setting. Lighting Clean bulbs and fixtures with soft moist cotton cloth, soft-bristled anti-static brush, or low-power vacuum cleaner. Check the Exit and Emergency lighting function.check the photocell function, change the defective bulb, starter and ballast. Record the replacement of faulty lamps and the replacement of any fittings, Record details of the test, cleaning and correct operation of the system