Section Three

Low Voltage Cables

FOUR CORE AL XLPE URD CABLES


Circular construction
Aluminium conductor
XLPE insulation
PVC sheath
Current ratings (A) and voltage drops (mV/A.m)

Product Sheet No. 171-04 B


Conductor
Size
(mm2)

(A)

(mV/A.m)

(A)

(mV/A.m)

(A)

(mV/A.m)

(A)

(mV/A.m)

50

143

1.43

154

1.43

170

1.43

128

1.43

70

182

0.993

196

0.993

209

0.993

161

0.993

95

224

0.723

242

0.723

250

0.723

194

0.723

120

262

0.577

282

0.577

286

0.577

225

0.577

185

347

0.388

374

0.388

364

0.388

291

0.388

240

413

0.307

446

0.307

423

0.307

345

0.307

300

475

0.258

514

0.258

477

0.258

391

0.258

Issue: January 2012


0.6/1 kV. Made to AS 4026
Note:
Content from AS/NZS 3008.1.2:2010 has been reproduced with the permission from Standards New Zealand under
Copyright Licence 000926. Please see the Standard for full details.
The values in this table are for typical New Zealand installation conditions of:Ambient Air Temperature
30C
Soil Temperature
15C
Soil Thermal Resistivity
1.2 K.m/W
Depth of Burial
0.5 m