Professional Documents
Culture Documents
Section Three
CURRENT RATINGS
Copper conductors
PVC insulation
Armoured or unarmoured -(including Neutral Screened cables)
Table 3.11 Two Conductor Cu PVC Cables Single Phase Ratings (A)
Conductor
Size
(mm2)
17
16
15
13
11
19
19
1.5
22
21
18
16
15
10
23
23
2.5
31
30
26
23
22
15
33
33
42
39
34
31
27
19
43
43
52
50
44
40
35
25
55
55
10
73
68
59
55
48
34
73
73
16
97
91
78
73
62
46
125
95
25
129
122
103
97
82
60
162
123
35
158
149
128
120
103
74
196
150
50
194
181
152
145
122
232
178
70
245
229
194
184
155
285
222
95
302
283
233
226
186
342
267
120
350
328
275
262
219
391
310
150
400
374
309
300
247
438
349
185
459
430
357
344
285
494
399
240
544
508
415
407
332
572
463
300
624
583
483
466
388
645
531
400
719
671
549
537
440
729
603
Note:
Content from AS/NZS 3008.1.2:2010 has been reproduced with the permission from Standards New Zealand under
Copyright Licence 000926. Please see the Standard for full details.
The values in this table are for typical New Zealand installation conditions of:Ambient Air Temperature
30C
Soil Temperature
15C
Soil Thermal Resistivity
1.2 K.m/W
Depth of Burial
0.5 m
Section 3, Page 81