Type CDG 11
Overcurrent and Earthfault Relay
CDG 11
drawn out from the case
Features
General description
Identical time/current
Application
Selective phase and earthfault
protection, in time graded systems
for AC machines, transformers,
feeders etc.
Technical data
Current ratings
1A or 5A.
Figure 1:
Time-current characteristic
inverse time relay CDG11 1.3 sec.
IDMT settings
Starting current
103 - 105% of current setting.
Closing current
Not more than 130% of current
setting.
Instantaneous highset settings
Thermal rating
Time settings
Operating time
0 - 3 seconds or at 10 times
0 - 1.3 seconds current setting.
Time/current characteristics given in
Figures 1 and 2.
Resetting time
4 seconds for 1.3
seconds relay.
9 seconds for 3
seconds relay.
with time
multiplier
at 1.0.
Accuracy
Overshoot
Overshoot time on removal of
20 times setting current.
Frequency error
Figure 2:
Time-current characteristic
inverse time relay CDG11 3 sec.
Approximate
Case
size
Height
mm
Width
mm
Depth*
mm
gross weight
Kg.
1D Vert.
233
170
203
6.0
3D Horz.
233
454
203
15.5
3D Vert.
524
170
203
15.0
Figure 3:
Impedance/Current Curves for type CDG relays
2.5-10 AMP 3 VA 50 Cycle Multi-strand Coil
Figure 4:
Typical external and internal connections
for type CDG 31 relay
ALSTOM Limited Pallavaram Works: 19/1, GST Road, Pallavaram, Chennai-600 043. India.
Tel: 91-044-2368621 Fax: 91-044-2367276 Email: plw.applications@alstom.sprintrpg.eml.vsnl.net.in.
1998 ALSTOM Limited
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should
only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
ALSTOM Limited cannot be held responsible for any reliance on any decision taken on its contents without specific advice
PR:010:0799:A
Printed in India.