You are on page 1of 1

Section Three

Low Voltage Cables

SINGLE CORE CU CANTOL CABLES


Circular construction
Copper conductor
XLPE insulation
PVC sheath
Current ratings (A) and voltage drops (mV/A.m)

Product Sheet No. 120-01 B


Conductor
Size
(mm2)

(A) (mV/A.m) (A) (mV/A.m) (A) (mV/A.m) (A) (mV/A.m) (A) (mV/A.m) (A) (mV/A.m) (A) (mV/A.m)

16

95

2.95

95

2.55

101

2.55

149

2.95

125

2.55

107

2.95

925

2.55

25

129

1.87

129

1.62

138

1.62

192

1.87

162

1.62

140

1.87

121

1.62

35

158

1.35

158

1.18

169

1.17

230

1.35

193

1.17

168

1.35

147

1.17

50

194

1.01

194

0.878

207

0.872

273

1.01

229

0.872

202

1.01

174

0.872

70

246

0.710

246

0.623

264

0.615

335

0.710

280

0.615

249

0.710

217

0.615

95

306

0.528

306

0.467

328

0.457

401

0.528

335

0.457

305

0.528

261

0.457

120

358

0.431

358

0.385

384

0.373

457

0.431

381

0.373

348

0.431

304

0.373

150

413

0.365

413

0.330

443

0.316

514

0.365

428

0.316

391

0.365

342

0.316

185

480

0.311

479

0.285

515

0.269

581

0.311

484

0.269

453

0.311

388

0.269

240

574

0.262

573

0.245

616

0.227

674

0.262

560

0.227

532

0.262

456

0.227

300

666

0.233

662

0.222

713

0.202

761

0.233

630

0.202

601

0.233

525

0.202

400

779

0.211

772

0.205

832

0.183

865

0.211

715

0.183

699

0.211

596

0.183

500

903

0.196

893

0.193

961

0.170

977

0.196

805

0.170

791

0.196

693

0.170

630

1045

0.184

1032

0.182 1111 0.159

1098

0.184

902

0.159

916

0.184

778

0.159

Issue: January 2012


0.6/1 kV. Made to AS/NZS 5000.1
Note:
Content from AS/NZS 3008.1.2:2010 has been reproduced with the permission from Standards New Zealand under
Copyright Licence 000926. Please see the Standard for full details.
The values in this table are for typical New Zealand installation conditions of:Ambient Air Temperature
30C
Soil Temperature
15C
Soil Thermal Resistivity
1.2 K.m/W
Depth of Burial
0.5 m

Section 3, Page 48