Section Three
CURRENT RATINGS
Copper conductor
PVC insulation
Unarmoured
Sheathed or unsheathed
Table 3.15 Single Conductor Cu PVC Cables Three Phase Ratings (A)
Conductor
Size
(mm2)
18
16
15
14
11
18
18
21
1.5
23
19
18
17
14
22
22
26
2.5
33
29
26
24
19
14
30
30
36
43
38
35
32
26
18
40
40
47
56
48
46
40
32
23
50
50
58
10
76
66
62
54
42
31
65
65
77
16
101
88
82
71
57
41
114
86
99
25
137
117
111
92
73
55
147
110
129
35
169
145
136
114
91
67
176
134
154
50
206
178
166
136
108
209
158
185
70
262
225
210
173
139
256
198
226
95
327
280
262
209
168
307
239
275
120
382
327
304
247
197
349
277
311
150
439
376
351
278
222
392
311
349
185
510
437
407
324
259
442
358
402
240
610
521
486
377
302
512
415
464
300
707
603
561
442
355
576
477
537
400
828
701
653
504
402
652
541
608
500
964
809
754
596
477
735
628
705
630
1129
931
866
670
537
823
703
795
Note:
Content from AS/NZS 3008.1.2:2010 has been reproduced with the permission from Standards New Zealand under
Copyright Licence 000926. Please see the Standard for full details.
The values in this table are for typical New Zealand installation conditions of:Ambient Air Temperature
30C
Soil Thermal Resistivity
Soil Temperature
15C
Depth of Burial
1.2 K.m/W
0.5 m
Section 3, Page 85