Specifier's comments:
1 Input data
Anchor type and diameter:
Material:
8.8
ETA 12/0084
Issued I Valid:
4/15/2015 | 4/15/2020
Proof:
Stand-off installation:
eb = 0 mm (no stand-off); t = 50 mm
Anchor plate:
Profile:
Base material:
cracked concrete, C40/50, fcc = 50.00 N/mm2; h = 10000 mm, Temp. short/long: 30/40 C
Installation:
Reinforcement:
no reinforcement or reinforcement spacing >= 150 mm (any ) or >= 100 mm ( <= 10 mm)
no longitudinal edge reinforcement
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Page:
Project:
Sub-Project I Pos. No.:
Date:
2
11/22/2015
Shear force y
0.000
0.000
0.000
0.000
4
Compression
Tension
1
Capacity [kN]
299.333
Utilization bN [%]
98
Status
OK
479.968
501.045
96
OK
479.968
586.109
82
OK
N/A
N/A
N/A
N/A
Steel Strength*
Splitting failure**
* anchor having the highest loading
gM,s
1.500
NRd,s [kN]
299.333
NSd [kN]
290.407
A0p,N [mm2]
720000
2
tRk,ucr,25 [N/mm ]
15.00
scr,Np [mm]
849
ccr,Np [mm]
424
yc
1.079
2
tRk,cr [N/mm ]
8.09
k
2.300
yg,Np
1.384
yg,Np
1.156
ec1,N [mm]
41
yec1,Np
0.912
ec2,N [mm]
41
yec2,Np
0.912
ys,Np
1.000
N0Rk,p [kN]
457.717
NRk,p [kN]
751.567
gM,p
1.500
NRd,p [kN]
501.045
NSd [kN]
479.968
cmin [mm]
850
yre,Np
1.000
A0c,N [mm2]
3240000
ccr,N [mm]
900
scr,N [mm]
1800
ec1,N [mm]
41
yec1,N
0.957
ec2,N [mm]
41
yec2,N
0.957
N0Rk,c [kN]
748.246
gM,c
1.500
NRd,c [kN]
586.109
NSd [kN]
479.968
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
ys,N
0.983
yre,N
1.000
k1
7.200
www.hilti-me.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Page:
Project:
Sub-Project I Pos. No.:
Date:
3
11/22/2015
Capacity [kN]
N/A
Utilization bV [%]
N/A
Status
N/A
N/A
N/A
N/A
N/A
Pryout Strength*
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
215.117 [kN]
VSk
0.000 [kN]
dN
0.380 [mm]
dV
0.000 [mm]
dNV
0.380 [mm]
dN
0.837 [mm]
dV
0.000 [mm]
dNV
0.837 [mm]
215.117 [kN]
VSk
0.000 [kN]
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
6 Warnings
Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!
Input data and results must be checked for agreement with the
existing conditions and for plausibility!
Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger
diameters of the clearance hole see Chapter 1.1. of EOTA TR029!
The design method ETAG (filled holes) assumes that no hole clearance between the anchors and the fixture is present. This can
be
achieved by filling the gap with mortar of sufficient compressive strength (e.g. by using the Hilti Dynamic Set) or by other suitable means
The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
Bore hole cleaning must be performed according to instructions for use (blow twice with oil-free compressed air (min. 6 bar), brush twice,
blow twice with oil-free compressed air (min. 6 bar)).
Characteristic bond resistances depend on short- and long-term temperatures.
Please contact Hilti to check feasibility of HIT-V rod supply.
Edge reinforcement is not required to avoid splitting failure
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Page:
Project:
Sub-Project I Pos. No.:
Date:
11/22/2015
7 Installation data
Anchor plate, steel: Custom; E = 210000.00 N/mm2; fyk = 275.00 N/mm2
Profile: Square hollow; 250 x 250 x 16 mm
Hole diameter in the fixture: df = 33 mm
Plate thickness (input): 50 mm
Recommended plate thickness: calculated (46 mm)
Cleaning: Premium cleaning of the drilled hole is required
Cleaning
Compressed air with required
accessories to blow from the bottom of
the hole
Proper diameter wire brush
y
200
50
200
Setting
Dispenser including cassette and mixer
Dynamic set
Torque wrench
300
200
200
2
50
50
300
x
-150
150
-150
150
y
-150
-150
150
150
c-x
9850
10150
9850
10150
c+x
1150
850
1150
850
c-y
-
c+y
10150
10150
9850
9850
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
50
www.hilti-me.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Page:
Project:
Sub-Project I Pos. No.:
Date:
5
11/22/2015
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan